SPECIFICATIONS
ITEM
MODEL NUMBER
1050FFD
1150FFD
Fuel Specification
No. 2
ASTM D396
No. 2
ASTM D396
Firing Range
High-Fire*
Low-Fire
15.00-25.00*
9.00-12.00
20.00-35.00*
12.00-15.00
Motor HP, RPM, Hz
1, 3450, 60
1
1/2
, 3450, 60
Motor Volts, 1-phase
3-phase
115/208-230**
208-230/460**
115/208-230**
208-230/460**
Motor Amps; 115 volts, 1-phase
230 volts, 1-phase
230 volts, 3 phase
460 volts, 3 phase
16.4
8.2
4.0
2.0
22.0
11.0
5.0
2.5
Control Volts, Hz
120, 60
120, 60
Ignitor Volts
120
120
Burner Housing
Rugged casting
Rugged casting
Blower Wheel, Dia. x W.
7" x 5"
7
5/8
" x 5"
Flame Retention Ring, O.D.
3
13/16
"
4
1/4
"
2-Stage Fuel Unit Pressure
100
100
Low and High-Fire Oil Valve
120V, 60-Hz
120V, 60-Hz
Damper Motor with End Switch
120V, 60-Hz
120V, 60-Hz
Oil Nozzle Specs.
(3) 45°SS
(3) 45°SS
Approximate Shipping Weight
135 lbs.
145 lbs.
*
* Gph ratings are based on sea level to 2,000 ft. elevation. For every
1,000 ft. rise over 2,000 ft., reduce the maximum gph rating by 4%.
**Motor volts and phase must be specified when ordering.