Unitary Products Group

7

035-20188-000-A-0704

FIG. 2 - CLEARANCES

3'

MINIMUM CLEARANCE OF 1"

ALL SIDES FOR THE FIRST 3'

OF DUCT FOR 20 & 25 kW.

ZERO INCHES THEREAFTER,

FOR ALL OTHER HEATERS,

ZERO INCH CLEARANCE ALL

SIDES FOR ENTIRE LENGTH

OF DUCT.

FLEXIBLE DUCT

COLLAR

DESCRIPTION

RESISTANCE, IWG

CFM

500

600

700

800

900

1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000

Wet Indoor coil

0.01

0.01

0.01

0.02

0.01

0.02

0.03

0.04

0.04

0.03

0.04

0.04

0.05

0.05

0.06

0.07

Economizer

0.00

0.00

0.00

0.01

0.01

0.01

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.07

0.08

0.08

Filter/Frame Kit

0.01

0.02

0.02

0.02

0.02

0.02

0.03

0.03

0.03

0.03

0.04

0.05

0.05

0.06

0.06

0.07

Electric Heat

0.02

0.03

0.03

0.03

0.04

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.01

0.11

0.11

0.12

NOTE: 1. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2. The pressure thru the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver

less CFM during full economizer operation.

CLEARANCES (Minimum)

Front

12"

Back

0"

Left Side (Filter Access)

24"

Right Side

24"

Below Unit



0"

Above Unit

‚

36" (For Condenser Air Discharge)

Q

Units may be installed on combustible floors made from wood or class A,

B or C roof covering material.

R

Units must be installed outdoors. Overhanging structures or shrubs

should not obstruct outdoor air discharge outlet.

NOTE: FOR UNITS APPLIED WITH A ROOF

CURB, THE MINIMUM CLEARANCE MAY BE

REDUCED FROM 1 INCH TO 1/2 INCH BE-

TWEEN COMBUSTIBLE ROOF CURB MA-

TERIAL AND THE SUPPLY DUCT.

TABLE 7 -

ADDITIONAL STATIC PRESSURE RESISTANCE

Q

All units are factory set to TB2-A. Above data includes allowances for a dry indoor coil and no filters. For additional pressure drops, refer to the “Additional Static Pressure Resistance” table.

 

 

 

 

     

         

 

       

 

         

 

       

 

 

      

 

 

           

 

 

  

 

  

      

 

 

       

 

 

  

 

 

   

 

   

 

 

 

           

 

  

 

      

 

       

 

  

  

  

 

TABLE 6 - SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE (208/230/460 VOLT

Q

)

Summary of Contents for BAUZ Series

Page 1: ...Post start Check List 035 16605 003 Electric Heater Accessory REPLACEMENT PARTS Refer to User s Maintenance and Service Information Manual for complete listing of replacement parts on this equipment C...

Page 2: ...nser section 5 Maintain level tolerance of unit to 1 8 maximum RIGGING OR HANDLING Care must be exercised when moving the unit Do not remove any packaging until the unit is near the place of installat...

Page 3: ...densate drain The plumbing must conform to local codes Use a seal ing compound on male pipe threads Install the condensate drain line NPTF to spill into an open drain SERVICE ACCESS Access to all serv...

Page 4: ...refrigerant leaks re placing refrigerant components such as filter drier pressure switch metering device or coil Units are shipped with compressor mounting which are factory adjusted and ready for op...

Page 5: ...4 208 230 1 60 187 253 14 3 60 0 0 9 4 8 21 7 30 30 0 96 40 030 208 230 1 60 187 253 16 4 72 5 1 0 4 8 24 2 35 35 0 96 40 208 230 3 60 187 253 11 6 60 0 1 0 4 8 18 8 25 25 0 96 75 460 3 60 414 504 5 0...

Page 6: ...5 150 150 175 175 030 208 230 3 60 11 6 60 0 1 0 4 8 2NH04501025 2NH04501525 7 5 10 0 11 3 15 0 20 8 24 1 31 3 36 1 44 7 48 7 57 7 63 7 45 50 60 70 45 50 60 70 036 208 230 3 60 12 9 77 0 1 0 6 9 2NH04...

Page 7: ...Performance Table 2 The pressure thru the economizer is greater for 100 outdoor air then for 100 return air If the resistance of the return air duct system is less then 0 25 IWG the unit will deliver...

Page 8: ...RALL OVERALL All dimensions are in inches They are subject to change without notice Certified dimensions will be provided upon request UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED OVERALL SIDE SUPPLY...

Page 9: ...ombination of outdoor ambient and outdoor coil temperatures indicate that defrosting is necessary When coil temperature is below the ini tiate point for the ambient temperature continuously for 4 1 2...

Page 10: ...OFF HEATER BANK 3 ELEC HEAT INSTANT OFF HEATER BANK 2 ELEC HEAT SEC DELAY OFF HEATER BANK 1 ELEC HEAT 1 SEC DELAY OFF FAN 10 SEC DELAY OFF G Y W ON FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON...

Page 11: ...OFF G W ON FAN INSTANT ON HEATER BANK 1 2 3 ELEC HEAT INSTANT ON HEATER BANK 4 5 6 ELEC HEAT 10 SEC DELAY ON OFF HEATER BANK 4 5 6 ELEC HEAT INSTANT OFF HEATER BANK 1 2 3 ELEC HEAT SEC DELAY OFF FAN 1...

Page 12: ...door coil surface or other parts in the air circuit Cleaning should be as often as necessary to keep the coil clean Use a brush vacuum cleaner attachment or other suitable means If water is used to cl...

Page 13: ...Unitary Products Group 13 035 20188 000 A 0704 FIG 5 TYPICAL WIRING DIAGRAM BUZ MODELS 208 230 1 60 POWER SUPPLY...

Page 14: ...14 Unitary Products Group 035 20188 000 A 0704 FIG 6 TYPICAL WIRING DIAGRAM BUZ 208 230 3 60 POWER SUPPLY...

Page 15: ...Unitary Products Group 15 035 20188 000 A 0704 FIG 7 TYPICAL WIRING DIAGRAM BUZ 460 3 60 POWER SUPPLY...

Page 16: ...an Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2004 All Rights Reserved Supersedes Nothing 035 20188 000 A 0704 0 1 2 1 2 3 1 2 4 53 6...

Reviews: