Unicont SPb Ltd
Technical Documentation PCH-205
Page
15
3.
Deliver cables of connected devices to the PS. When selecting, use the cable with an
appropriate core section (see Cable Core Section Table, Table 7 and Figure 9).
Table 7. Types of Cables and Section of the Cores Connected to the Terminals of PCH-205
Terminal
Terminal Purpose
Terminal Name
Core
Section
Recommended
Cable Types
1 J1.1 Connection of SB
BATTERY INPUT
16 mm
2
КМПВ
(
Э
) (2
х
16)
2
J3.2
Connection of load
(0 ... 20
А
)
24 VAC Output
4 mm
2
КМПВ
(
Э
) (2
х
4)
3 24
VAC
Output
4 J3.1
Connection of load
(0 ... 40 A)
24 VAC Output
10 mm
2
КМПВ
(
Э
) (2
х
6)
5 J3.6
Connection of load
(0 ... 10 A)
24 VAC Output
2.5 mm
2
КМПВ
(
Э
) (2
х
1.5)
6 J3.5
24
VAC
Output
7 J3.4
24
VAC
Output
8 J3.3
24
VAC
Output
9 J5
Connection of input
supply
220 VAC INPUT
6 mm
2
КМПВ
(
Э
) (3
х
1.5)
10 J11
Connection of an alarm
unit
AU-106
1.5 mm
2
КУПЭВ
(2
х
2
х
0.5)
11 J9
Connection of a
temperature sensor
TS
КУПЭВ
(2
х
2
х
0.5)
12
J14
Connection of storage
battery control unit
Remote/Bat_control
КМПВ
(
Э
) (2
х
0.5)
J8
КУПЭВ
(2
х
2
х
0.5)
4.
Remove the device lid.
5.
Pass connecting wires of the power supply circuit, electric power storage, etc. of the
connected devices through the gaskets located at the bottom part of the device housing.
IMPORTANT!
Before delivering cables to the PS, make sure in lack of voltage in
them.
6.
Earth the PS housing in the commom earthing bus of the vessel. An earthing bolt is
located from the right side at the bottom part of the PS housing (see Figure 8).
7.
Connect wires of the storage battery and external device to the terminals of the
charging device according to the connection diagram (Figure 9).
8.
Check compliance of onboard supply with the requirements of the OM (220 V,
50/60 Hz).
9.
Connect a power supply cable to the terminals of PS “220 VAC INPUT” (see Figure
9) according to the following designation:
L
Wire of the phase
Protective earth
N
Neutral wire