![Unigas RG75 Manual Of Installation - Use - Maintenance Download Page 6](http://html2.mh-extra.com/html/unigas/rg75/rg75_manual-of-installation-use-maintenance_4840569006.webp)
PART I: SPECIFICATIONS
6
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Technical Specifications
* NOTE ON THE WORKING SERVICE: the control box automatically stops after 24h of continuous working. The control box
immediately starts up, automatically.
Type
RG75
Model
G.
MD. S.
*.
A.
(1)
(2)
(3)
(4)
(5)
(6)
1
BURNER TYPE
RG75
2
FUEL
G - Light oil
3
OPERATION (Available versions)
PR - Progressive
MD - Fully modulating
AB - Double stage
4
BLAST TUBE
S - Standard
5
DESTINATION COUNTRY
* - see data plate
6
BURNER VERSION
A - Standard
Y - SpecialeSpecial
BURNER TYPE
RG75
Output
min - max kW
590 - 2050
Fuel
Light oil
Power supply
400V 3N~ 50Hz
Total power consumption
kW
3.5
Pump motor
kW
3
Light oil rate
min. - max. kg/h
50 - 173
Oil viscosity
2 - 7.4 cSt @ 40°C
Oil density
kg/m
3
840
Approximate weight
kg
150
Protection
IP40
Operation
Two stages - Progressive - Fully modulating
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service*
Intermitent