TABLE 5 - ELECTRICAL DATA (13 SEER HEAT PUMP / ELECTRIC HEAT)

MODEL

BUZ

POWER

SUPPLY

COMPRESSOR

COND.

FAN

MOTOR

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

ELECTRIC HEAT ACCESSORY

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,



AMPS

MAX.

HACR

‚

BREAKER

SIZE

RLA

LRA

MODEL NO.

KW

TOTAL

AMPS

024 208/230-1-60

14.3

60

0.9

4.8

2NH04500506
2NH04500706
2NH04501006

3.8 / 5.0  *
5.6 / 7.5  *

7.5 / 10.0  *

18.1 / 20.8
27.1 / 31.3
36.1 / 41.7

44.3 / 47.7
55.6 / 60.8
66.8 / 73.8

50 / 50
60 / 70
70 / 80

50 / 50
60 / 70
70 / 80

030 208/230-1-60

16.4

72.5

1.0

4.8

2NH04500506
2NH04500706
2NH04501006
2NH04501506

3.8 / 5.0  *
5.6 / 7.5  *

7.5 / 10.0  *

11.3 / 15.0  *

18.1 / 20.8
27.3 / 31.3
36.1 / 41.7
54.2 / 62.5

46.7 / 50.2
58.0 / 63.2
69.3 / 76.3

91.9 / 102.3

50 / 60
60 / 70
70 / 80

100 / 110

50 / 60
60 / 70
70 / 80

100 / 110

036 208/230-1-60

17.1

83.0

1.0

6.9

2NH04500506
2NH04500706
2NH04501006
2NH04501506

3.8 / 5.0  *
5.6 / 7.5  *

7.5 / 10.0  *

11.3 / 15.0  *

18.1 / 20.8
27.1 / 31.3
36.1 / 41.7
54.2 / 62.5

49.7 / 53.2
61.0 / 66.2
72.3 / 79.2

94.9 / 105.3

60 / 60
70 / 70
80 / 80

100 / 110

60 / 60
70 / 70
80 / 80

100 / 110

042 208/230-1-60

20.7

105.0

1.1

6.9

2NP04501006
2NP04501506

7.5 / 10.0  *

11.3 / 15.0  *

36.1 / 41.7
54.2 / 62.5

76.4 / 83.3

99.0 / 109.4

80 / 90

100 / 110

80 / 90

100 / 110

048 208/230-1-60

20.4

113.0

1.2

6.9

2NP04501006
2NP04501506
2NP04502006
2NP04502506

7.5 / 10.0  *

11.3 / 15.0  *

15.0 / 20.0  *
18.8 / 25.0  *

36.1 / 41.7
54.2 / 62.5
72.2 / 83.3

90.3 / 104.2

79.6 / 86.6

102.2 / 112.6

124.8 / 138.6
147.3 / 164.7

90 / 90

110 / 125

125 / 150
150 / 175

90 / 90

110 / 125

125 / 150
150 / 175

060 208/230-1-60

26.3

150.0

1.7

8.9

2NP04501006
2NP04501506
2NP04502006
2NP04502506

7.5 / 10.0  *

11.3 / 15.0  *

15.0 / 20.0  *
18.8 / 25.0  *

36.1 / 41.7
54.2 / 62.5
72.2 / 83.3

90.3 / 104.2

88.5 / 95.4

111.1 / 121.5

133.6 / 147.5
156.2 / 173.6

100 / 110

125 / 125
150 / 150
175 / 175

100 / 110

125 / 125
150 / 150
175 / 175

030 208/230-3-60

11.6

60.0

1.0

4.8

2NH04501025
2NH04501525

7.5 / 10.0  *

11.3 / 15.0  *

20.8 / 24.1
31.3 / 36.1

44.7 / 48.7
57.7 / 63.7

45 / 50
60 / 70

45 / 50
60 / 70

036 208/230-3-60

12.9

77.0

1.0

6.9

2NH04501025
2NH04501525

7.5 / 10.0  *

11.3 / 15.0  *

20.8 / 24.1
31.3 / 36.1

48.7 / 52.7
61.7 / 67.8

60 / 60
70 / 80

60 / 60
70 / 80

042 208/230-3-60

15.3

88.0

1.1

6.9

2NP04501025
2NP04501525

7.5 / 10.0  *

11.3 / 15.0  *

20.8 / 24.1
31.3 / 36.1

51.8 / 55.8
64.9 / 70.9

50 / 60
70 / 70

50 / 60
70 / 70

048 208/230-3-60

16.0

120.0

1.2

6.9

2NP04501025
2NP04501525
2NP04502025
2NP04502525

7.5 / 10.0  *

11.3 / 15.0  *

15.0 / 20.0  *
18.8 / 25.0  *

20.8 / 24.1
31.3 / 36.1
41.7 / 48.1
52.1 / 60.1

51.1 / 55.1
64.1 / 70.2
77.2 / 85.2

90.2 / 100.2

60 / 60
70 / 80
80 / 90

100 / 100

60 / 60
70 / 80
80 / 90

100 / 100

060 208/230-3-60

17.6

120.0

1.7

8.9

2NP04501025
2NP04501525
2NP04502025
2NP04502525

7.5 / 10.0  *

11.3 / 15.0  *

15.0 / 20.0  *
18.8 / 25.0  *

20.8 / 24.1
31.3 / 36.1
41.7 / 48.1
52.1 / 60.1

63.0 / 67.0
77.1 / 83.1
91.1 / 99.1

105.1 / 115.2

70 / 70
80 / 90

100 / 100

110 / 125

70 / 70
80 / 90

100 / 100

110 / 125

030

460-3-60

5.0

31.0

0.5

2.4

2NH04501046
2NH04501546

10.0**
15.0**

12.0
18.0

32.6
41.1

35
45

35
45

036

460-3-60

5.7

35.0

0.5

3.5

2NH04501046
2NH04501546

10.0**
15.0**

12.0
18.0

37.4
45.9

45
50

45
50

042

460-3-60

7.1

39.0

0.6

3.5

2NP04501046
2NP04501546

10.0**
15.0**

12.0
18.0

42.1
50.7

50
60

50
60

048

460-3-60

8.3

60.0

0.6

3.5

2NP04501046
2NP04501546
2NP04502046
2NP04502546

10.0**
15.0**
20.0**
25.0**

12.0
18.0
24.1
30.1

47.5
56.0
64.5
71.4

60
70
80
80

60
70
80
80

060

460-3-60

9.6

70.0

0.9

4.5

2NP04501046
2NP04501546
2NP04502046
2NP04502546

10.0**
15.0**
20.0**
25.0**

12.0
18.0
24.1
30.1

55.4
64.0
72.5
81.0

70
80
90

100

70
80
90

100

Q

= Dual element, time delay type.

R

= Standard circuit breakers may be used in Canada and on applications

over 60 amps where the heaters are separately fused.

*

= KW listed is for 240 volts, use table on previous page for 208 or 230 volts.

**

= KW listed is for 480 volts, use table on previous page for 460 volts.

Summary of Contents for BAUZ Series

Page 1: ...Post start Check List 035 16605 003 Electric Heater Accessory REPLACEMENT PARTS Refer to User s Maintenance and Service Information Manual for complete listing of replacement parts on this equipment C...

Page 2: ...nser section 5 Maintain level tolerance of unit to 1 8 maximum RIGGING OR HANDLING Care must be exercised when moving the unit Do not remove any packaging until the unit is near the place of installat...

Page 3: ...densate drain The plumbing must conform to local codes Use a seal ing compound on male pipe threads Install the condensate drain line NPTF to spill into an open drain SERVICE ACCESS Access to all serv...

Page 4: ...refrigerant leaks re placing refrigerant components such as filter drier pressure switch metering device or coil Units are shipped with compressor mounting which are factory adjusted and ready for op...

Page 5: ...4 208 230 1 60 187 253 14 3 60 0 0 9 4 8 21 7 30 30 0 96 40 030 208 230 1 60 187 253 16 4 72 5 1 0 4 8 24 2 35 35 0 96 40 208 230 3 60 187 253 11 6 60 0 1 0 4 8 18 8 25 25 0 96 75 460 3 60 414 504 5 0...

Page 6: ...5 150 150 175 175 030 208 230 3 60 11 6 60 0 1 0 4 8 2NH04501025 2NH04501525 7 5 10 0 11 3 15 0 20 8 24 1 31 3 36 1 44 7 48 7 57 7 63 7 45 50 60 70 45 50 60 70 036 208 230 3 60 12 9 77 0 1 0 6 9 2NH04...

Page 7: ...Performance Table 2 The pressure thru the economizer is greater for 100 outdoor air then for 100 return air If the resistance of the return air duct system is less then 0 25 IWG the unit will deliver...

Page 8: ...RALL OVERALL All dimensions are in inches They are subject to change without notice Certified dimensions will be provided upon request UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED OVERALL SIDE SUPPLY...

Page 9: ...ombination of outdoor ambient and outdoor coil temperatures indicate that defrosting is necessary When coil temperature is below the ini tiate point for the ambient temperature continuously for 4 1 2...

Page 10: ...OFF HEATER BANK 3 ELEC HEAT INSTANT OFF HEATER BANK 2 ELEC HEAT SEC DELAY OFF HEATER BANK 1 ELEC HEAT 1 SEC DELAY OFF FAN 10 SEC DELAY OFF G Y W ON FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON...

Page 11: ...OFF G W ON FAN INSTANT ON HEATER BANK 1 2 3 ELEC HEAT INSTANT ON HEATER BANK 4 5 6 ELEC HEAT 10 SEC DELAY ON OFF HEATER BANK 4 5 6 ELEC HEAT INSTANT OFF HEATER BANK 1 2 3 ELEC HEAT SEC DELAY OFF FAN 1...

Page 12: ...door coil surface or other parts in the air circuit Cleaning should be as often as necessary to keep the coil clean Use a brush vacuum cleaner attachment or other suitable means If water is used to cl...

Page 13: ...Unitary Products Group 13 035 20188 000 A 0704 FIG 5 TYPICAL WIRING DIAGRAM BUZ MODELS 208 230 1 60 POWER SUPPLY...

Page 14: ...14 Unitary Products Group 035 20188 000 A 0704 FIG 6 TYPICAL WIRING DIAGRAM BUZ 208 230 3 60 POWER SUPPLY...

Page 15: ...Unitary Products Group 15 035 20188 000 A 0704 FIG 7 TYPICAL WIRING DIAGRAM BUZ 460 3 60 POWER SUPPLY...

Page 16: ...an Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2004 All Rights Reserved Supersedes Nothing 035 20188 000 A 0704 0 1 2 1 2 3 1 2 4 53 6...

Reviews: