background image

 

 

 

5

/10 

 

Warning:

 

!

 

The earthed mounting structure "C" must be connected to the reference potential of the evaluation 
unit (X1/3) via its own line! 

The potential of the mounting structure (PE) serves as a reference potential for the evaluation 
unit. 

!

 

The number of spacers should be calculated and distributed over the length of the electrodes to 
guaranty reasonable mechanical stability. 

!

 

The  measurement  and  opposite  electrodes  must  be  fixed  on  the  mounting  structure  avoiding 
electrical  contact.  Ignoring  this  rule,  will  change  the  way  the  electrodes  work  and  make  them 
unusable for the application. 

2.3

 

Configurations and Indication elements 

2.3.1

 

SW1: Set sensitivity (relay switching point) & start calibration (SW2-2 OFF) 

With the rotational selector SW1 the sensitivity (switching point of the relay) is set and a new adjust-
ment of the bias point of the S-SW-8 can be triggered. 

● 

SW1 cw rotation

 

→ Increase sensitivity 

 

SW1 a-cw rotation

 

 Decrease sensitivity 

● 

SW1 > 5s pushing

  → New calibration of the sensor is done. The LED4 blinks until the calibration 

process  is completed (up  to  60s). The  settings of sensitivity,  hysteresis 
and memory function are preserved. 

 

2.3.2

 

SW2: Setting of functional properties 

The 2-poles switch SW2, leads to the following behavior of the evaluation unit: 

Hysteresis

 

 

Memory-Function

 

 

 

SW2-1

 

 

SW2-2

 

 

 

ON 

10 %   

ON 

active 

 

 

OFF 

5 % 

♥ 

OFF 

inactive  ♥ 

♥ = Default values

 

 

● 

Hysteresis

 

(5 or 10%) 

:

  It  is  the  difference  in  the  sensor  signal  between  the  switch-on  point 

(occupied) and the switch-off point (free) for the relay. 
The  sensor signal  level  for the  switch-ON  point  is  stronger than the 
switch-OFF point. A larger hysteresis means that the switch ON/OFF 
points are distanced. 

● 

Memory Function OFF

 

SW2-2 = OFF

 

:

 

Each time the power supply of the evaluation unit is switched ON, 
a new adjustment is started automatically.

 

The last set sensitivity counter is retained, but all other operating pa-
rameters are reset to the current operating situation. The readjustment 
means that any objects that are located in the detection area are "for-
gotten". This means that the relay is dropped out, even if it was ON in 
the last power down. Only additional objects would switch the relay on 
again!  

● 

Memory Function ON

 

SW2-2 = ON

 

:

 

When the power supply of the evaluation unit is switched ON, no 
new  adjustment  is  made.

  The  last  valid  operating  parameters  are 

restored from nonvolatile memory and used. Changes in the reference 
conditions in the meantime are taken into account by moving the ref-
erence point. 

This function is useful and recommended if there is a work-piece 
in the detection area at the time of switch-OFF and should be rec-
ognized when it is switched ON again. However, it must be the 
same object in the same position

, otherwise the difference is treated 

as a change in the reference conditions. This would result in an invalid 
displacement of the reference point and thus a malfunction. 

 

 

Case a detected object is removed from the detection area while 
the sensor is turned-OFF, in the next turning-ON, the sensor will 
incorrectly behave as if the object is still there and the relay will 

Summary of Contents for S-SW-8

Page 1: ...manual adjustment switch SW2 2 to OFF 6 2 4 2 Sensitivity setting relay switching point 6 2 5 Technical Data 7 3 Montage Cabling 8 3 1 System arrangement 8 3 2 Electrical connections 9 4 Installation...

Page 2: ...the sensitivity is set appropriately the presence of the new objects is detected A potential free contact relay turns ON OFF according to the IN OUT movement of objects over the sensing area the swit...

Page 3: ...Connections Con nector Pin Connection X1 1 24 VAC DC Supply Voltage Both polarity accepted 2 3 PE Reference Potential Connected to the earth X2 1 C Relay common contact 2 NO Relay normally open contac...

Page 4: ...of the evaluation unit via the shield of the coaxial cable Montage structure C The design of the mounting structure depends on the conditions at the installation place It must be made of conductive ma...

Page 5: ...switch on point occupied and the switch off point free for the relay The sensor signal level for the switch ON point is stronger than the switch OFF point A larger hysteresis means that the switch ON...

Page 6: ...ves the reference value of the system The sensor electrodes must be free when performing a new adjustment No objects or person may be near the sensor electrodes SW2 2 OFF Memory OFF After power ON the...

Page 7: ...n 2 5 Technical Data Parameter Sim Condition min tip max Unit Supply Voltage UV AC DC 18 24 30 V Operation Power IV 18V UV 30V 3 W Environment Tempera ture TF In operation 15 20 55 C TL Storage 20 60...

Page 8: ...ts to be detected This ensures safe switching behavior The evaluation unit should be installed near the sensor electrodes The sensor line coaxial cable between the evaluation unit and sensor electrode...

Page 9: ...e 5 Connect the reference potential of the evaluation unit X1 3 direct to the earthed mounting struc ture 6 Connect the supply voltage 24VAC DC to the evaluation unit X1 1 X1 2 7 First operation By th...

Page 10: ...timum sensitivity for the working object is set LED2 confirms the process by flashing briefly 2 Manual Relay OFF LED5 OFF Rotate the switch SW1 clock wise until the relay switches ON plus three more p...

Reviews: