9
2010-07-23
COPYRIGHT 2010, UNIQUE AUTOMATION
Right arrow increments the desired
depth D: in 10s to a maximum of 250%
FILL
Service
Menu
bathomatic will go into FILLING
bathomatic will go into PAUSED
Allow water to cover the waste and
then
SET 0%
Main
Menu
Service
Menu
Service
Menu
3 x
0% - bath calibration
The easiest and fastest way for 0% bath calibration is done by pouring water into
the bath tub with the plug closed until the water fills the cavity of the waste
completely and becomes level with the bottom of the bath tub. When the water is
level with the bottom of the bath tub let it settle for a little while then select SET 0%
in the SERVICE MENU and press
to store the value.
Below is a method for 0% bath calibration using the BUI. Some practice is
necessary until you can precisely draw the right amount of water by using only the
BUI and often it is easier to draw more water than needed and adjust the depth by
manually lifting the plug until the water level is at 0%
Bath tub calibration should only be undertaken when the bath tub is in sight, and
you have easy access to the power switches supplying bathomatic and all
associated equipment. It is advisable that calibration is done prior to final
positioning of the bath panels/aprons.
bathomatic can only operate reliably if it is
calibrated correctly