background image

SIEMENS OIL BURNERS AUTOMATIC CONTROLLER LOA24

Use

LOA... safety devices are intended for use solely with QRB... photoresi-
stors, for lighting and controlling low capacity forced air light oil burners
with max. capacity 30 kg/h in accordance with standard DIN 4787.
The One or two flamess are lit through electrical connections with or
without post-ignition.

To replace LAl... AND LAB.. WITH LOA...

LOA... models can be used as replacement for LAl... and LAB.. controllers
by means of the adapter KF8819 and without the need to change the
electrical wiring. Because the LOA is smaller in dimensions, when it is
used with the adapter the external dimensions are almost identical, which
means that there is no need to move the reset button.

Performance

The controllers just need plugging in, so they can be mounted in almost
any position: on the burner, on the electrical panel or on the control panel.
The casing is made of robust heat-resistant plastic and contains:

z

the thermic programmer operating a multiple switch control system
with ambient temperature compensator 

z

flame signal amplifier with flame relay

z

warning light indicating lockout and associated sealed reset button.

The plug-in socket, also made of robust heat-resistant plastic, contains
the 12 terminals and also:

z

3 neutral terminals, ready wired up to terminal 2

z

4 earth terminals for earthing the burner

z

2 supplementary terminals numbered “31” and “32”.

The socket has two openings at the bottom for the leads; 5 others with
threaded connection for cable holders PG11 or 3/4UNP for non-metallic
sleeves are located on a mobile stuffing box, one on either side and 3 on
the front.
There are two flexible metal tongues on the sides of the socket for moun-
ting.
To dismantle it only requires gentle pressure with a screw driver in the slot
of the mounting guide. The base dimensions of the socket are exaclty the
same as for types LAB/LAI and there is no difference in the diameter of
the reset button, the two mounting screws and the flange of the burner
earth.

Safety at low voltage levels

Safety devices against any reduction in the mains voltage operate on a
special electronic circuit which, in the event of the power supply falling
below 165V~, stops the burner switching on without releasing the fuel and
locks out the apparatus.

Wiring diagram of the programme

To ensure correct wiring it is essential to observe local standards and fol-
low the instructions of the burner manufacturer with regard to assembly
and start-up.

Program's legend:

Controller output signals

Required input signals

A’Burner start up with light oil pre-heater OH

A

Burner start-up without light oil pre-heater

B

Flame lit

C

Normal operation

D

Normal stop through R

tw

Oil pre-heating time until operational all clear given through 
contact OW

tl

Pre-purge time

t3

Pre-ignition time

t2

Safety time

t3n

Post-ignition time

t4

Interval between the flame lighting and energising of solenoid 
2a at terminal 5

Internal layout

AL

Optical alarm

BV.

Fuel valve

EK

Reset button

FR

Flame relay

fr

Flame relay contacts

FS

Flame alight signal

G

Burner motor

K

Flame relay anchor to delay the tzl command in the event of a 
premature flame signal or endorse it where the signal is
correct.

OH

light oil pre-heater

OW

Operational all-clear contact

QRB Photo-resistant cell (flame detector)
R

Thermostat or pressure switch

TZ

Thermo-electric programmer (bimetal system)

tz..

TZ contacts

V

Flame signal amplifier

W

Safety thermostat or pressure switch

Z

Ignition transformer

The above are safety devices!

To tamper with them in any way may have unforeseeable conse-
quences!

Do not open them!

Technical characteristics

Voltage

220V -15%..240V+10% or
100V -15%...110V+10%

Frequency

50...60Hz +/- 6%

APPENDIX

Summary of Contents for IDEA Series

Page 1: ...MANUAL OF INSTALLATION USE MAINTENANCE LO60 LO90 IDEA series Light oil burners M039136CC Rev 2 04 2008 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES...

Page 2: ...Connecting the light oil flexible hoses 12 ADJUSTMENTS 14 Adjusting the fuel flow rate 14 Priming the pump 15 Priming the pump for single stage burners 15 Priming the pump for double stage burners 15...

Page 3: ...ins electricity gas oil or other fuel z Observe caution with hot burner components These are usually near to the flame and the fuel pre heating system they become hot during the unit operation and wil...

Page 4: ...f toxic or explosive mixtures DIRECTIVES AND STANDARDS Gas burners European directives Directive 90 396 CEE Gas Appliances Directive 2006 95 EC on low voltage Directive 2004 108 CEE on electromagnetic...

Page 5: ...ntrol box for safety reasons one controlled shutdown must take place every 24 hours z Burners provided with Siemens LMO24 44 control box the control box automatically stops after 24h of continuous wor...

Page 6: ...307 304 14 291 80 98 145 218 M8 153 96 120 108 2 291 LO60 Extended 443 58 169 274 385 304 14 291 80 98 145 218 M8 153 96 120 108 2 291 LO90 Standard 365 58 71 294 307 304 14 291 80 98 145 218 M8 153 9...

Page 7: ...ON CHAMBER mbar LO60 G TN kW LO60 G AB kW PRESSURE IN COMBUSTION CHAMBER mbar LO90 G TN kW LO90 G AB kW 0 0 5 1 1 5 2 2 5 3 20 30 40 50 60 70 0 0 5 1 1 5 2 2 5 3 20 30 40 50 60 70 0 0 5 1 1 5 2 2 5 3...

Page 8: ...dimensions 2 fix the flange of the burner to the boiler 3 install the burner into the boiler 4 according to the reference showed on Fig 2 fix the flange to the boiler s stud bolts D without completely...

Page 9: ...y the chapter WARNINGS and the Electrical connections section WARNING the burner is fitted with a bridge between terminals T6 and T8 on CN2 TAB connector external side link male connector remove this...

Page 10: ...the use of fuel pumps z Make sure that the by pass plug is not used in a single pipe installation because the fuel unit will not function properly and damage to the pump and burner motor could result...

Page 11: ...for ced circulation feed systems If the device installed is a solenoid valve a timer must be installed to delay the valve closing The direct connection of the device without a timer may cause pump br...

Page 12: ...600 rpm Key Suntec AS47 1 Pressure governor 2 Pressure gauge port G1 8 3 Vacuum gauge port G1 8 4 Solenoid valve 5 Delivery to nozzle G1 8 7 Inlet G1 4 8 Return G1 4 Key Suntec AT2 45A 1 Low pressure...

Page 13: ...l on the flexible light oil hoses and the power cord as shown in the figure while also re assem bling the cable clamp plate P in Fig 11 Fig 10 Insert the rubber seal in its seat in the burner volute a...

Page 14: ...he following chart Recommended combustion parameters Fuel Recommended CO2 Recommended O2 Light oil 11 5 13 2 9 4 9 Note all pumps are set to 12 bar The nozzle rate must be higher than the rate referre...

Page 15: ...the burner locks press the unlock pushbutton placed on the upper side of the burner and repeat the steps above 10 The oil flow rate depends on the choosen nozzle 11 Checking the combustion values adju...

Page 16: ...h flame by means of the thermostat TAB if TAB is not present insert a bridge between T6 and T8 contacts on the related connector see page 9 12 adjust the high flame air flow rate acting on the related...

Page 17: ...IN position rotating the VR screw clockwise Fig 20 Combustion setting Tab 3 LO60 Tab 4 LO90 BERGER STA4 5BO 37 Air adjustment in high flame cam I Air adjustment in low flame Stand by Ignition cam II A...

Page 18: ...AND SAFE FUNCTIONING OF THE BURNER THEREFORE ANY OPERATION OF THE APPLIANCE MUST BE PREVENTED WHICH DEPARTS FROM THE INSTALLATION OPERATIONS OR WHICH HAPPENS AFTER TOTAL OR PARTIAL TAMPERING WITH THE...

Page 19: ...on for a few seconds after the ignition of the flame post ignition time after which it is disconnected from the circuit Double stage burners 1 Set Switch G on the burner control panel in ON position 2...

Page 20: ...insulators clean adjust and replace if necessary z Disassemble and clean the light oil nozzles IMPORTANT cleaning must be performed using solvent not metal tools At the end of maintenance operations a...

Page 21: ...ing 4 adjust the electrodes to replace them if necessary disconnect the cables and unscrew the electrodes fixing screw 5 clean the combustion head by means of a vacuum cleaner use a metallic brush to...

Page 22: ...onal stop To stop the burner in the seasonal stop proceed as follows 1 turn the burner s main switch to 0 Off position 2 disconnect the power mains 3 close the fuel cock of the supply line Burner s di...

Page 23: ...the components plate and the burner cover Before disassembling the nozzle measure the real position A see Fig 26 and make a note in the table below ATTENTION check that the factory set values are obs...

Page 24: ...ATION MAINS SWITCH OPEN z FUSES INTERVENTION z MAXIMUM PRESSURE SWITCH FAULT z z AUXILIARIES RELAY FUSES INTERVEN TION z CONTROL BOX FAULT z z z z z SERVOCONTROL FAULT z SMOKY FLAME z z IGNITION TRANS...

Page 25: ...ER COFI 2170139 2170139 2170139 2170139 IGNITION TRANSFORMER DANFOSS 2170231 2170231 2170231 2170231 ELECTRIC MOTOR 2180713 2180713 2180713 2180713 SOLENOID VALVE 2190638 2190638 2190638 2190638 FLEXI...

Page 26: ...T 7 1 AIR DAMPER ADJUSTING SCREW 8 1 DAMPER SHAFT 9 1 1 NUT 9 2 1 FAIRLEAD 9 3 1 AIR INTAKE DAMPER 9 4 1 MOTOR SUPPORT PLATE 9 5 1 FAIRLEAD 9 6 1 CONTROL BOX 9 7 1 FAN WHEEL 9 8 1 MOTOR 9 9 1 PIN 9 10...

Page 27: ...C I B UNIGAS M039136CC 27...

Page 28: ...power supply terminal board MV Fan motor SATRONIC DKO976 DKW976 DKW976 Contrl box N Neutral ST Thermostats or pressure switches STA4 5B0 37 63N21L Air damper actuator TA Ignition transformer TS Thermo...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ...ssure with a screw driver in the slot of the mounting guide The base dimensions of the socket are exaclty the same as for types LAB LAI and there is no difference in the diameter of the reset button t...

Page 34: ...ty solenoid external light short circuit in the photoresisto or wiring malfunction in the flame signal amplifier etc at the end of pre purge and safety time the controller locks out the burner and sto...

Page 35: ...is restarted each time controlled switching on by R W SB takes place Operation Lock out reset button EK is the key operating element for resetting the burner control and for activating deactivating t...

Page 36: ...s using no oil pre heater Controller output signals Required input signals OH Oil pre heater QRB Photoresistive detector QRC Blue flame detector bl blue br brown sw black R Control thermostat or press...

Page 37: ...Max perm amperage at cos 0 6 LMO14 LMO24 LMO44 Terminal 1 5 A 5 A Terminals 3 and 8 3 A 5 A Terminals 4 5 6 and 10 1 A 1 A Flame supervision with QRB and QRC QRB QRC Min detector current required wit...

Page 38: ......

Page 39: ......

Page 40: ...and data subject to change Errors and omissions excepted C I B UNIGAS S p A Via L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail...

Reviews: