Installation Guide | 11
• Measurable range: 32 – 99 °F / 0 – 40 °C
• Controllable range: 40 – 95 °F / 5 – 35 °C
• Resolution: 1°F / 0.5°C
• Temperature display: °F / °C
Embedded thermistor for measuring
Room Temperature
• When temperature is below 32°F / 0°C,
temperature keeps display LO
• When temperature is above 99°F / 40°C,
temperature keeps display HI
• Sensor open/short will show “
- -
“
• Heat and Cool output will be off when sensor
open/short
Remote water temperature sensor
(for 2-pipe systems only)
• When 2-pipe system is selected (2H or 2P
mode), remote water temperature sensor must
be present
• LCD flashes error code “E1” under the following
condition –
• Sensor not connected or shorted
• When “E1” is flashing on the display, all outputs
are disabled
Temperature Measurement
Technical data
1.
Power supply
24VAC ± 20%
2.
Relay contact voltage
24VAC 50/60 Hz
3.
Relay contact current
2(1)A max
4.
Sensing Element
103AT
5.
Terminals:
2 mm2 cable
5.
Operating Temperature
32 ~ 122 °F / 0 ~ 50 °C
7.
Storage Temperature
23 ~ 122 °F / -5 ~ 50 °C
8.
Operating Humidity
5 ~ 95%R.H. non-condensing