UNIFIRE FORCE 50 Robotic Nozzle
Installation and setup manual
MECHANICAL INSTALLATION
Installing The Robotic Nozzle
By now we assume you have decided if the Robotic Nozzle
is to be installed on the wall, or hanging from the ceiling.
The FORCE 50 Robotic Nozzle is fitted with a DN50/PN16
flange (or similar size 2” ANSI flange or JIS flange).
!
WARNING
The maximum reaction force at 2000 lit/min and 10 bar is
1400 N. The mounting pipe and bracket must withstand
minimum 8 000 N of Force, to provide a safe and stable
base.
The flange itself provides the required support to hold
the FORCE 50. Additional support and brackets must be
applied to the feeding pipe to keep it stable under operation.
This is especially important during fully automatic operation.
Use suitable M16 bolts and a flat seal to install the flange.
!
CAUTION
Clearance!!
Take special precaution to ensure the Robotic Nozzle can
move and rotate /- 90° in all directions
Make sure there are no obstructions with 600 mm from the
centre of rotation
Clearance behind/above minimum 350 mm
Clearance each side 600 mm
Clearance each side 600 mm
The FORCE 50 weighs 19 Kg incl flange and nozzle