Removing the filter in theMULTIBLOC DUNGS MB-DLE 415 - 420 B01 1” 1/2 - 2”
Check the filter at least once a year!
Change the filter if the pressure difference between pressure connection 1 and 2 (Fig. 51-Fig. 52) Dp> 10 mbar.
Change the filter if the pressure difference between pressure connection 1 and 2 (Fig. 51-Fig. 52) is twice as high compared to the last
check.
You can change the filter without removing the fitting.
1
Interrupt the gas supply closing the on-off valve.
2
Remove screws 1 ÷ 6 (Fig. 53).
3
Change filter insert.
4
Re-insert filter housing, screw in screws 1 ÷ 6 without using any force and fasten.
5
Perform leakage and functional test, p
max.
= 360 mbar.
6
Pay attention that dirt does not fall inside the valve.