PART I: SPECIFICATIONS
6
1.1 Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
1.2 Technical Specifications
* NOTE ON THE WORKING SERVICE: the control box automatically stops after 24h of continuous working. The control box
immediately starts up, automatically.
Type
HR512A
Model
MG. MD. S.
*.
A. 1.
80.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
1 BURNER TYPE
HR91A, HR92A, HR93A, HR512A, HR515A, HR520A, HR525A
2 FUEL
M - Natural gas
L - LPG
G - Light oil
3 OPERATION (Available versions)
PR - Progressive
MD - Fully modulating
4 BLAST TUBE
S - Standard
5 DESTINATION COUNTRY
* - see data plate
6 BURNER VERSION
A - Standard
Y - SpecialeSpecial
7 EQUIPMENT
1 = 2 gas gas proving system
8 = 2 gas gas proving maximum gas pressure switch
8 GAS CONNECTION
50 = Rp2 65 = DN65
80 = DN80 100 = DN100
BURNER TYPE
HR91A MG..
HR92A MG..
HR93A MG..
Output
min. - max. kW
480 - 2670
480 - 3050
550 - 4100
Fuel
Natural gas - Light oil
Category
(
see next paragraph
)
Gas rate-
Natural gas
min.- max. (Stm
3
/h)
51 - 283
51 - 323
58 - 434
Gas pressure
mbar
(
see Note 2
)
Light oil rate
min.-max. kg/h
40 - 225
40 - 257
46 - 345
Oil viscosity
cSt @ 40°C
2 - 7.4
Oil density
kg/m
3
840
Light oil train inlet pressure
bar max
2
Power supply
230V 3~ / 400V 3N ~ 50Hz
Total power consumption
kW
5.6
7.1
9.1
Electric motor
kW
4
5.5
7.5
Pump motor
kW
1.1
1.1
1.1
Protection
IP40
Operation
Progressive - Fully modulating
Gas train 50
Valves size / Gas connection
50 / Rp 2
Gas train 65
Valves size / Gas connection
65 / DN65
Gas train 80
Valves size / Gas connection
80 / DN80
Gas train 100
Valves size / Gas connection
100 / DN100
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service (*)
Intermitent
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34.02 MJ/Stm
3
); for L.P.G. (net calorific value H
i
= 93.5 MJ/Stm
3
)
Note2:
Maximum gas pressure = 500mbar (with
Siemens VGD)
Minimum gas pressure = see gas curves.
Summary of Contents for HR91A
Page 42: ...PART III OPERATION 42 Fig 18...
Page 51: ...PART IV MAINTENANCE 51 12 0 BURNER EXPLODED VIEW...
Page 53: ......
Page 54: ......
Page 55: ......