Technical features and dimensions
ENGLISH
paraMeTers prOgraMMaBle BY Technician and prOTecTed BY access cOde FOr heaTing
cOnTrOller e8
INSTALLATION
Description
Value range
Default
Individual values
COdE NumBEr
0000 - 9999
ENTrY
COdE NumBEr (adjustment)
0000 - 9999
0
BOILEr BuS Id
......, 01 - 08
----
BuS Id 1
(00), 01 - 015
1
BuS Id 2
(00), 01 - 016
2
AF SuPPLY
00,01 (OFF/ON)
01 (ON)
BuS CONNECTION
1
1
BuS SuPPLY
00,01 (OFF/ON)
01 (ON)
TEmPErATurE mASTEr
00, 01 (OFF/ON)
01 (ON)
mAX-T HS1 mAX T-HEAdEr
30 °C - 110 °C
85 °C
mIN-T HS1 mIN T-HEAdEr
10 °C - 80 °C
10 °C
mAX-T HS2
30 °C - 110 °C
85 °C
mIN-T HS2
10 °C - 80 °C
10 °C
CurVE VOLTAGE
0 - 11
11
CurVE11-u2
0,00-10,00V
0V
CurVE 11-u2
0,00-10,00V
10V
CurVE 11-T1
00 - 120 °C
0 °C
CurVE 11-T2
00 - 120 °C
100 °C
CurVE 11-uA
0,00-10,00V
0V
T-WArmE-uP
10 °C - 85 °C
10
mINImum LImIT
00, 01, 02
0
HYSTErESIS
2K - 20K
5
HYSTErES TImE
00 - 30 min
00 min
BOILEr dETECTEd
dISPLAY ONLY
OuTPuT LEVEL
00 - 1000kW
* see note
NEW CONFIGurATION
00,01 (OFF/ON)
mINImum mOduLATION CASCAdE
00 - 100
0
dHW LEVEL
00 - 08
0
CONTrOL VArIANCE
(K)
dISPLAY
NOmINAL OuTPuT INdEX
0 - 100%
dISPLAY
SWITCH VALuE
(-99) - 0 - (99)
dISPLAY
BLOCK TImE
rEmAINING (min)
dISPLAY
mAXImum BOILEr TEmPErATurE
50 - 110 °C
85
BOILEr dYNAmICS uPWArd
20 - 500K
30K
BOILEr dYNAmICS dOWNWArd
20 - 500K
20K
rESET TImE
5 - 500
50
mOduLATION mAX
0% - 100%
80%
mOduLATION mIN
0% - 100%
50%
mIN mOduLATION HS
0% - 100%
0%
mOduLATION dHW
40% - 100%
80%
BOILEr SEQuENCE 1
----
12345678
BOILEr SEQuENCE 2
----
87654321
3.13.1-
PROGRAMMING
HEATING CONTROLLERS
WITH SINGLE BOILER
Per la regolazione / programmazione dei termoregolatori, si veda
libretto istruzioni allegato ai singoli termoregolatori. di seguito si
riportano i parametri programmati in fabbrica e pertanto “non
modificabili”.
Per quanto riguarda i parametri programmabili dall’utente in
base alle proprie esigenze, si rimanda al libretto istruzioni per
il responsabile dell’impianto.