Battery
Breaker Size
[A]
40A
50A
65A
Wire Size
[mm
2
/AWG]
10/6
10/6
16/4
Table 4-3 Cable Sizes
4.5.6 Symmetry Connection
1. Attach the interblock connection plates between the batteries.
2. Insert a suitably sized cable lug into one pole of the interblock connection plate. Fasten
the lugs and plates to individual battery poles.
3.
For 2-block battery symmetry measurement fix one wire of the symmetry cable to the
cable lug in the mid-point of the battery string, see Figure 4-11.
4.
For 4-block measurement fix the 3 wires (red, green and blue) of the symmetry cable to
individual cable lugs. Colour coding of the cables must be respected for proper symmetry
measurement see Figure 4-12.
Figure 4-11 2-block Symmetry Measurement (for illustration only)
Figure 4-12 4-Block Symmetry Measurement (for illustration only)