035-20186-001-A-0704
Unitary Products Group
27
TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
3200
1150
2325
1182
2425
1212
2525
-
-
-
-
-
-
-
-
3000
1100
2010
1129
2090
1157
2150
1185
2225
1215
2290
1242
2360
-
-
2800
1045
1700
1074
1780
1102
1850
1131
1940
1160
2025
1190
2075
1217
2130
2600
985
1425
1015
1475
1045
1540
1075
1630
1103
1715
1135
1760
1163
1825
2400
930
1240
958
1300
990
1350
1020
1400
1051
1430
1081
1490
1111
1600
2200
-
-
905
1070
933
1160
965
1210
997
1250
1028
1285
1060
1325
2000
-
-
-
-
-
-
919
1025
950
1100
982
1130
1014
1160
1800
-
-
-
-
-
-
-
-
909
925
939
1005
968
1030
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
3200
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2800
1245
2190
-
-
-
-
-
-
-
-
-
-
-
-
2600
1193
1920
1222
1990
1250
2060
-
-
-
-
-
-
-
-
2400
1142
1675
1173
1730
1205
1800
1234
1885
-
-
-
-
-
-
2200
1090
1380
1124
1450
1155
1550
1186
1640
1217
1710
1249
1775
-
-
2000
1045
1175
1077
1200
1109
1275
1140
1360
1170
1460
1205
1545
1235
1600
1800
998
1050
1028
1060
1058
1060
1087
1075
1118
1150
1148
1250
1176
1360
0.60
0.70
0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20
0.30
0.40
0.50
UNIT
TONNAGE
AIR
FLOW
CFM
6
1
,
2
UNIT
TONNAGE
AIR
FLOW
CFM
6
1
,
2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90
1.00
1.10
1.20
1.30
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
TABLE 16: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
MODEL
SIZE
BLOWER
RANGE
(RPM)
MOTOR
1
ADJUSTABLE MOTOR PULLEY
FIXED BLOWER PULLEY
BELT
(NOTCHED)
HP
FRAME
DESIG-
NATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIG-
NATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIG-
NATION
PITCH
LENGTH
(IN.)
QTY.
6 TON
900/1250
1 1/2
56
1VL44
3.1-4.1
2.8-3.8
7/8
AK56
5.4
5.2
1
A36
37.3
1
1.
All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located
in the moving air, upstream of any heating device.