background image

 

Manual – 3000 NRL Family

 

 

Unidata Manual - 3000 NRL Family - 17 09 2018.docx 

Page 23 

 

            3004B-M0 and 3004B-MC – Product Options  

 

 

 

 

 

 

 

 

4.5 

3004B-ME Neon Remote Logger Ethernet 

 

The 3004ME Neon Remote Logger 
Ethernet is a Neon Remote Logger in the 
3004M range which has a smaller form 
factor than the standard metal enclosure 
3004. It is housed in a polycarbonate case. 
It utilises the Ethernet networks as its 
method of sending sensor data from the 
field to the Neon Server. 
 
 

4.5.1 

3004B-ME Specifications  

Physical specifications 

Material: 

 

Polycarbonate

 

Size: 

 

190mm x 80mm x 55mm (LxWxH)

 

Weight: 

 

300 grams

 

Operating Temperature:

 

-20°C to 60°C. Not affected by humidity

 

Antennae: 

 

n/a

 

Electrical Specifications 

External Power:

 

9 to 30V DC (provision for dual power inputs) 

Current Draw:

 

50µA Standby

 

Internal Power:

 

3.6 Volt Lithium D Cell

 

Instrument Power

:  

5V or 12V or 18V regulated, 80mA User Selectable 

Instrument Reference 
Voltage:  

5V 10mA Max

 

Analog channels:

 

4 Single ended (0-5000mV) with 24 bit resolution

 

Modbus:

 

1xModbus RS485 RTU protocol, 57600 baud max

 

SDI-12:

 

1xSDI V1.3 Compliant, instrument mode

 

Model Number 

Description  

3004B-M000 

NRL No Modem No Batteries (no LCD) 

3004B-M0B0 

NRL No Modem with Lithium Battery (no LCD) 

3004B-M00L 

NRL No Modem No Batteries with LCD 

3004B-M0BL 

NRL No Modem with Lithium Battery with LCD 

3004B-MC00 

NRL 3G/4G Modem No Batteries (no LCD) 

3004B-MCB0 

NRL 3G/4G Modem with Lithium Battery (no LCD) 

3004B-MC0L 

NRL 3G/4G Modem No Batteries with LCD 

3004B-MCBL 

NRL 3G/4G Modem with Lithium Battery  with LCD 

Summary of Contents for Neon 3016A

Page 1: ...08 Any changes or modifications to this equipment not expressly approved by the manufacturer Unidata Pty Ltd could void the user s authority to operate this equipment Revision History File name Revisi...

Page 2: ...rmware Update Indication 11 3 0 NRL Status Menu Screens 11 3 1 Logger Status Screen Navigation 12 3 2 Scheme Status Data 13 3 3 Configure Logger 14 4 0 Summary of Neon Remote Loggers 16 4 1 3016A Neon...

Page 3: ...and reducing cost The communication protocol between Neon Field Units Neon Remote Loggers and the central Neon Server is Internet Protocol TCPIP and LoRa LPWAN technology protocol The communications...

Page 4: ...Manual 3000 NRL Family Unidata Manual 3000 NRL Family 17 09 2018 docx Page 4 Overview of the Neon System...

Page 5: ...ceives processes displays stores and reports collected data in many ways The Neon Server also can issue control commands based on pre set algorithms and issue alarms and notifications via several medi...

Page 6: ...the Neon Servers and the telecommunication provider gateways This means that NRL units can be used anywhere in the world provided there is an internet connection available The connection to the intern...

Page 7: ...rates logger interval etc and various engineering unit definitions These files are called for example the LDR and KBD files 2 A COMMUNICATOR section which deals with communications to the server This...

Page 8: ...and has a memory layout and configuration settings broadly the same It allows existing NRT schemes to be used immediately without change In Emulation mode the logger operates like a Prologger 3016 or...

Page 9: ...ion port which is used for configuration and local programming unloading Red indicates the logger has detected something plugged in but not communicating Green indicates successful communication Schem...

Page 10: ...e control but by default green indicates correct operation Unless the logger is communicating no other LEDs will be lit 2 4 Telemetry Indication When the logger communicates with Neon the Neon COMS LE...

Page 11: ...on the LCD touch display There are two streams of Logger Status data You can toggle between these by again pressing the LOGGER STATUS button The status values that can be displayed are as below Parame...

Page 12: ...n The Logger Status screen has two pages that can be scrolled using the UP DOWN keys Pressing the LOGGER STATUS button on the LCD screen will toggle between the two pages Press ENTER Press LOGGER STAT...

Page 13: ...keys A00 910 491mV A01 914 145mV A02 915 391mV A03 914 716mV A04 913 443mV A05 913 297mV A06 912 669mV A07 915 209mV Logger Status Scheme Status Configure Logger LoRa EUI 0000000000000000 100V001_001...

Page 14: ...a parameter the DOWN and UP keys should be used to navigate to the desired parameter The LEFT and RIGHT keys in combination with the DOWN and UP keys can be used to select and change values 3 3 1 Gene...

Page 15: ...iority 3G 4G SIM2 priority Serial Satellite priority Serial X Bee priority Set SIM1 APN Access Point Name and corresponding Username and Password for the SIM1 SIM2 Satellite communications interfaces...

Page 16: ...r the operation of all the models is very similar The difference in the models is based on the number of sensor interfaces the connectivity options and if the customer wishes to have a small display o...

Page 17: ...n FET 30V DC 250mA max Relays 2 Normally Open and Normally Closed Contacts 1A 30V DC 0 5A 125V AC Configuration Port RS232 serial port 230400 maximum baud rate USB B port Optional Bluetooth Low Power...

Page 18: ...on Remote Logger Ethernet 3G 4G and LoRa 16 Analog Channels Touch Screen Display 4 2 3008A Neon Remote Logger 8 Analogue Channels The 3008 Neon Remote Logger NRL is self contained data logger RTU with...

Page 19: ...nal internal 3G 4G Modem Dual SIM card support RS232 Interface for connection of external Satellite Modem Serial Instrument RS232 port full implementation all 9 signals available baud rate 230400 max...

Page 20: ...Analog Channels Touch Screen Display 3008A CL0 Neon Remote Logger Ethernet 3G 4G and LoRa 8 Analog Channels Touch Screen Display 4 3 3004A Neon Remote Logger 4 Analogue Channels The 3004 Neon Remote...

Page 21: ...al Instrument RS232 port full implementation all 9 signals available baud rate 230400 max LCD Display Optional 320 x 240 Colour Resistive Touch Panel Keypad LCD option l 5 button membrane keypad Accel...

Page 22: ...ual power inputs Current Draw 50 A Standby Internal Power 3 6 Volt Lithium D Cell Instrument Power 5V or 12V or 18V regulated 80mA User Selectable Instrument Reference Voltage 5V 10mA Max Analog chann...

Page 23: ...n a Electrical Specifications External Power 9 to 30V DC provision for dual power inputs Current Draw 50 A Standby Internal Power 3 6 Volt Lithium D Cell Instrument Power 5V or 12V or 18V regulated 80...

Page 24: ...on Remote Logger Microsatellite is a Neon Remote Logger in the 3004M range which has a smaller form factor than the standard metal enclosure 3004 It is housed in a polycarbonate case It utilises a mic...

Page 25: ...1xSDI V1 3 Compliant instrument mode Unidata HSIO High speed serial interface Counters 4 2 x 16 bit DC to 3KHz potential free contacts or 0 to 5V DC digital input C0 C2 2 x 16 bit DC to 300Hz potenti...

Page 26: ...rbonate Size 190mm x 80mm x 55mm LxWxH Weight 300 grams Operating Temperature 20 C to 60 C Not affected by humidity Antennae On board stub antenna optional external whip antenna Electrical Specificati...

Page 27: ...nate Size 190mm x 80mm x 55mm LxWxH Weight 300 grams Operating Temperature 20 C to 60 C Not affected by humidity Antennae On board stub antenna optional external whip antenna Electrical Specifications...

Page 28: ...t Options Model Number Description 3004B ML00 NRL LoRa No Batteries no LCD 3004B MLB0 NRL LoRa with Lithium Battery no LCD 3004B ML0L NRL LoRa No Batteries with LCD 3004B MLBL NRL LoRa with Lithium Ba...

Page 29: ...e Counters 1 x 16 bit DC to 300Hz potential free contacts or 0 to 5V DC digital input C0 Configuration Port USB serial port Operating Frequencies Option C 2G 3G and 4G Option L AU915 US915 EU868 AS923...

Page 30: ...2018 docx Page 30 5 0 CONNECTIONS This section provides brief descriptions of available connections terminations for all 3000 range loggers The tables below list each termination with a brief descrip...

Page 31: ...S NO1 Normally open 1 1A 30Vdc 0 5A 125VAC COM1 Common 1 NC1 Normally closed 1 1A 30Vdc 0 5A 125VAC NO0 Normally open 0 1A 30Vdc 0 5A 125VAC COM0 Common 0 NC0 Normally closed 0 1A 30Vdc 0 5A 125VAC IN...

Page 32: ...D7 ve differential AGND Analog Ground AGND Analog Ground A13 D6 A13 ve single D6 ve differential A12 D6 A12 ve single D6 ve differential AGND Analog Ground ANALOG INPUTS AGND Analog Ground A3 D1 A3 v...

Page 33: ...Manual 3000 NRL Family Unidata Manual 3000 NRL Family 17 09 2018 docx Page 33 5 2 3008A Neon Remote Logger Connections Terminations...

Page 34: ...d 0 1A 30Vdc 0 5A 125VAC NO1 Normally open 1 1A 30Vdc 0 5A 125VAC COM1 Common 1 NC1 Normally closed 1 1A 30Vdc 0 5A 125VAC INST PWR 12V 12V regulated 200mA fused GND Ground 5V 5V regulated 100mA fused...

Page 35: ...Manual 3000 NRL Family Unidata Manual 3000 NRL Family 17 09 2018 docx Page 35 5 3 3004A Neon Remote Logger Connections Terminations...

Page 36: ...d SDI 12 SDI 1 SDI 12 Signal RELAYS NO0 Normally open 0 1A 30Vdc 0 5A 125VAC COM0 Common 0 NC0 Normally closed 0 1A 30Vdc 0 5A 125VAC 5V 5V regulated 100mA fused GND Ground COUNTERS GND Ground C 3 16...

Page 37: ...ections Terminations Terminal Connection Description OUT OUT0 Digital Output0 Open Drain FET 30V DC 250mA max GND Ground SDI 12 SDI 1 SDI 12 Signal GND Ground EXT PWR GND External Power Supply PEXT Ex...

Page 38: ...18V Regulated 80mA AREF Instrument Reference Voltage 5V 10mA Max CN12 UPS Instrument Power 5V or 12V or 18V Regulated 80mA UPS Instrument Power 5V or 12V or 18V Regulated 80mA GND Ground GND Ground A...

Page 39: ...ire JP4 OPEN P8 C0 N A N A P1 SDI SDI 12 Signal White P9 GND N A N A P2 MB Ground Blue P3 MB Ground Green P7 GND Insitu housing GND TBA P4 ILP N A N A P5 IPWR External Power Red P6 G LP A Ground Black...

Page 40: ...o feed return current through loop current sensing resistor P8 C0 N A N A P1 SDI N A N A P9 GND N A N A P2 MB N A N A P3 MB N A N A P7 GND Insitu housing GND TBA P4 ILP Loop Supply Output Brown P5 IPW...

Page 41: ...ric Counter Mode JP Config Connection Description Cable Colour JP1 CLOSED to supply power to sensor via Red P5 JP2 OPEN JP3 OPEN JP4 OPEN P8 C0 Counter Input TBA P1 SDI N A N A P9 GND Ground TBA P2 MB...

Reviews: