DPAC1UT-AB-I-2-590

OPERATING MANUAL

Manual No. dpac1u-590-2

dpac1ut_ab_i_2_590-man-rev2-0516.indd

10

G

LOAD

1

A - SIDE

L2

N

L2

L1

N

L2

IN

N

1

IN

B - SIDE

10

G

L1

G

L2

L1

N

G

LOAD

L1

12 AWG

WH

RED

BLK

Figure 5 - External Wiring

 

The input terminals on each side are marked G, N, L1 & L2 and are supplied by a single phase 

120/240VAC source.  The input current rating is 25A for each side.  N, L1 & L2 terminals of 

the A side are paralleled with the B side as shown in the external wiring schematic, figure 5 

and rear view photo, figure 3, with #12AWG wire.  This allows the user to provide a single 

50A feed to either the A side or the B side.

 

The load terminals on each side A & B are marked G, N, L1 & L2 and are rated 120/240VAC 

@ 25A each.

Summary of Contents for DPAC1UT-AB-I-2-590

Page 1: ...ts Reserved dpac1ut_ab_i_2_590 man rev2 0516 indd NORTH AMERICA 3900 Coral Ridge Drive Coral Springs Florida 33065 USA Tel 1 954 346 2442 Fax 1 954 340 7901 sales northamerica unipowerco com EUROPE Pa...

Page 2: ...man rev2 0516 indd FIGURES Figure 1 Front View 4 Figure 2 Rear View 4 Figure 3 Internal Wiring 5 Figure 4 External Wiring of 5 Contents 1 0 DESCRIPTION 4 2 0 SAFETY WARNINGS 6 3 0 WARRANTY summary 6 4...

Page 3: ...ack space and can be mounted in either a 19 or 23 inch relay rack with corresponding brackets It can be mounted from the front of the rack with offsets every inch from front to back to align with exis...

Page 4: ...with a single 10 position terminal block on each side A and B see Figure 3 below Figure 3 Rear View 1 5 Figure 4 below is a schematic for the internal wiring while figure 5 is for the external wiring...

Page 5: ...ide are marked G N L1 L2 and are supplied by a single phase 120 240VAC source The input current rating is 25Afor each side N L1 L2 terminals of the A side are paralleled with the B side as shown in th...

Page 6: ...h the maximum specified ambient temperature 2 5 Reduced Air Flow Installation of these panels in a rack should be such that the amount of air flow required for safe operation is not compromised 2 6 Me...

Page 7: ...Nominal SAFETY CERTIFICATIONS UL60950 1 2nd Ed CSA22 2 No 60950 1 2nd Ed EN60950 1 2nd Ed ENVIRONMENTAL Operating Temp Range 0 C to 50 C Storage Temp Range 40 C to 85 C Humidity 0 to 95 Non Condensin...

Page 8: ...thout proper packing 6 0 INSTALLATION 6 1 Mounting This distribution panel can be mounted in either 19 or 23 inch racks by using the appropriate brackets Mount it from the front of the rack using the...

Page 9: ...7 3 Turn on the input power source Check the AC output voltage from L1 and L2 to N at each set of output terminals loads with a digital AC voltmeter The voltage should be approximately 120VAC 7 4 On...

Reviews: