background image

Installation  

and

 

Operating  

Instructions

For

Carlin Flame Funnel

®

 

Oil Burners

Models 1050FFD and 

1150FFD

126 Bailey Rd   

 North Haven, CT 06473

Ph  203-680-9401 

Fx  203-680-9403

Tech Support 800-989-2275 

carlincombustion.com

©

 

Copyright 2016 — Carlin Combustion Technology, Inc.

Carlin Combustion Technology, Inc.

IT IS IMPORTANT THAT THE INSTALLATION OF 
THE OIL BURNER, PIPING AND FITTINGS, SAFETY 
DEVICES, CONTROLS, ELECTRICAL WIRING AND 
EQUIPMENT BE DONE IN ACCORDANCE WITH NA-
TIONAL AND/OR LOCAL REGULATIONS OF THE 
AUTHORITIES HAVING JURISDICTION OVER SUCH 
INSTALLATION.

SPECIFICATIONS

ITEM

MODEL NUMBER

1050FFD

1150FFD

Fuel Specification

No. 2  

ASTM D396

No. 2  

ASTM D396

Firing Range 

     High-Fire* 

     Low-Fire

 

15.00-25.00* 

  9.00-12.00

 

20.00-35.00* 

12.00-15.00

Motor HP, RPM, Hz

1, 3450, 60

1

1/2

, 3450, 60

Motor Volts,  1-phase 

3-phase

115/208-230** 

208-230/460**

115/208-230** 

208-230/460**

Motor Amps;  115 volts, 1-phase 

230 volts, 1-phase 

230 volts, 3 phase 

460 volts, 3 phase

16.4 

8.2 

4.0 

2.0

22.0 

11.0 

5.0 

2.5

Control Volts, Hz

120, 60

120, 60

Ignitor Volts

120

120

Burner Housing

Rugged casting

Rugged casting

Blower Wheel, Dia. x W.

7" x 5"

7

5/8

" x 5"

Flame Retention Ring, O.D.

3

13/16

"

4

1/4

"

2-Stage Fuel Unit Pressure

100

100

Low and High-Fire Oil Valve

120V, 60-Hz

120V, 60-Hz

Damper Motor with End Switch

120V, 60-Hz

120V, 60-Hz

Oil Nozzle Specs.

(3) 45°SS

(3) 45°SS

Approximate Shipping Weight

135 lbs.

145 lbs.

*

* Gph ratings are based on sea level to 2,000 ft. elevation. For every  

1,000 ft. rise over 2,000 ft., reduce the maximum gph rating by 4%.

**Motor volts and phase must be specified when ordering.

Summary of Contents for Flame Funnel 1050FFD

Page 1: ...igh Fire Low Fire 15 00 25 00 9 00 12 00 20 00 35 00 12 00 15 00 Motor HP RPM Hz 1 3450 60 11 2 3450 60 Motor Volts 1 phase 3 phase 115 208 230 208 230 460 115 208 230 208 230 460 Motor Amps 115 volts...

Page 2: ...low burner cycle operates as follows 1 Call for heat Burner motor and ignition are energized Air is in the low fire position The low fire oil valve admits oil to the low fire nozzle and its spray igni...

Page 3: ...e is correct Oil Supply Piping GENERAL In systems where the bottom of the tank is higher than or about equal to the level of the fuel unit a one pipe system may be used In systems requiring lift a two...

Page 4: ...ply to the L1 and I2 terminals of the motor contactor For three phase motors wire two 2 legs to Ll and I2 Wire the third leg directly to the motor lead that is in the motor contactor enclosure This th...

Page 5: ...NG THIS BURNER THE FIRST TIME OR AFTER CHANGING NOZZLES THE FLAME MAY GO OUT DURING THE SWING FROM LOW TO HIGH BE READY TO SHUT THE BURNER DOWN JUST AFTER THE FLAME GOES OUT REPEAT THIS UNTIL THE AIR...

Page 6: ...highfire 9 Check the flame signal on both low and high fire The Honeywell R4140M primary control with photocell should read at least 2 microamperes The Fireye D30 5010 primary control with photocell s...

Page 7: ...will be necessary to readjust the settings during operation Example Water Boiler Operating Range 170 190 F 2 Set Safety Hi Limit Cut in 200 Cut out 210 3 Set Operating Limit Cut in 180 Cut out 190 4...

Page 8: ...H O T L I N E 8 0 0 9 8 9 2 2 7 5 Carlin Combustion Technology Inc 126 Bailey Road North Haven CT 06473 Phone 203 680 9401 Fax 203 764 1714 e mail us at info carlincombustion com visit our website www...

Reviews: