42
( Num ) =
see key Par. 2.2
codE
dEScRIPtIoN
detected on Bmm
SoLutIoNS
01
SAFETY THERMOSTAT
Intervention of the safety thermostat
(10)
Press the release button on the panel and/or check that the thermostat
and its connections are not blocked, and make sure the INtc switches
are closed (position1)
04
BLOCK
No gas or failed burner ignition
check the gas supply or that the ignition/detection electrode is working
properly
(4)
.
05
FLAME LOSS
DURING
OPERATION.
check the detection electrode
06
HIGH TEMPERATURE
Boiler temperature too high
check pump operation and if needed
clean the exchanger
(24)
10
INTERNAL FAULT
11
Flame detection prior to ignition (flame
parasite)
12
HEATING SENSOR (11)
Heating sensor fault
Check the efficiency of the sensor (see table Res/Temp) (Par.4) or its
connections.
14
RETURN PROBE (if present)
Auxiliary
(SRR)
sensor interrupted
check the wiring, if needed replace the auxiliary sensor
(22)
15
INSUFFICIENT wATER
CIRCULATION
Primary circuit water circulation insuffi
-
cient (∆t > 40° C)
check pump operation and its speed - remove any obstructions in the
heating system
16
EXCHANGER
FREEZING ( 24 )
Exchanger freezing is detected If the heat-
ing sensor detects a temperature below
2° c, burner ignition is inhibited until the
sensor detects a temperature above 5°c.
disconnect the from the power supply, close the gas valve, defrost the
exchanger carefully.
4.6 - ERROR CODES
When the boiler detects a fault, the alarm symbol is displayed
on the screen with the relative error code and description.
You can reset the boiler by pressing
‘‘A’’ from HScP, or by pressing RESEt from Bcm.