background image

IM_1GSW-02

www.ueonline.com

2

Local and Remote Temperature Models

For Immersion Sensing: Use of a thermowell is highly recommended to aid in maintenance. Insert the sensor housing (0.25” 

diameter) into the well ensuring that the housing bottoms out and will be completely immersed in the media (2.5” min.) Secure 

the sensor using an appropriately sized compression fitting or union connector. Refer to options W073, W074 and W080 in the 

Excela technical brochure. 

For Surface Sensing: Secure the sensor housing to the pipe or vessel using an adhesive or strapping method suitable for the 

application.

WIRING

Tools Required

Phillips-head screwdriver

Wire strippers

ALL MODELS ACCEPT 8-50 VDC DISCRETE POWER SOURCE DIRECTLY FROM DIGITAL INPUTS of PLCs, DCSs AND OTHER 

LOW-POWER DC LOADS. THE SWITCHED OUTPUT MAXIMUM LOAD RATING IS 0.1A. OVERLOADING THE SWITCH MAY 

CAUSE FAILURE.

THE DEVICES SHALL BE PROPERLY GROUNDED IN THE END USE APPLICATION.

THE INPUT POWER SHALL BE NEC/CEC CLASS 2, UL/CSA/IEC 60950 LPS OR UL/CSA/IEC 61010 LIMITED ENERGY

LEADWIRES MUST BE RATED 105°C MINIMUM.  FOR AMBIENT TEMPERATURES BELOW -10°C, USE SUITABLE FIELD WIRING.

Excela is powered through the residual current of the PLC

 Note: For bench testing using a 24 VDC power supply, use the test resistor supplied (1.8K Ω) with the unit.

•  Loosen the four (4) Phillips-head screws holding the faceplate to the enclosure. Gently remove the faceplate module. Dis-

connect the 8 wire connector from the faceplate to allow easy wiring.

•  Pass the wires through the conduit connector and connect to the terminal block.  You can wire the unit as a Normally 

Open or a Normally Closed switch.

Terminal Block Wiring

•  Excela’s terminal block is marked Common (COM), Normally Closed (NC) and Normally Open (NO)

•  If replacing a mechanical switch, match the wiring to make it simple.

•  The unit is not polarity sensitive and mimics a mechanical SPDT switch operation

•  Terminal block accepts 12-24 AWG wiring. 

•  Reconnect the 8 wire connector to the faceplate which is keyed and can only be connected one way.

•  Place the faceplate back on the enclosure and re-attach using the (4) Phillips screws (4 in-lbs or 0.45 N-m). DO NOT OVER-

TIGHTEN.

 

Wiring configurations

The signal output of the Excela mimics that of a single pole double throw (SPDT) mechanical switch. When connecting the 

Excela to a programmable logic controller (PLC), this is the signal the PLC sees coming from the Excela:

When wiring Normally Open (NO) and Common (COM)

•  PLC sees open circuit below setpoint 

•  PLC sees closed circuit above setpoint 

When wiring Normally Close (NC) and Common (COM)

•  PLC sees closed circuit below setpoint

•  PLC sees open circuit above setpoint

Wiring and 

Setup Video

Summary of Contents for Excela 1GSWLL

Page 1: ... TO PREVENT MOISTURE FROM ENTERING ENCLOSURE DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS FOR DIFFERENTIAL PRESSURE MODELS ESPECIALLY LOW RANGE UNITS MOUNT THE SENSOR LEVEL TO MINI MIZE ANY PRESSURE READING OFFSETS THE OFFSET COMMAND MAY BE USED TO ZERO THE DISPLAY SEE PAGE 5 FOR ADDITIONAL INFORMATION Excela is rated for both indoor and outdoor operation IP66 and Nema 4X w...

Page 2: ...power supply use the test resistor supplied 1 8K Ω with the unit Loosen the four 4 Phillips head screws holding the faceplate to the enclosure Gently remove the faceplate module Dis connect the 8 wire connector from the faceplate to allow easy wiring Pass the wires through the conduit connector and connect to the terminal block You can wire the unit as a Normally Open or a Normally Closed switch T...

Page 3: ...ax process values and the number of switch trips The dis play will revert back to the Process Display mode after scrolling Note While scrolling you can clear the values by pushing the right g arrow Pushing the right g button once the display will scroll setpoint Rise and Fall The display will revert back to the Process Display mode after scrolling ALARM CONDITION When the process goes beyond the R...

Page 4: ...when switch trips PASSWRD Add your own 4 digit password for security OFST Allows low range value offset by 10 SPAN Change the high end by 10 LCH1 Latch switch output on rise needs to be reset manually PLUG PORT Monitors pressure fluctuations in process 1 min 1 hr 24 hr FILTER Smoothens transient pressure spikes Programmable from 1 4 to 2 seconds TRIP DELAY Like a switch timer delay trip up to 999 ...

Page 5: ...mit Span 400 404 x 450 446 rounded LATCH MODE Similar to Manual Reset on mechanical switch The switch output can be configured to latch when the setpoint is reached on rising set point only Set Latching Mode In the Programming Mode set LCH1 to ON When the set point is crossed on increasing process parameter the switch will latch and will remain in the latched state until it is manually reset by th...

Page 6: ...easure the voltage drop across the switch connected to the terminal block A properly functioning Excela electronic switch will exhibit the following voltage levels Model Voltage when switch is open Voltage when switch is closed 1GSWLL 8 50 VDC 5 VDC DISPLAY MODULE CALIBRATION The Serial on the module and the enclosure must match for proper operation Swapping modules among similar ranges would resu...

Page 7: ...d clear the error and operate normally If error continues check for sensor damage due to over range exposure Overrange Process input is above 103 of range PRESSURE and TEMPERATURE above range value Automatic Reset when process variable returns to normal Underrange Process input is be low 1 25 of range PRESSURE and TEMPERATURE below range value Automatic Reset when process variable returns to norma...

Page 8: ...RD CONFIRM PWORD PWORD CONFIRMED IF ON SET BLINKING DIGIT IF OFF DISCARD NEW PWORD POS NEG 8888 POS NEG ON OFF 8888 Both FILTER NOTE while scrolling pressing the right arrow will clear MAX MIN TRIPS values Advanced Menu OFF 1 4S 1 2S 1Sec 2Sec OFF and 1 4 Sec settings not available on temperature models TRIP DELAY ON OFF 8888 ON OFF SAVE CHNG NOTE Ifentriesareoutofrange ERR messagewillflashonscree...

Page 9: ...IM_1GSW 02 www ueonline com 9 DIMENSIONAL DRAWINGS Model 1GSWLL Gauge Pressure Sensor Model 1GSWLL Differential Pressure Sensor ...

Page 10: ...IM_1GSW 02 www ueonline com 10 Model 1GSWLL Temperature Model R Sensor Model 1GSWLL Temperature Model L Sensor ...

Page 11: ...ight arrow button and continue to record new min max values 4 Press the right key to display the switch setpoints Verify that the setpoints are correct 5 To confirm process display on Excela connect calibration gauge to the Excela and verify that both displays match within tolerance If minor adjustment is needed up to 10 of range use the offset and span features within Excela s advanced programmin...

Page 12: ...be used to zero the display see page xx for additional information Pour les modèles de pression différentielle de pressions faibles montez le niveau du capteur afin de minimiser tout décalage de lecture de pression La commande décalée peut être utilisée pour mettre l affichage à zéro voir la page xx pour plus d informations 1 Never insert any object into the pressure sensor opening Damage to the s...

Page 13: ...sonnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery...

Reviews: