TMN/TMP SERIES

OPERATING MANUAL

10.0

DESCRIPTION OF FEATURES & OPTIONS

DESCRIPTION

The input current is a sine wave in-phase with the input voltage
to give a power factor of 0.99.  Input current total harmonic
distortion meets EN61000-3-2.

The AC input range is continuous from 85 to 265VAC (TMN) or
170 to 264VAC (TMP), 47-63Hz, for worldwide operation.

This filter suppresses conducted noise from the module back
onto the AC line.  The filter meets FCC20780 part 15J Curve B
and EN55022 Curve B.

When the module is turned on from a cold start, the initial input
current is limited to a peak value of 50 amperes.

For a 48V unit the adjustment range is 45V to 58V. For a 24V
model the adjustment range is 22.5V to 29V. The adjustment is
made from the front panel by means of a 12-turn potentiometer
or from the input to the remote adjust terminal.

This input is used to remotely adjust each module output
voltage. An analog voltage from 0 to +5V controls approxi-
mately 45-58V output for a 48V module or 22.5-29V output for a
24V module. The analog inputs can also be connected together
so that the external control voltage adjusts all the module
outputs simultaneously.

If the output power converter overheats, the TMN/TMP module
will automatically shut down. The DC Good LED also turns off.
After a few minutes the module will cool and automatically start
up again.

The TMN/TMP modules are automatically connected to current
share with each other when they are inserted into the rack.  A
single-wire connection provides this.  The modules current share
with an accuracy of 10% of their full load output current for total
loads of 50% to 100%.  The rack current share pin can be used
to current share with another rack of the same output voltage.

This diode in series with each module output protects the
parallel-connected modules.  If the output of one module fails to
a short or to a lower than normal output voltage, the other
modules are not affected.  Also when hot-swapping modules,
the diode prevents a glitch in the output voltage while the output
is still rising on the inserted module.

Power Factor Correction

Wide Range AC Input

EMI Input Filter

Inrush Current Limiting

FEATURE / OPTION

Thermal Protection

Current Sharing

ORing Diodes

Output Voltage

Adjustment Range

Remote Output Adjust

Summary of Contents for TMN5000

Page 1: ...Rights Reserved UNIPOWER Corporation TMNTMP Man2 08 29 01 NORTH AMERICA 3900 Coral Ridge Drive Coral Springs Florida 33065 USA Tel 1 954 346 2442 Fax 1 954 340 7901 sales unipower corp com EUROPE Par...

Page 2: ...ions 6 10 0 Description of Features and Options 9 11 0 Mechanical Specifications 10 12 0 Safety and Industry Standards 10 13 0 Operating Information 11 14 0 Parallel Operation 14 15 0 Rack Control Sup...

Page 3: ...eries Module 7 4 TMN TMP Series Mechanical Dimensions 7 5 Rear Rack Input and Output Connections 12 6 Rated Output Current vs Ambient Temperature 13 7 Remote Sensing Connection 13 8 Parallel Connectio...

Page 4: ...modules while the system is operating The TMN Series operate worldwide with a 85 264VAC input range at 47 63Hz The TMP Series operates with a 170 264VAC input range at 47 63Hz Each module has input po...

Page 5: ...2 TMN TMP SERIES OPERATING MANUAL Figure 1 TMN TMP Series Bulk Power Front End Figure 2 TMN TMP Series Module Block Diagram...

Page 6: ...appable Modules u LED Operating Indicators u Control and Monitoring Interface Signals 3 0 PRODUCT LINE 3 1 Hot Swap Modules 3 2 Rack 4 0 SAFETY WARNINGS 4 1 These hot swap modules and racks have hazar...

Page 7: ...TICULAR PURPOSE As the sole and exclusive remedy under this warranty the manufacturer at its option may repair or replace the non conforming product or issue credit provided the manufacturer s inspect...

Page 8: ...egulates the output voltage and keeps it constant 7 2 Power Factor Correction This high frequency converter circuit switch ing at 45kHz achieves a power factor of 0 99 by forcing the AC input current...

Page 9: ...ime 3 20mS Dynamic Response 4 1 msec Temperature Coefficient 0 02 C Minimum Load 0A Overload Protection Constant Power Limiting Overvoltage Protection Latched Shutdown Active Current Share 10 Differen...

Page 10: ...G MANUAL Figure 4 TMN TMP Series Mechanical Dimensions Figure 3 Front Panel of TMN TMP Series Module HOT PLUG MODULE MATING RACK MOUNT RACK MOUNT 17 20 436 9 3 50 88 9 AC CONNECTION AREA J1 SIGNAL CON...

Page 11: ...an PHYSICAL SPECIFICATIONS Case Material Module Aluminum Rack Mount Steel Finish Rack Mount Powder Coat Gray Dimensions Inches mm Hot Swap Module 3 30 H x 4 90 W x 13 09 D 84 x 124 x 332 3 Module Rack...

Page 12: ...inputs can also be connected together so that the external control voltage adjusts all the module outputs simultaneously If the output power converter overheats the TMN TMP module will automatically s...

Page 13: ...ondi tion This protection is continuous without damage and recovery is automatic when the overload is removed Current limiting begins at about 105 of rated output current The AC Good indicator is a gr...

Page 14: ...on 18 3 and Figure 5 Both positive and negative outputs are floating and isolated from the chassis 13 3 Output Voltage The output voltage of each module is factory set to 24 28 or 48 volts 1 The volta...

Page 15: ...ING MANUAL Figure 5 Rear Rack Input and Output Connections b Uncovered AC Input Connection Area c Top View of DC Output Bus Bars a Rear Connections to Rack MODULE NO AC CONNECTION AREA J1 SIGNAL CONNE...

Page 16: ...13 TMN TMP SERIES OPERATING MANUAL Figure 6 Rated Output Current vs Ambient Temperature Figure 7 Remote Sensing Connection...

Page 17: ...back of the rack See Section 17 for a complete description of these input and output signals 13 8 Alarm Signals Among the control and supervisory signals are two logic alarms for each module AC Good...

Page 18: ...ation is achieved by reserving one module of the total for redundancy For example if two full 19 inch racks are employed with a total of six modules then 5 1 redundancy is achieved and the full load m...

Page 19: ...1 2 3 4 5 6 7 8 9 10 FUNCTION AC Neutral N C 5V 100mA Aux DC Power Good Remote Enable Sense DC Out DC Out DC Out DC Out PIN 21 22 23 24 25 26 27 28 29 30 FUNCTION AC Line N C N C N C Current Share Rem...

Page 20: ...Good 3 20 N C 21 N C 22 Signal Common 23 Sense 24 Remote Adjust 1 25 Remote Adjust 3 J1 A TTL LO sinking 5mA or short to Pin 22 enables turns on all modules in the rack This input is referenced to Si...

Page 21: ...ule or outside the 22 5 29V range for a 24V module the unit has failed or is in current limit This signal is referenced to Signal Common Pin 22 SIGNAL PIN DESCRIPTION 18 0 INSTALLATION 18 1 Mounting S...

Page 22: ...on the TMN TMP Series except for periodic cleaning of dust and dirt around the fans and the ventilation holes A small vacuum nozzle should be used for this 20 0 TMN TMP MODULES AND RACK SETUP AND TEST...

Page 23: ...ire from J1 Pin 1 to Pin 22 The module output should turn off giving zero volts across the load The DC Good LED should go off 20 8 Checking the AC Good and DC Good Outputs Connect the lead of an exter...

Page 24: ...21 TMN TMP SERIES OPERATING MANUAL Figure 11 Checking Remote Adjust Input Figure 10 Checking AC Good and DC Good Outputs...

Page 25: ...his test each module should be connected to a separate 15A 230VAC circuit Plug the rack into the 230VAC power sources Check the load voltage with a digital voltmeter It should be very close to 24 28 o...

Page 26: ...ood LED off AC Good LED on No output DC Good LED off AC Good LED on SYMPTOM POSSIBLE CAUSE No input power Remote Enable in OFF mode Shorted output Overvoltage protection OVP has latched Check connecti...

Reviews: