PART IV: MAINTENANCE
41
Replacing the ignition electrode
To replace the ignition electrode, proceed as follows:
1
remove the burner cover
2
disconnect the electrode (E) cable (CE);
3
remove the combustion head (see par. “Removing the combustion head”);
4
loose screw (B) that fasten the ignition electrode (E) to the burner pilot (P);
5
remove the electrode and replace it, referring to the values quoted on figure.
Checking the detection current
To check the detection signal follow the scheme in the picture below. If the signal is less than the value indicated, check the position of
the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.
ATTENTION: avoid the electrode to get in touch with metallic parts (blast tube, head, etc.), otherwise the boiler
operation would be compromised. Check the electrode position after any intervention on the combustion head.
Fig. 19: Detection by photocell QRA..
Fig. 20: Detection by photocell QRA..
P
E
CE
B
Control box
Minimum detection signal
Siemens LME7...
70µA with UV detector)
Siemens LFL1.3..
70µA with UV detector)
TERMINAL BOARD
MC
Summary of Contents for HR1025
Page 46: ...PART IV MAINTENANCE 46 10 5 2 1 1 ...
Page 47: ......
Page 49: ...LME73 000Ax PME73 831AxBC LME73 831AxBC Service instruction manual M12921CB Rel 1 2 02 2016 ...
Page 71: ...23 ...
Page 72: ...Note Specifications and data subject to change Errors and omissions excepted ...
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......