Carlin Flame Funnel 1050FFD Installation And Operating Instructions Manual Download Page 4

32961  110916

Electrical Wiring

1.  Bring the 110-120V power supply to the control circuit 

through a fused disconnect switch as shown in the dia-
gram shipped with the burner.

2.  Wire the burner motor power supply through a fused 

disconnect switch. Refer to the diagram shipped with the 
burner. For single-phase motors, wire the power supply 
to the L1 and I2 terminals of the motor contactor. For 
three-phase motors, wire two (2) legs to Ll and I2. Wire 
the third leg directly to the motor lead that is in the motor 
contactor enclosure. This third leg is shipped from the 
factory, tagged, and capped with instructions.

3.  Refer to the specification table on page 1 for motor cur-

rent ratings.

Be sure that the supply voltage corresponds to the voltage 
as labeled on the top of the motor contactor, because the 
motor winding connections are installed at the factory for 
that voltage. 

Summary of Contents for Flame Funnel 1050FFD

Page 1: ...igh Fire Low Fire 15 00 25 00 9 00 12 00 20 00 35 00 12 00 15 00 Motor HP RPM Hz 1 3450 60 11 2 3450 60 Motor Volts 1 phase 3 phase 115 208 230 208 230 460 115 208 230 208 230 460 Motor Amps 115 volts...

Page 2: ...low burner cycle operates as follows 1 Call for heat Burner motor and ignition are energized Air is in the low fire position The low fire oil valve admits oil to the low fire nozzle and its spray igni...

Page 3: ...e is correct Oil Supply Piping GENERAL In systems where the bottom of the tank is higher than or about equal to the level of the fuel unit a one pipe system may be used In systems requiring lift a two...

Page 4: ...ply to the L1 and I2 terminals of the motor contactor For three phase motors wire two 2 legs to Ll and I2 Wire the third leg directly to the motor lead that is in the motor contactor enclosure This th...

Page 5: ...NG THIS BURNER THE FIRST TIME OR AFTER CHANGING NOZZLES THE FLAME MAY GO OUT DURING THE SWING FROM LOW TO HIGH BE READY TO SHUT THE BURNER DOWN JUST AFTER THE FLAME GOES OUT REPEAT THIS UNTIL THE AIR...

Page 6: ...highfire 9 Check the flame signal on both low and high fire The Honeywell R4140M primary control with photocell should read at least 2 microamperes The Fireye D30 5010 primary control with photocell s...

Page 7: ...will be necessary to readjust the settings during operation Example Water Boiler Operating Range 170 190 F 2 Set Safety Hi Limit Cut in 200 Cut out 210 3 Set Operating Limit Cut in 180 Cut out 190 4...

Page 8: ...H O T L I N E 8 0 0 9 8 9 2 2 7 5 Carlin Combustion Technology Inc 126 Bailey Road North Haven CT 06473 Phone 203 680 9401 Fax 203 764 1714 e mail us at info carlincombustion com visit our website www...

Reviews: