UniPOS Fire Extinguishing Control Panel FS5200E
Service Personnel’s Instruction Manual page2/2
4. Operation of the personnel on duty in the case of signal for Fire condition Stage I
In the case of fire condition along one line the sounder of the fire extinguishing control panel produces continuous
signal, and simultaneously the indicator
for fire condition and the individual indicator for fire condition of the
respective light start to illuminate. In this event do the following:
4.1. Turn the switch (Pos. 23) to position
;
4.2. Press the buttons
and
thus the sound signaling for fire condition is switched off;
4.3. Check as fast as possible for fire condition (smoke, heat, flames) in the indicated zone;
4.4. Possible options for further actions:
4.4.1. If there is no fire condition (smoke, heat, flames) and the activation of the fire detector is “false”, press
the reset button
. Then turn the switch to position
. The fire extinguishing control panel is turned to Duty
Mode. If "false” activation occurs in the same zone/zones, turn the switch to position
and press the button
to suspend the sounder. Then immediately notify the service company.
4.4.2. In the event of fire situation leave the protected premise as soon as possible, close the doors and press
the button Extinguishing from the outside of the premise. After the fire focus has been extinguished, reset the fire
extinguishing control panel in Duty Mode;
5. Operation of the personnel on duty in the case of signal for Fire condition Stage II - Extinguishing
If there is a signal for fire condition along both lines in the protected premise or a situation has occurred when it
was needed the button Extinguishing to be pressed the fire extinguishing control panel enters Fire condition Stage II –
the indicator
illuminates in flashing light. From the moment of entering Fire condition Stage II to the moment of
activation of the extinguishing installation a time starts to run while the service personnel must to the following:
5.1. If the fire situation is confirmed:
−
To evacuate the personnel from the premise and to close the doors tightly;
−
To undertake the measures stipulated in the Fire Rules at the site in the case of fire.
5.2. If eventually it is found that the fire alarm is false:
−
To activate the button
Reset
to suspend the extinguishing;
−
To turn the Disable Extinguishing switch to position
Disable Extinguishing
. The indicator
should
start to illuminate;
−
To notify immediately the company in charge for the maintenance of the fire installation.
UniPOS wishes you a successful work