5. Specification
6.
MODEL
400
600
800
CAPACITY
VA/W
400VA/240W
600VA/360W
800VA/480W
INPUT
Voltage
110/120VAC or 220/230/240VAC
Voltage Range
81-140VAC or 162-290VAC
Frequency
45-65 Hz (Auto Sensing)
OUTPUT
Voltage
110/120/220/230/240VAC
Voltage
Regulation
(Batt. Mode)
+/-10%
Frequency
50Hz or 60Hz
Frequency Regulation
(Batt. Mode)
+/-1 Hz
Output Waveform
Modified Sinewave
BATTERY
Battery Type
6V4Ah x 2 or
12V4.5Ah x 1
12V7Ah x 1
12V9Ah x 1
Backup Time (at a PC
load with 15” monitor)
12 minutes
23 minutes
34 minutes
Recharge Time
8 hours to 90% after complete discharge
TRANSFER
TIME
Typical
2-6 ms
INDICATOR
AC Mode
Green lighting
Backup Mode
Green flashing
AUDIBLE
ALARM
Backup Mode
Sounding every 10 seconds
Low Battery
Sounding every second
Overload
Sounding every 0.5 second
Battery Replacement
Sounding every 2 seconds
Fault
Continuously sounding
PROTECTION
Full Protection
Discharge, overcharge, and overload protection
PHYSICAL
Dimension
(mm),
DXWXH
330X100X140
WEIGHT
Net Weight
5kgs
6kgs
6.5kgs
ENVIRONMENT
Operating Environment
0- 40°C, 0-90 % relative humidity
(non-condensing)
Noise Level
Less than 40dB
INTERFACE
USB Port
Windows 98/2000/ME/XP