Carlin Flame Funnel 1050FFD Installation And Operating Instructions Manual Download Page 6

7.  Check draft, smoke number, C0

2

 and stack temperature. 

Typical readings are as follows for natural draft:

Fire 

Draft 

Smoke C0

2

Low-fire (higher) 

Trace  11-13% 

High-fire 

.03/.05 W.C. 

Zero 

12-14%

Adjust burner as required to obtain these readings.
8.  Stop the burner with the service switch. Wait for the 

postpurge, then turn it on again. After a prepurge period 
the burner should light-off smoothly; then go to highfire.

9.  Check the flame signal on both low and high-fire. The 

Honeywell R4140M primary control with photocell should 
read at least 2 microamperes. The Fireye D30-5010 
primary control with photocell should read near 20 volts 
DC normally, and 16-20 volts DC at saturation. For other 
control readings, see Carlin wiring diagrams.

10.  Check the flame failure response and safety lockout 

by shutting off the fuel supply (or de-energizing the oil 
valves) while the burner is running.

11.  Check the low water cut-off (if used) by depressing float 

switch or by draining water to reduce the level.

32961  110916

Summary of Contents for Flame Funnel 1050FFD

Page 1: ...igh Fire Low Fire 15 00 25 00 9 00 12 00 20 00 35 00 12 00 15 00 Motor HP RPM Hz 1 3450 60 11 2 3450 60 Motor Volts 1 phase 3 phase 115 208 230 208 230 460 115 208 230 208 230 460 Motor Amps 115 volts...

Page 2: ...low burner cycle operates as follows 1 Call for heat Burner motor and ignition are energized Air is in the low fire position The low fire oil valve admits oil to the low fire nozzle and its spray igni...

Page 3: ...e is correct Oil Supply Piping GENERAL In systems where the bottom of the tank is higher than or about equal to the level of the fuel unit a one pipe system may be used In systems requiring lift a two...

Page 4: ...ply to the L1 and I2 terminals of the motor contactor For three phase motors wire two 2 legs to Ll and I2 Wire the third leg directly to the motor lead that is in the motor contactor enclosure This th...

Page 5: ...NG THIS BURNER THE FIRST TIME OR AFTER CHANGING NOZZLES THE FLAME MAY GO OUT DURING THE SWING FROM LOW TO HIGH BE READY TO SHUT THE BURNER DOWN JUST AFTER THE FLAME GOES OUT REPEAT THIS UNTIL THE AIR...

Page 6: ...highfire 9 Check the flame signal on both low and high fire The Honeywell R4140M primary control with photocell should read at least 2 microamperes The Fireye D30 5010 primary control with photocell s...

Page 7: ...will be necessary to readjust the settings during operation Example Water Boiler Operating Range 170 190 F 2 Set Safety Hi Limit Cut in 200 Cut out 210 3 Set Operating Limit Cut in 180 Cut out 190 4...

Page 8: ...H O T L I N E 8 0 0 9 8 9 2 2 7 5 Carlin Combustion Technology Inc 126 Bailey Road North Haven CT 06473 Phone 203 680 9401 Fax 203 764 1714 e mail us at info carlincombustion com visit our website www...

Reviews: