Excela™ Electronic Pressure and 

Temperature Switches

Discrete Input Powered

U N I T E D   E L E C T R I C 
C O N T R O L S

Installation and Maintenance 

Instructions

IM_1GSW-02

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of 
Recommended Practices, Liabilities and Warranties.

GENERAL (MOUNTING and WIRING) 

MISUSE OF THIS PRODUCT MAY CAUSE PERSONAL INJURY.  THESE INSTRUCTIONS MUST BE THOROUGHLY 

READ AND UNDERSTOOD BEFORE UNIT IS INSTALLED.  SEE PRODUCT NAMEPLATE INFORMATION FOR SPE-

CIFIC AGENCY CERTIFICATIONS APPLICABLE TO YOUR PRODUCT.

CONTINUOUS OPERATION SHOULD NOT EXCEED THE DESIGNATED OVER RANGE PRESSURE OR WORKING 
PRESSURE RANGE STATED WITHIN THE LITERATURE AND ON DEVICE NAMEPLATE.

INSTALLATION

Tools Required

    1-1/16” wrench for sensor hex fitting 

screwdriver for mounting bolts

2 mounting bolts (1/4” Max.)

MOUNTING

FOR PRESSURE AND LOCAL TEMPERATURE MODELS, ALWAYS HOLD A WRENCH ON THE SENSOR HEX WHEN 

MOUNTING UNIT. DO NOT TIGHTEN BY TURNING ENCLOSURE. THIS WILL DAMAGE THE CONNECTION BETWEEN 

THE SENSOR AND HOUSING.

INSTALL UNITS WHERE SHOCK, VIBRATION AND TEMPERATURE FLUCTUATIONS ARE MINIMAL. ORIENT UNIT 

MAKING SURE THAT THE ELECTRICAL CONDUIT CONNECTION IS NOT FACING UP, TO PREVENT MOISTURE FROM 

ENTERING ENCLOSURE. DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS.

FOR DIFFERENTIAL PRESSURE MODELS (ESPECIALLY LOW RANGE UNITS), MOUNT THE SENSOR LEVEL TO MINI-
MIZE ANY PRESSURE READING OFFSETS. THE OFFSET COMMAND MAY BE USED TO ZERO THE DISPLAY (SEE 
PAGE 5 FOR ADDITIONAL INFORMATION). 

 

  

Excela is rated for both indoor and outdoor operation, IP66 and Nema 4X, with a temperature rating of  -40°C to 71°C

• 

Surface mount the unit using the two (2) 1/4” clearance holes in the mounting ears

• 

Pressure and Differential Pressure units can be mounted directly to process connections if  they are able to sup-

port the product.

• 

To pipe mount: Thread the pressure connection onto the pressure port. Use a wrench on the hex pressure con-

nection to tighten. Test for leaks. On Differential Pressure models, the Low (L) side pressure must NOT exceed the 

high (H) side pressure. 

• 

Allow space in front of  the unit to access the programming function of  the product.

Over Range Pressure:
The maximum pressure to which a pressure sensor may be continuously subjected to without causing damage and maintaining setpoint repeatability.
Max Working Pressure:
The maximum that can be applied to both process ports simultaneously without affecting sensor performance.  The low (L) side pressure must NOT 
exceed the high (H) side pressure.  Damage to the sensor may result.

WARNING: NEVER INSERT ANY OBJECT INTO THE PRESSURE SENSOR OPENING. DAMAGE TO THE SENSOR WILL 

RESULT, AFFECTING ACCURACY.

Summary of Contents for Excela 1GSWLL

Page 1: ... TO PREVENT MOISTURE FROM ENTERING ENCLOSURE DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS FOR DIFFERENTIAL PRESSURE MODELS ESPECIALLY LOW RANGE UNITS MOUNT THE SENSOR LEVEL TO MINI MIZE ANY PRESSURE READING OFFSETS THE OFFSET COMMAND MAY BE USED TO ZERO THE DISPLAY SEE PAGE 5 FOR ADDITIONAL INFORMATION Excela is rated for both indoor and outdoor operation IP66 and Nema 4X w...

Page 2: ...power supply use the test resistor supplied 1 8K Ω with the unit Loosen the four 4 Phillips head screws holding the faceplate to the enclosure Gently remove the faceplate module Dis connect the 8 wire connector from the faceplate to allow easy wiring Pass the wires through the conduit connector and connect to the terminal block You can wire the unit as a Normally Open or a Normally Closed switch T...

Page 3: ...ax process values and the number of switch trips The dis play will revert back to the Process Display mode after scrolling Note While scrolling you can clear the values by pushing the right g arrow Pushing the right g button once the display will scroll setpoint Rise and Fall The display will revert back to the Process Display mode after scrolling ALARM CONDITION When the process goes beyond the R...

Page 4: ...when switch trips PASSWRD Add your own 4 digit password for security OFST Allows low range value offset by 10 SPAN Change the high end by 10 LCH1 Latch switch output on rise needs to be reset manually PLUG PORT Monitors pressure fluctuations in process 1 min 1 hr 24 hr FILTER Smoothens transient pressure spikes Programmable from 1 4 to 2 seconds TRIP DELAY Like a switch timer delay trip up to 999 ...

Page 5: ...mit Span 400 404 x 450 446 rounded LATCH MODE Similar to Manual Reset on mechanical switch The switch output can be configured to latch when the setpoint is reached on rising set point only Set Latching Mode In the Programming Mode set LCH1 to ON When the set point is crossed on increasing process parameter the switch will latch and will remain in the latched state until it is manually reset by th...

Page 6: ...easure the voltage drop across the switch connected to the terminal block A properly functioning Excela electronic switch will exhibit the following voltage levels Model Voltage when switch is open Voltage when switch is closed 1GSWLL 8 50 VDC 5 VDC DISPLAY MODULE CALIBRATION The Serial on the module and the enclosure must match for proper operation Swapping modules among similar ranges would resu...

Page 7: ...d clear the error and operate normally If error continues check for sensor damage due to over range exposure Overrange Process input is above 103 of range PRESSURE and TEMPERATURE above range value Automatic Reset when process variable returns to normal Underrange Process input is be low 1 25 of range PRESSURE and TEMPERATURE below range value Automatic Reset when process variable returns to norma...

Page 8: ...RD CONFIRM PWORD PWORD CONFIRMED IF ON SET BLINKING DIGIT IF OFF DISCARD NEW PWORD POS NEG 8888 POS NEG ON OFF 8888 Both FILTER NOTE while scrolling pressing the right arrow will clear MAX MIN TRIPS values Advanced Menu OFF 1 4S 1 2S 1Sec 2Sec OFF and 1 4 Sec settings not available on temperature models TRIP DELAY ON OFF 8888 ON OFF SAVE CHNG NOTE Ifentriesareoutofrange ERR messagewillflashonscree...

Page 9: ...IM_1GSW 02 www ueonline com 9 DIMENSIONAL DRAWINGS Model 1GSWLL Gauge Pressure Sensor Model 1GSWLL Differential Pressure Sensor ...

Page 10: ...IM_1GSW 02 www ueonline com 10 Model 1GSWLL Temperature Model R Sensor Model 1GSWLL Temperature Model L Sensor ...

Page 11: ...ight arrow button and continue to record new min max values 4 Press the right key to display the switch setpoints Verify that the setpoints are correct 5 To confirm process display on Excela connect calibration gauge to the Excela and verify that both displays match within tolerance If minor adjustment is needed up to 10 of range use the offset and span features within Excela s advanced programmin...

Page 12: ...be used to zero the display see page xx for additional information Pour les modèles de pression différentielle de pressions faibles montez le niveau du capteur afin de minimiser tout décalage de lecture de pression La commande décalée peut être utilisée pour mettre l affichage à zéro voir la page xx pour plus d informations 1 Never insert any object into the pressure sensor opening Damage to the s...

Page 13: ...sonnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery...

Reviews: