Close Control Regulation Program
62 06MC0071@00B0110
01/10/2012
DEFAULT VALUES
CONFIGURATION
NUMERICAL
PARAMETERS
PARAMETER DESCRIPTION
DEF. PARAMETER
DESCRIPTION VAL. DEF. MIN. MAX.
CONTROL PARAMETERS
SET POINT
Heating
No Cooling
Set
point
Hot water coil
No
with Room Temperature
°C
23.0
17.0
35.0
Hot gas coil
No
Cooling Propor. Band
°C
1.5
0.5
9.9
External Humidifier (On/Off)
No
2
nd
cooling set point
°C
17.5
17
35
External Humidifier (0-10V)
No
Cooling Set point
Delivery sensor
No
with Delivery Temperature
°C
17.0
17.0
35.0
2
nd
Cooling SetP. of the remote cont.
No Cooling
Propor.
Band
°C
15.0
0.5
18.0
Flooding
No Heating
Set
point
°C
23.0
12.0
30.0
Smoke/Fire
No Heating
Propor.
Band
°C
1.5
0.5
9.9
External sensor
No
Dehumidifier Set point
rH %
55
20
90
AFPS
No
Dehumidifier Propor. Band
rH %
05
03
15
Disable BP transitory start limit
No
Humidifier Set point
rH %
45
20
90
Off unit with flood alarm
No
Humidifier Propor. Band
rH %
05
03
20
Off water valve with flood alarm
No
Delivery T. Set Limit
°C
14.0
10.0
25.0
Remote On/Off of via digital input
No
SETPOINT COMPENSATION
Remote On/Off of via serial
No
P1:Delivery SetP.
°C
17.0
14.0
35.0
Motorized
damper
No P1:Room
Temp.
°C
22.0
17.0
35.0
Buzzer enabled
Si
P2: Delivery SetP.
°C
18.0
14.0
35.0
Dehumidification
Si
P2: Room Temp.
°C
20.0
17.0
35.0
Humidification No
SET ALARMS
SetP. change of the Dehum. CW
No
High Room Temp.
°C
30.0
20.0
40.0
Enabled High T.Delivery alarm
No
Low Room Temp.
°C
10.0
0.0
32.0
SetP. compen. of the CW working
Si
High Room Humidity
rH %
80
40
99
Enabled Set Back mode
No
Low Room Humidity
rH %
30
0
65
Enabled Fan Cyclical Start
No
High Delivery Temp.
°C
23.0
10.0
40.0
Enabled ON/OFF cycle
No
SET BACK MODE
“A” AND “B” ALARMS TYPES
Min. Room Temp.
°C
16.0
5.0
24.0
Loss of Air Flow
A
Max. Room Temp
°C
28.0
20.0
35.0
Clogged Filters
A
Min. Room Humidity
rH %
35
20
60
Heaters Overheating
A
Max. Room Humidity
rH %
75
50
90
EEPROM Failure
A
Fan cyclical start time
min
30
15
99
Wrong Password
A
TIMER THRESHOLD
High Air Flow
A
Timer threshold
h
0
0
32000
High Cond.Pressure
A
CHANGE PASSWORD
*(password found in the envelope enclosed with the manual)
Low Evap.Pressure
A
Password Settings
n°
xxxxx
00000
32000
EXV Valve Failure
A
Password Service
n°
xxxxx
00000
32000
High Room Temp.
A
LAN SETTINGS
Low Room Temp.
A
Lan units number
n°
0
2
10
High Room Humidity
A
Cycle time
h
168
1
98
Low Room Humidity
A
Number of Stand-by units
n°
1
1
2