TMN/TMP SERIES

OPERATING MANUAL

4.2

The input terminals are at hazardous voltage potentials.  Do not touch this
area when power is applied.

4.3

When operating this power system, the frame ground terminal must be
connected to safety ground by means of a three-wire AC power line to
minimize electrical shock hazard and to ensure low EMI (electromagnetic
interference).

4.4

The internal voltages are at hazardous potentials.  The module covers
should not be removed.  There are no user-serviceable components in
these units.  Removing the covers of the modules will void the warranty.

5.0

WARRANTY

All products of UNIPOWER Corporation are warranted for two (2) years from date of shipment
against defects in material and workmanship.  This warranty does not extend to products which
have been opened, altered or repaired by persons other than persons authorized by the manu-
facturer or to products which become defective due to acts of God, negligence or the failure of
customer to fully follow instructions with respect to installation, application or maintenance.  This
warranty is extended directly by the manufacturer to the buyer and is the sole warranty appli-
cable.  EXCEPT FOR THE FOREGOING EXPRESS WARRANTY, THE MANUFACTURER
MAKES NO WARRANTY, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  As the
sole and exclusive remedy under this warranty, the manufacturer, at its option, may repair or
replace the non-conforming product or issue credit, provided the manufacturer’s inspection
establishes the existence of a defect.  To exercise this remedy, the buyer must contact the
manufacturer’s Customer Service Department to obtain a Return Material Authorization number
and shipping instructions.  Products returned without prior authorization will be returned to buyer.
All products returned for repair must be shipped freight prepaid to UNIPOWER.  If the buyer fails
to fully comply with the foregoing, the buyer agrees that no other remedy (including, but not
limited to, incidental or consequential damages for lost profits, lost sales, injury to person or
property or any other incidental or consequential losses) shall be available to the buyer.

6.0

UNPACKING AND INSPECTION

6.1

This TMN/TMP Series Power System was carefully tested, inspected and
packaged for shipment from our factory.  Upon receipt of the unit it should
be carefully unpacked and inspected for any damage in shipment.

6.2

If there is evidence of damage, do not attempt to test the unit.  The freight
carrier should be notified immediately and a claim for the cost of the
power system should be filed with the carrier for direct reimbursement.
Be sure to include the model and serial number of the damaged unit in all
correspondence with the freight carrier.  Also save the shipping carton
and packing material as evidence of damage for the freight carrier’s

Summary of Contents for TMN5000

Page 1: ...Rights Reserved UNIPOWER Corporation TMNTMP Man2 08 29 01 NORTH AMERICA 3900 Coral Ridge Drive Coral Springs Florida 33065 USA Tel 1 954 346 2442 Fax 1 954 340 7901 sales unipower corp com EUROPE Par...

Page 2: ...ions 6 10 0 Description of Features and Options 9 11 0 Mechanical Specifications 10 12 0 Safety and Industry Standards 10 13 0 Operating Information 11 14 0 Parallel Operation 14 15 0 Rack Control Sup...

Page 3: ...eries Module 7 4 TMN TMP Series Mechanical Dimensions 7 5 Rear Rack Input and Output Connections 12 6 Rated Output Current vs Ambient Temperature 13 7 Remote Sensing Connection 13 8 Parallel Connectio...

Page 4: ...modules while the system is operating The TMN Series operate worldwide with a 85 264VAC input range at 47 63Hz The TMP Series operates with a 170 264VAC input range at 47 63Hz Each module has input po...

Page 5: ...2 TMN TMP SERIES OPERATING MANUAL Figure 1 TMN TMP Series Bulk Power Front End Figure 2 TMN TMP Series Module Block Diagram...

Page 6: ...appable Modules u LED Operating Indicators u Control and Monitoring Interface Signals 3 0 PRODUCT LINE 3 1 Hot Swap Modules 3 2 Rack 4 0 SAFETY WARNINGS 4 1 These hot swap modules and racks have hazar...

Page 7: ...TICULAR PURPOSE As the sole and exclusive remedy under this warranty the manufacturer at its option may repair or replace the non conforming product or issue credit provided the manufacturer s inspect...

Page 8: ...egulates the output voltage and keeps it constant 7 2 Power Factor Correction This high frequency converter circuit switch ing at 45kHz achieves a power factor of 0 99 by forcing the AC input current...

Page 9: ...ime 3 20mS Dynamic Response 4 1 msec Temperature Coefficient 0 02 C Minimum Load 0A Overload Protection Constant Power Limiting Overvoltage Protection Latched Shutdown Active Current Share 10 Differen...

Page 10: ...G MANUAL Figure 4 TMN TMP Series Mechanical Dimensions Figure 3 Front Panel of TMN TMP Series Module HOT PLUG MODULE MATING RACK MOUNT RACK MOUNT 17 20 436 9 3 50 88 9 AC CONNECTION AREA J1 SIGNAL CON...

Page 11: ...an PHYSICAL SPECIFICATIONS Case Material Module Aluminum Rack Mount Steel Finish Rack Mount Powder Coat Gray Dimensions Inches mm Hot Swap Module 3 30 H x 4 90 W x 13 09 D 84 x 124 x 332 3 Module Rack...

Page 12: ...inputs can also be connected together so that the external control voltage adjusts all the module outputs simultaneously If the output power converter overheats the TMN TMP module will automatically s...

Page 13: ...ondi tion This protection is continuous without damage and recovery is automatic when the overload is removed Current limiting begins at about 105 of rated output current The AC Good indicator is a gr...

Page 14: ...on 18 3 and Figure 5 Both positive and negative outputs are floating and isolated from the chassis 13 3 Output Voltage The output voltage of each module is factory set to 24 28 or 48 volts 1 The volta...

Page 15: ...ING MANUAL Figure 5 Rear Rack Input and Output Connections b Uncovered AC Input Connection Area c Top View of DC Output Bus Bars a Rear Connections to Rack MODULE NO AC CONNECTION AREA J1 SIGNAL CONNE...

Page 16: ...13 TMN TMP SERIES OPERATING MANUAL Figure 6 Rated Output Current vs Ambient Temperature Figure 7 Remote Sensing Connection...

Page 17: ...back of the rack See Section 17 for a complete description of these input and output signals 13 8 Alarm Signals Among the control and supervisory signals are two logic alarms for each module AC Good...

Page 18: ...ation is achieved by reserving one module of the total for redundancy For example if two full 19 inch racks are employed with a total of six modules then 5 1 redundancy is achieved and the full load m...

Page 19: ...1 2 3 4 5 6 7 8 9 10 FUNCTION AC Neutral N C 5V 100mA Aux DC Power Good Remote Enable Sense DC Out DC Out DC Out DC Out PIN 21 22 23 24 25 26 27 28 29 30 FUNCTION AC Line N C N C N C Current Share Rem...

Page 20: ...Good 3 20 N C 21 N C 22 Signal Common 23 Sense 24 Remote Adjust 1 25 Remote Adjust 3 J1 A TTL LO sinking 5mA or short to Pin 22 enables turns on all modules in the rack This input is referenced to Si...

Page 21: ...ule or outside the 22 5 29V range for a 24V module the unit has failed or is in current limit This signal is referenced to Signal Common Pin 22 SIGNAL PIN DESCRIPTION 18 0 INSTALLATION 18 1 Mounting S...

Page 22: ...on the TMN TMP Series except for periodic cleaning of dust and dirt around the fans and the ventilation holes A small vacuum nozzle should be used for this 20 0 TMN TMP MODULES AND RACK SETUP AND TEST...

Page 23: ...ire from J1 Pin 1 to Pin 22 The module output should turn off giving zero volts across the load The DC Good LED should go off 20 8 Checking the AC Good and DC Good Outputs Connect the lead of an exter...

Page 24: ...21 TMN TMP SERIES OPERATING MANUAL Figure 11 Checking Remote Adjust Input Figure 10 Checking AC Good and DC Good Outputs...

Page 25: ...his test each module should be connected to a separate 15A 230VAC circuit Plug the rack into the 230VAC power sources Check the load voltage with a digital voltmeter It should be very close to 24 28 o...

Page 26: ...ood LED off AC Good LED on No output DC Good LED off AC Good LED on SYMPTOM POSSIBLE CAUSE No input power Remote Enable in OFF mode Shorted output Overvoltage protection OVP has latched Check connecti...

Reviews: