36
In the example the Gmod gas train has been set (Configuration “1”).
Choose the fuel train by pressing ENTER, then press “
+
” / “
-
”. Press ENTER to confirm: number “1” will appear on the right side of the
display.
Then press ESC
to quit. The following display is:
Press “
+
” to show the first point to be set P0.
Press
F
and
“+”
to increase the opening angle of the fuel actuator “
0F”
until the requested value is reached (for example
12
°
÷15°
, see
below) for the ignition point; or press
F
and
“-”
to decrease the angle:
To set the air damper opening angle “0A” in the ignition point (
1
0
° for example - see below), press “A” and “+” “A” and “-” at the
same
time:
LMV37:
Now the air and fuel quantities are set at the ignition point P0:
By pressing “+”, point P9 can be programmed to set the air and fuel values at the maximum output
go on as described above to the the opening angles of the air actuator (A) and fuel actuator (F):
Lo 3-stage
Summary of Contents for C83X
Page 42: ......
Page 43: ......
Page 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023 ...
Page 52: ...8 Parameters level heating engineer ...
Page 94: ...50 ERROR CODE TABLE ...
Page 95: ...51 ...
Page 96: ...52 ...
Page 97: ...53 ...
Page 98: ...54 ...
Page 99: ...55 ...
Page 100: ...56 ...
Page 101: ...57 ...
Page 102: ...58 ...
Page 103: ...59 ...
Page 104: ...60 ...
Page 105: ...61 ...
Page 106: ...62 ...
Page 107: ...63 ...
Page 108: ...64 ...
Page 113: ......
Page 114: ......
Page 115: ......
Page 117: ...IG FU B ...
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......