4. Operation of the personnel on duty in the case of signal for Fire condition  Stage I 

In the case of fire condition along one line the sounder of the fire extinguishing control panel produces continuous 

signal, and simultaneously the indicator 

 for fire condition and the individual indicator for fire condition of the 

respective light start to illuminate. In this event do the following: 

4.1. Turn the switch (Pos. 23) to position 

4.2. Press the buttons 

 and 

 thus the sound signaling for fire condition is switched off; 

4.3. Check as fast as possible for fire condition (smoke, heat, flames) in the indicated zone; 
4.4. Possible options for further actions: 

4.4.1. If there is no fire condition (smoke, heat, flames) and the activation of the fire detector is “false”, press 

the reset button 

. Then turn the switch to position

. The fire extinguishing control panel is turned to Duty 

Mode. If "false” activation occurs in the same zone/zones, turn the switch to position 

 and press the button 

  

to suspend the sounder. Then immediately notify the service company.  

4.4.2. In the event of fire situation leave the protected premise as soon as possible, close the doors and press 

the button Extinguishing from the outside of the premise. After the fire focus has been extinguished, reset the fire 
extinguishing control panel in Duty Mode; 

 

5. Operation of the personnel on duty in the case of signal for Fire condition  Stage II - Extinguishing 

If there is a signal for fire condition along both lines in the protected premise or a situation has occurred when it 

was needed the button Extinguishing to be pressed the fire extinguishing control panel enters Fire condition Stage II – 

the indicator 

 illuminates in flashing light. From the moment of entering Fire condition Stage II to the moment of 

activation of the extinguishing installation a time starts to run while the service personnel must to the following: 

5.1. If the fire situation is confirmed: 

  To evacuate the personnel from the premise and to close the doors tightly; 

  To undertake the measures stipulated in the Fire Rules at the site in the case of fire.  

5.2. If eventually it is found that the fire alarm is false: 

  To activate the button 

Reset 

 to suspend the extinguishing; 

  To turn the Disable Extinguishing switch to position 

Disable Extinguishing

. The indicator

 should 

start to illuminate; 

  To notify immediately the company in charge for the maintenance of the fire installation.  

 
 
 
 

UniPOS wishes you a successful work 

 

 