PART II: INSTALLATION
28
VR. After removal of cover screw: pressure regulation
"Note: pump with “C” rotation.
1. Inlet G1/2
2. To the nozzle G1/2
3. Return G1/2
4. Pressure gauge port G1/4
5. Vacuum gauge port G1/4
6. Pressure governor
Connecting the oil flexible hoses to the pump
To connect the flexible oil hoses to the pump, proceed as follows, according to the pump provided:
1
remove the closing nuts A and R on the inlet and return connections of the pump;
2
screw the rotating nut of the two flexible hoses on the pump
being careful to avoid exchanging the lines
: see the arrows marked
on the pump.
For further information, refer to the technical documentation of the pump.
.
Suntec T..
Viscosity
3 - 75 cSt
Oil temperature
0 - 150 °C
Minimum suction pressure
- 0.45bar to prevent gasing
Maximum suction pressure
5 bar
Rated speed
3600 rpm max.
Key
1
Inlet G3/4
2
Pressure gauge port G1/4
3
Vacuum gauge port to measure the inlet vacuum G1/4
4
To pressure adjusting valve G3/4
Suntec TA..
Oil viscosity
3 ÷ 75 cSt
Oil temperature
0 ÷ 150°C
Min. suction pressure
- 0.45 bar to avoid gasing
Max. suction pressure
5 bar
Max. return pressure
5 bar
Rotation speed
3600 rpm max.
Suntec T+TV
HP Technik UHE-A
Suntec TA
R
A
R
A
R
A