LOOP FUNCTION
Plug
Rapid Pro
in the socket and press FUNC button for select LOOP. Press
button for select TT or TN and press button for select TEST STD or LOW.
Press the
RED
button for 2 second to start the measurement
LOOP
Fig. 8
Fig. 9
The measurament is performed according IEC/EN61557-3 it measure impedance
between Phase and Ground withouth RCD trip. Test Mode:
•
TT Measure Earth Resistance (Ω) and Contact Voltage (V) Fig.8
•
TN Measure Impedance Z L-Pe (Ω) and Ipsc prospective short circuit current
(A) Fig.9
•
Std Test with 15mA nominal current
•
Low Test with 6mA. Use this setup if during the test the RCD trip due to the
presence of leackage current in the electric system under test.
During the LOOP measurement, if the SUPER CAP is not
fully charged, the Display may switch off or decrease the
intensity, however the measurement will be performed and
shown at the end.