28
Checking parameters by means of the combustion analyzer go on increasing the Air (and/or VSD if provided) and the Fuel actuators.
At the end the last point will be set.
ATTENTION: Set the % output load values, for every curve-point
ATTENTION: Adjust actuators position by small changes, always checking combustion parameters.
Caution! For safety reasons, once the maximum load point P2 is set, never go down to the minimum load point P1, without
having set the other intermediate points before (see next paragraph).
Point Load 100
:2 Fuel
12
O2 Air 6.7
VSD
70
Point Load 100
:2 Fuel
12
O2 Air 6.7
VSD
70
Point Load 100
:2 Fuel
12
O2 Air 6.7
VSD
70
To choose the actuator to set, press the “left arrow”
and choose Air or VSD
Press "Enter"
to access the Air actuator value to be set.
Press keys
to change value.
Press Enter
to confirm the value and go back to Air actuator. (Do not
exit by pressing Esc from the values column because data will not be
stored)
Press arrows
to select another actuator to be set, for example,
press
to
choose
Fuel)
Press keys
to change the value. Press Enter to confirm the
value and go back to Fuel actuator
Point Load 100
:10 Fuel 90
O2 Air 50
VSD
85
Act on the pressure governor to adjust the fuel pressure at the proper value in order to reach the real
100% load of the generator/boiler.
Act only on the AIR or VSD actuators, to adjust the combustion.
Point Load 100
:2 Fuel
12
O2 Air 9.5
VSD
70
Point Load 100
:2 Fuel
12
O2 Air 9.5
VSD
70
Point Load 100
:2 Fuel
12
O2 Air 9.5
VSD
70
Point Load 100
:2 Fuel
12
O2 Air 9.5
VSD
70
Point Load 100
:2 Fuel
15
O2 Air 9.5
VSD
70
Press keys
to change value.
Press Enter
to confirm the value and go back to Fuel
actuator. (Do not exit by pressing Esc from the values column
because data will not be stored)
Point Load 100
:10 Fuel 90
O2 Air 90
VSD
100
An example of final point will be as per the display aside, imaging to set 10 curve-points.
Summary of Contents for HRX2050R
Page 40: ...PARTE III FUNCIONAMIENTO 40...
Page 51: ......
Page 53: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 60: ...8...
Page 64: ...12 2 2 LMV5x program structure...
Page 91: ...39...
Page 98: ......
Page 99: ......
Page 100: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 102: ...Annex1 Example for motor cable...
Page 103: ......
Page 104: ...Annex 2 Example for sensor cable...
Page 105: ......
Page 106: ......
Page 110: ......