PART III: OPERATION
25
Entering the Parameter levels
By means of a proper use of the keys, it is possible to enter the various level parameters, as shown in the following flow chart:
Ph10
t10 = tempo raggiungimento posizione riposo
t10 = home run
Ph12 Pausa
Standby
(stationary)
Ph22
t22 = tempo di salita ventilatore (motore ventilatore = ON,
valvola intercettazione di sicurezza = ON)
t22 = fan ramp up time (fan motor = ON,
safety shutoff valve = ON)
Ph24
Verso posizione preventilazione
Traveling to the prepurge position
Ph30
t1 = tempo preventilazione
t1 = prepurge time
Ph36
Verso posizione accensione
Traveling to the ignition position
Ph38
t3 = tempo preaccensione
t3 = preignition time
Ph40
TSA1 = primo tempo sicurezza (trasformatore accen-
sione ON)
TSA1= 1st safety time (ignition transformer
ON)
Ph42
TSA1 = primo tempo sicurezza (trasformatore accen-
sione OFF)
TSA1 = 1st safety time (ignition transformer
OFF)
t42 = preignition time OFF
Ph44
t44 = intervallo 1
t44 = interval 1
Ph50
TSA2 = secondo tempo sicurezza
TSA2 = 2nd safety time
Ph52
t52 = intervallo 2
t52 = interval 2
Ph60
Funzionamento 1 (stazionario) Operation
1
(stationary)
Ph62
t62 = massimo tempo bassa fiamma (funzionamento 2, in
preparazione per spegnimento, verso bassa fiamma)
t62 = max. time low-fire (operation 2, prepa-
ring for shutdown, traveling to low-fire)
Ph70
t13 = tempo postcombustione
t13 = afterburn time
Ph72
Verso posizione postcombustione
Traveling to the postpurge position
Ph74
t8 = tempo postventilazione
t8 = postpurge time
Ph80
t80 = tempo evacuazione controllo tenuta valvole
t80 = valve proving test evacuation time
Ph81
t81 = tempo perdita pressione atmosferica, prova atmo-
sferica
t81 = leakage time test time atmospheric
pressure, atmospheric test
Ph82
t82 = test perdita, test riempimento
t82 = leakage test filling test, filling
Ph83
t83 = tempo perdita pressione gas, test pressione
t83 = leakage test time gas pressure, pres
sure test
Ph90
Tempo attesa “mancanza gas”
Gas shortage waiting time
Summary of Contents for LX60
Page 35: ...PART IV MAINTENANCE 35 Fig 28 Fig 29 Fig 30 B A C D E...
Page 41: ......
Page 42: ......
Page 43: ......
Page 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 52: ...8 Parameters level heating engineer...
Page 94: ...50 ERROR CODE TABLE...
Page 95: ...51...
Page 96: ...52...
Page 97: ...53...
Page 98: ...54...
Page 99: ...55...
Page 100: ...56...
Page 101: ...57...
Page 102: ...58...
Page 103: ...59...
Page 104: ...60...
Page 105: ...61...
Page 106: ...62...
Page 107: ...63...
Page 108: ...64...
Page 113: ......
Page 114: ......
Page 115: ......