PROGRAMMING

See flowchart on page 8

NOTE: 

The

 

 

arrow moves down the menu and the

  

arrow moves to the right for the next selection

Basic Programming Menu

Unit of measure and set-points

To use the product as a basic switch, Excela programming is simple:
• 

Enter the basic programming mode by pressing the 

o

 

and

 

g

 

buttons simultaneously.

• 

The display will scroll “SET UNITS”.and allow you to select the unit of  measure. After the selection pressing 
the

 

o

 

arrow displays SW.

Note: Whenever the unit of measure is changed, Min/Max memory is reset but trip count will not be reset.

Note: Trip count is reset when power to the unit is disconnected (e.g., power cycle).

• 

The SW screen allows you to set rise and fall settings by changing each digit on the display.

• 

Set-points can be separated from 1% to 99% of  range.

• 

If  the unit has negative  range capability then a – or + option will be offered.  Otherwise it is always positive.

• 

Returning to the SW screen allows you to either save your settings and resume operation or move into the 
advanced menu settings.

• 

See programming flowchart on page 8 for saving settings.

Advanced Programming Menu
NOTE: 

No initial configuration of  these features is required.  The default for these advanced 

commands is zero or off.

Press the

 

o

 

and

 

g

 

buttons simultaneously; press the

 

o

 

to get to the SW .At this point press

 

o

 

and

 

g

 

buttons 

simultaneously to get into the advanced menu, which starts with the LED FLIP display.

Advanced Menu List

• 

LED FLIP – Changes LED color from Red to Green when switch trips

• 

PASSWRD – Add your own 4-digit password for security

• 

OFST – Allows low range value offset by +/- 10%

• 

SPAN – Change the high end by +/- 10%

• 

LCH1 – Latch switch output on rise – needs to be reset manually

• 

PLUG PORT – Monitors pressure fluctuations in process - 1 min; 1 hr; 24 hr.

• 

FILTER – Smoothens transient pressure spikes - Programmable from 1/4 to 2 seconds 

• 

TRIP DELAY – Like a switch timer – delay trip up to 999.9 seconds

LED FLIP:  LED LIGHT COLOR REVERSAL:

This function allows you to reverse the LED color logic to match your process (i.e., rise or fall application). 

Set to RED:

 This is for applications on the rise.  The GREEN LED will flash in normal operating condition.  Above the 

rise setpoint the LED will flash RED and it will revert to GREEN once it is below the fall setpoint.

Set to GREEN:

 This is for applications on the fall.  The GREEN LED will flash in normal operating condition.  Below 

the fall setpoint, the LED will flash RED and it will revert to GREEN once it is above the rise setpoint.

PASSWORD:

The Excela allows you to enable password protection to make any adjustments to the unit’s operation.  Once acti-

vated and saved through the advanced programming menu, it becomes the key to all subsequent changes to the 

unit’s operational settings.  Make sure you remember the password, since it will be required for all future changes.  

NOTE: 

Password 0000 is not an acceptable password.

You can also deactivate it from the advance-programming menu if you decide it is no longer needed.  

If you lose your password and need to access the programming menu, contact UE ([email protected];  

+1 617-923-6977) and we can give you a one-time password to enter the programing mode.

Basic Programming 

Video

Advanced Programming 

Video

Summary of Contents for Excela 1GSWLL

Page 1: ... TO PREVENT MOISTURE FROM ENTERING ENCLOSURE DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS FOR DIFFERENTIAL PRESSURE MODELS ESPECIALLY LOW RANGE UNITS MOUNT THE SENSOR LEVEL TO MINI MIZE ANY PRESSURE READING OFFSETS THE OFFSET COMMAND MAY BE USED TO ZERO THE DISPLAY SEE PAGE 5 FOR ADDITIONAL INFORMATION Excela is rated for both indoor and outdoor operation IP66 and Nema 4X w...

Page 2: ...power supply use the test resistor supplied 1 8K Ω with the unit Loosen the four 4 Phillips head screws holding the faceplate to the enclosure Gently remove the faceplate module Dis connect the 8 wire connector from the faceplate to allow easy wiring Pass the wires through the conduit connector and connect to the terminal block You can wire the unit as a Normally Open or a Normally Closed switch T...

Page 3: ...ax process values and the number of switch trips The dis play will revert back to the Process Display mode after scrolling Note While scrolling you can clear the values by pushing the right g arrow Pushing the right g button once the display will scroll setpoint Rise and Fall The display will revert back to the Process Display mode after scrolling ALARM CONDITION When the process goes beyond the R...

Page 4: ...when switch trips PASSWRD Add your own 4 digit password for security OFST Allows low range value offset by 10 SPAN Change the high end by 10 LCH1 Latch switch output on rise needs to be reset manually PLUG PORT Monitors pressure fluctuations in process 1 min 1 hr 24 hr FILTER Smoothens transient pressure spikes Programmable from 1 4 to 2 seconds TRIP DELAY Like a switch timer delay trip up to 999 ...

Page 5: ...mit Span 400 404 x 450 446 rounded LATCH MODE Similar to Manual Reset on mechanical switch The switch output can be configured to latch when the setpoint is reached on rising set point only Set Latching Mode In the Programming Mode set LCH1 to ON When the set point is crossed on increasing process parameter the switch will latch and will remain in the latched state until it is manually reset by th...

Page 6: ...easure the voltage drop across the switch connected to the terminal block A properly functioning Excela electronic switch will exhibit the following voltage levels Model Voltage when switch is open Voltage when switch is closed 1GSWLL 8 50 VDC 5 VDC DISPLAY MODULE CALIBRATION The Serial on the module and the enclosure must match for proper operation Swapping modules among similar ranges would resu...

Page 7: ...d clear the error and operate normally If error continues check for sensor damage due to over range exposure Overrange Process input is above 103 of range PRESSURE and TEMPERATURE above range value Automatic Reset when process variable returns to normal Underrange Process input is be low 1 25 of range PRESSURE and TEMPERATURE below range value Automatic Reset when process variable returns to norma...

Page 8: ...RD CONFIRM PWORD PWORD CONFIRMED IF ON SET BLINKING DIGIT IF OFF DISCARD NEW PWORD POS NEG 8888 POS NEG ON OFF 8888 Both FILTER NOTE while scrolling pressing the right arrow will clear MAX MIN TRIPS values Advanced Menu OFF 1 4S 1 2S 1Sec 2Sec OFF and 1 4 Sec settings not available on temperature models TRIP DELAY ON OFF 8888 ON OFF SAVE CHNG NOTE Ifentriesareoutofrange ERR messagewillflashonscree...

Page 9: ...IM_1GSW 02 www ueonline com 9 DIMENSIONAL DRAWINGS Model 1GSWLL Gauge Pressure Sensor Model 1GSWLL Differential Pressure Sensor ...

Page 10: ...IM_1GSW 02 www ueonline com 10 Model 1GSWLL Temperature Model R Sensor Model 1GSWLL Temperature Model L Sensor ...

Page 11: ...ight arrow button and continue to record new min max values 4 Press the right key to display the switch setpoints Verify that the setpoints are correct 5 To confirm process display on Excela connect calibration gauge to the Excela and verify that both displays match within tolerance If minor adjustment is needed up to 10 of range use the offset and span features within Excela s advanced programmin...

Page 12: ...be used to zero the display see page xx for additional information Pour les modèles de pression différentielle de pressions faibles montez le niveau du capteur afin de minimiser tout décalage de lecture de pression La commande décalée peut être utilisée pour mettre l affichage à zéro voir la page xx pour plus d informations 1 Never insert any object into the pressure sensor opening Damage to the s...

Page 13: ...sonnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery...

Reviews: