The circuit number can also be set by using the iSERIES remote. To set the circuit, follow these steps: 

1.

 

Power the indoor unit ON (or outdoor unit if power is from the outdoor unit). 

2.

 

Set the remote controller according to the table below.  

3.

 

Press the FAN and IFEEL keys of the remote controller at the same time and hold for more than 5 seconds, then 
release them while pointing the remote control towards the indoor unit to be set.  

If the setting is correct, you will hear 4 BEEPS as confirmation and the indoor unit starts operating with the new address. 

 

 

 

After the wiring and piping is complete, verify that the system is fully communicating to each device.  
 

1.

 

Power ON the system. 

2.

 

Set the remote controller of unit 

1

 as follows (units 

2

3

, and 

4

 must be OFF): 

 

Mode: cooling 

 

Filter: ON 

 

Set point: 90 °F (32 °C) 

3.

 

Press FAN + IFEEL button for at least 5 seconds, pointing the remote control unit directly at the air conditioner 
receiver.  
System starts and runs for 3 minutes. 
During this operation TIMER LED is flashing, while OPERATION LED is ON. 
After 3 minutes operation: 

 

If the setting is right, the unit switches to COOL mode and stops (set point: 90 °F [32 °C]). The system is ready to 
operate.  

 

If the setting is wrong, the STANDBY lamp flashes; check the setting of indoor units and the connections of the 
refrigerant circuits. 

 

button

settings to select the Circuit number

Circuit

1

Circuit

2

Circuit

3

Circuit

4

ON

OFF

AUTO

52 °F (11 °C)

54 °F (12 °C)

55 °F (13 °C)

57 °F (14 °C)

ON

ON

ON

OFF

OFF

OFF

AUTO

AUTO

AUTO

AUTO

AUTO

AUTO

AUTO

filter

night mode / high mode

operating mode (COOL - HEAT)

set point

flap

CIRCUIT NUMBER (Method B 

– Using the iSERIES Remote)

 

VERIFY COMMUNICATIONS

 

Summary of Contents for IS12MPA iSeries

Page 1: ...Room temperature 91 F 27 C D B Cooling Minimum conditions Outdoor temperature 5 F 15 C D B Room temperature 50 F 10 C D B 17 F 6 C W B Heating Minimum conditions Outdoor temperature 25 F 32 C D B Roo...

Page 2: ...connection points and a possible fire hazard Do not allow wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and...

Page 3: ...areas where electrical wiring or conduits are located DO Choose places as cool as possible and well ventilated use lug bolts or equal to bolt down the unit reducing vibration and noise Deoxidized anne...

Page 4: ...anel as a template Check the horizontal position with the level Mark the holes to be made Drill a 2 5 inch 65 mm diameter hole Insert a 2 inch PVC pipe and secure in place Prepare wall for attachment...

Page 5: ...h lightly on the shown marks arrows Tubing connections on right or left side Cut a corner of the frame The refrigerant tubes and drain hose are on the right side of the unit The drain tray is supplied...

Page 6: ...se of the unit into the hole in the wall then hang the unit on the panel previously mounted on the wall Connect the line set to the refrigerant tubing on the outside of the wall refer to outdoor unit...

Page 7: ...unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected Install the condensate drain to the outside with a positive slope The condensate can then be carried awa...

Page 8: ...rotection MOP IS18G50 1 phase 60 Hz 208 230 V 10 0 13 20 IS24G65 12 5 16 25 IS30G80 16 0 20 35 IS36G110 22 0 28 50 Indoor units MODEL Power Supply Full Load Current Minimum Circuit Ampacity MCA Maximu...

Page 9: ...rews and hang the remote control unit To reset the indoor unit to default factory setting set the remote control as follows Filter ON Night Mode High Power Mode OFF Operation mode AUTO Flap AUTO Set p...

Page 10: ...NG Disconnect the power 1 Disconnect the power of indoor unit 2 Remove the batteries from the remote control unit 3 Set the micro switches see table The switches are located in the battery compartment...

Page 11: ...circuit board inside the control box Disconnect the power of indoor unit Set the micro switches see table below Switch on the indoor unit At this point the system will operate with the new address OU...

Page 12: ...et the remote controller of unit 1 as follows units 2 3 and 4 must be OFF Mode cooling Filter ON Set point 90 F 32 C 3 Press FAN IFEEL button for at least 5 seconds pointing the remote control unit di...

Page 13: ...lso be used to reach 77 but this will not change the display from Celsius to Fahrenheit or vice versa 4 To finish the switch press and hold the Filter Shift button for 6 seconds This will cause the re...

Reviews: