Unitary products group YMB Series Installation Manual Download Page 11

170761-UIM-B-0406

Unitary Products Group

11

Wiring Related Fault Codes

Table 8 shows the faults that the control can detect when a problem is
present with the system wiring or jumper configurations. The control
displays this type of error by flashing LED1 (Red) and energizing LED2
(Green) constantly. These faults typically occur when the heat pump is
first installed or when a system component such as the room thermostat
or indoor unit is replaced or rewired. 

FAULT CODE MEMORY

Displaying Stored Fault Codes

The control will store up to five fault codes in memory. If more than five
faults occur, the five most recent fault codes will remain in memory. The
stored faults can be displayed by depressing the LAST ERROR push-
button for one to five seconds while no thermostat inputs to the control
are energized. See Figures 10 and 13 for the location of the pushbut-
ton. Since some room thermostats energize the O signal even when not
calling for compressor operation, turn the room thermostat to the SYS-
TEM OFF setting when displaying fault codes. 

When the LAST ERROR pushbutton is depressed and released, the
control will display the stored fault codes beginning with the most
recent. The control will display the most recent fault code, pause two
seconds, and display the next fault code. The control will display the
stored error codes and then return to the normal LED status display
mode. The stored fault codes can be displayed again by depressing the
pushbutton again. When the control displays the fault codes with the
onboard LED’s, it will also energize the X/L output with the correspond-
ing flash code. The X/L output signal can be observed at the room ther-
mostat or at the control using a 24VAC LED test device connected to
the X/L terminal.

If the control has no fault codes stored in memory, it will flash both
LED’s twice simultaneously. If a thermostat signal is energized while the
control is displaying the stored error codes, the control will stop display-
ing the stored error codes and resume normal operation.

Clearing Fault Code Memory

Once the stored fault codes have been displayed and recorded, the
installer should clear the stored fault codes from the control’s memory.
This practice will enable better troubleshooting and diagnosis of system
problems. If the stored fault codes are not cleared after the cause of the
problem has been resolved, a service technician doing a later service
call may not know that the fault codes in the memory were caused by a
problem that has already been fixed. The technician may waste time
trying to fix a condition that no longer exists. Therefore, it is very impor-
tant to always clear the fault code memory after the unit is installed and
running properly following a service call.

IMPORTANT: Always clear the fault code memory after resolving the
condition that caused the fault code. 

To clear the fault code memory, depress the LAST ERROR pushbutton
for longer than 5 seconds. The control will flash both LED’s three times
to indicate that the memory has been cleared. To confirm that the mem-
ory has been cleared, depress the LAST ERROR pushbutton for one to
five seconds. The control will flash both LED’s twice to indicate that no
faults are stored in memory.

LOCKOUT MODES

Soft Lockout

The control will cause a soft lockout during the following conditions.
Detailed descriptions of the conditions required for the control to enter
the soft lockout mode are contained in other sections of this document. 

1.

High-pressure switch 

a.

Two openings within six hours

2.

Low-pressure switch

a.

One opening of the switch for more than five seconds except
under certain conditions.

3.

High discharge temperature (with optional discharge sensor)

a.

Temperature reading exceeds 263F

4.

Low discharge temperature (with optional discharge sensor)

a.

Temperature reading does not reach 90F following timer expi-
ration under certain conditions.

During the soft lockout mode, the control will do the following.

1.

De-energize the compressor

2.

If in heating mode, the control will energize auxiliary heat as if the
outdoor ambient temperature was below the LTCO setting.

3.

Energize the LED and X/L outputs with the appropriate flash codes

4.

Store the appropriate fault code in memory.

The control will reset the soft lockout condition when any of the follow-
ing occur following removal of the fault condition.

1.

Power is cycled to the R or Y1 inputs of the control. This will cause
the soft lockout condition to be reset when the thermostat is satis-
fied or when the thermostat is set to SYSTEM OFF and back to
HEAT or COOL mode.

2.

The TEST terminals are shorted for more than two seconds.

When the soft lockout condition is reset, the control will stop displaying
the fault code and will respond to thermostat inputs normally. 

Hard Lockout

If four soft lockouts occur within a twelve-hour period, the control shall
cause a hard lockout condition. These soft lockouts can be caused by
the same or different conditions. The control will function in the same
way during soft and hard lockout conditions. The difference is in the
requirements for resetting the lockout condition. The control will reset
the hard lockout condition when any of the following occur following
removal of the fault condition.

1.

Power is removed from the R input of the control.

2.

The TEST terminals are shorted for more than two seconds.

A hard lockout condition will not be reset when the thermostat is satis-
fied or when the thermostat is set to SYSTEM OFF and back to HEAT
or COOL mode. Power (24 VAC) to the control must be removed and
reapplied.

When the hard lockout condition is reset, the control will de-energize
the LED and X/L outputs and respond to thermostat inputs normally.

Wiring or Setting Related Lockouts

The control will not operate the compressor when the following faults
occur. These faults can be reset using the same methods used to reset
a soft lockout. However, two occurrences of these faults will not cause a
hard lockout condition.

1.

Presence of Y2 thermostat signal without Y1.

2.

Shorted discharge sensor input

3.

Shorted bonnet sensor

4.

Shorted or open liquid line or outdoor ambient sensor 

5.

Defrost curve jumper error

If a compressor wiring error is detected, the control will not operate the
compressor. Once the compressor wiring error has been detected,
power (24 VAC) must be cycled to the control for the control to sense
the wiring change and clear the lockout condition.

TABLE 8: Wiring Related Fault Codes

Description

LED1 
(Red)

LED2

 (Green)

X/L

Wiring Related Faults
Compressor Contactor Miswire

1

ON

4

Y2 present without Y1

2

ON

4

Y1 and W present without Y2 in 
two stage mode

3

ON

4

O signal received in AC mode

4

ON

4

W signal received in AC mode

5

ON

4

W and O signal received in AC mode

6

ON

4

W and O signal received in HP mode

7

ON

4

Defrost Curve Jumper Error (Invalid jumper 
setting preventing compressor operation)

8

ON

4

Summary of Contents for YMB Series

Page 1: ...or moderate injury It is also used to alert against unsafe practices and hazards involving only property dam age Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installation adjustment alteration service or mainte nance can cause injury or property damage Refer to this manual for assistance or for additional in...

Page 2: ...sor burnout then installation of a 100 activated alumina suction line filter drier is required in addition to the factory installed liquid line drier Operate the system for 10 hours Monitor the suction drier pres sure drop If the pressure drop exceeds 3 psig replace both the suction line and liquid line driers After a total of 10 hours run time where the suction line pressure drop has not exceeded...

Page 3: ...door unit is above the indoor coil oil trapping is necessary An oil trap should be provided for every 20 ft of rise See Figure 2 PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possible Care must be taken not to damage the couplings or kink the tubing Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary If soft copp...

Page 4: ...l 5 Slide the grommet away from the vapor connection at the indoor coil Braze the vapor line to the evaporator vapor connection After the connection has cooled slide the grommet back into original position Refer to the Tabular Data Sheet for proper vapor line siz ing 6 Protect the vapor valve with a wet rag and braze the vapor line connection to the outdoor unit The nitrogen flow should be exiting...

Page 5: ...orous copper alloy material such as Silfos 5 or equivalent DO NOT use soft solder Install the TXV bulb to the vapor line near the equalizer line using the two bulb clamps furnished with the TXV assembly Ensure the bulb is making maximum contact Refer to TXV installation instruction for view of bulb location a Bulb should be installed on a horizontal run of the vapor line if possible On lines under...

Page 6: ...xposed glass or appliances drafts from outside doors or supply air grilles 5 Route the 24 volt control wiring NEC Class 2 from the outdoor unit to the indoor unit and thermostat NOTE To eliminate erratic operation seal the hole in the wall at the thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat DEHUMIDIFICATION CONTROL A dehumidification con...

Page 7: ...brated charging cylinder or accurate weighing device is avail able add refrigerant accordingly Otherwise model specific charging charts are provided in Tables 12 18 for cooling mode only There is no accurate method for charging these units in the heating mode If charg ing is required during the heating mode the unit must be evacuated and charge weighed in according to the rating plate If TXV indoo...

Page 8: ...95 212 105 242 115 94 56 124 71 154 84 184 96 214 106 244 115 96 57 126 72 156 85 186 97 216 107 246 116 98 58 128 73 158 86 188 97 218 107 248 117 100 59 130 74 160 87 190 98 220 108 250 117 102 60 132 75 162 88 192 99 222 109 252 118 104 61 134 76 164 88 194 99 224 109 254 118 106 62 136 77 166 89 196 100 226 110 256 119 108 63 138 78 168 90 198 101 228 111 258 119 FIGURE 8 Heat Pump Flow Diagra...

Page 9: ...display various types of diagnostic information LED1 is red and LED2 is green The location of the LED s is shown in Figures 10 and 13 These LED s are used to display opera tional mode status and fault information OPERATIONAL MODE DETECTION The control can be used in a variety of applications including heat pumps and air conditioners with modulating compressors The control uses various inputs to de...

Page 10: ...reen is not energized These faults typically occur when the heat pump has been operating and a problem occurs Sensor or Switch Fault Codes Table 7 shows the faults that the control can detect when a problem is present with a sensor or switch The control displays this type of error by energizing LED1 Red constantly and flashing LED2 Green These faults typically occur when the heat pump has been ope...

Page 11: ...criptions of the conditions required for the control to enter the soft lockout mode are contained in other sections of this document 1 High pressure switch a Two openings within six hours 2 Low pressure switch a One opening of the switch for more than five seconds except under certain conditions 3 High discharge temperature with optional discharge sensor a Temperature reading exceeds 263F 4 Low di...

Page 12: ...at has been forced using the TEST inputs It will also display the active defrost curve using the X L terminal when the operational mode is being displayed using the LED s For instance the X L output will be energized with two flashes when defrost curve 2 is active The control will lock out the com pressor if the defrost curve selection jumper is not properly set Defrost Cycle Initiation The contro...

Page 13: ...onnected to the indoor unit The SWITCH POINT jumper on the control has no effect on the opera tion of the heat pump The control implements the Hot Heat Pump Mode by controlling the indoor airflow level during heating operation only Cooling operation is not affected By reducing the indoor airflow level the heat pump system will operate with increased indoor discharge air temperatures The con trol c...

Page 14: ...flow because of the Y1 signal being delivered to the Y1 input of the indoor unit When the ten minute timer expires the control will compare the liquid line temperature to the indoor airflow control curve for the measured outdoor ambient temperature If the point is within region A See Figure 12 the control shall maintain Y2 OUT in the de energized state until the liquid line temperature rises so th...

Page 15: ...ient temperature is greater than the bal ance point setting the control will not energize the auxiliary heat out puts However the control shall ignore the balance point setting and energize auxiliary heat under some conditions as described in the auxil iary heat sections of this document FOSSIL FUEL JUMPER FFUEL Setting The control includes a FFUEL jumper to specify whether the control is installe...

Page 16: ...ll de energize the compressor outputs and energize W1 Out and W2 Out immediately Table 11 describes the auxiliary heat operation for fossil fuel mode Bonnet Sensor Fossil Fuel Mode The heat pump may be equipped in the field with an optional indoor air discharge temperature or bonnet sensor The control does not allow the heat pump and the furnace to operate simultaneously even with a bon net sensor...

Page 17: ...n time If the control senses another opening of the high pressure switch before the timer expires it will cause a soft lockout condition The second opening of the high pressure switch must be greater than 160 milliseconds for the lockout to occur If the second opening is between 40 and 160 milliseconds the control will de energize the com pressor but not cause a soft lockout condition If the contr...

Page 18: ... and assure proper drainage IT IS UNLAWFUL TO KNOWINGLY VENT RELEASE OR DIS CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR SERVICE MAINTENANCE OR THE FINAL DIS POSAL OF THIS UNIT WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE OWNER HAS BEEN FULLY INSTRUCTED SECURE THE OWNER S APPROVAL TABLE 12 1 1 2 Ton Subcooling Charging Chart Outdoor Ambient Indoor Wet Bulb F 57 62 67 72 DB F Liquid Pressu...

Page 19: ...7 11 269 11 110 286 11 287 11 286 11 288 11 115 305 11 306 11 305 11 307 11 120 324 10 326 11 324 11 326 11 125 344 10 345 10 343 11 346 11 TABLE 17 4 Ton Subcooling Charging Chart Outdoor Ambient Indoor Wet Bulb F 57 62 67 72 DB F Liquid Pressure psig at Base Valve 65 141 4 140 3 141 3 142 2 70 155 5 154 4 156 4 157 3 75 169 5 169 5 171 4 172 4 80 183 5 183 5 185 5 187 4 85 197 5 198 5 200 5 202 ...

Page 20: ...ce Printed in U S A 170761 UIM B 0406 Copyright by York International Corp 2006 All rights reserved Supersedes 170761 UIM A 0106 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION X WIRING DIAGRAM FIGURE 13 Wiring Diagram ...

Reviews: