Page 15
P O W E R I N G T E C H N O L O G Y
Manual No. sli-15-G-3a
sli15-userguide-rev3a-0718.indd
Set Manual Switch
The MANUAL SWITCH submenu is enabled by the selecting the Mode 3 (Manual mode) setting in the
TRANSFER-SWITCH-MODE submenu.
1.12.6
Manual switch - - >
ENT
1.12.6.1
Connected to grid
1.12.6.2
Not Connected
1.12.6.3
Connected to the inverter
With this setting it is possible to force the STS to be connect the load to the grid to the inverter or
to
maintain the load disconnected.
7 The STATUS menu
SETTINGS
1
st
Level
Sub- Menu
Master Ad. "X"
Parallel mode
INFO Menu
STATUS Menu - - >
2.0
UP/
DOWN
UP/
DOWN
ENT
ESC
Serial port
address
Master Ad.1
Parallel Mode 2
Master (
or
Slave)
Parallel (
or
Stand - Alone)
Figure 8
The STATUS menu shows:
-
the current status (
Master
or
Slave
)
-
the current configuration mode (
Stand Alone mode
or
Parallel mode
)
-
the serial port address