background image

4

Installation

• Each appliance must have its own flue with 

a cross-section equal to or larger than the 

diameter of the flue gas exhaust pipe of the 

stove and no lower than declared.

•  There must never be two stoves, a fireplace 

and a stove or a stove and a woodburning 

cooker, etc. in the same environment, as the 

draught of one could hinder the draught of 

the other.

•  Collective ventilation ducts which can create 

a vacuum in the installation environment 

are not allowed, even if installed in adjacent 

environments communicating with the 

installation room.

•  It  is  forbidden  to  make  fixed  or  movable 

openings on the flue to connect appliances 

other than the one used.

•  It is forbidden to have other air ducts or pipes 

pass  through  the  inside  of  the  flue  even  if 

oversized.

•  It is recommended that the flue be equipped 

with a collection chamber for solid materials 

and condensation located underneath the 

flue inlet so that it can easily be opened and 

inspected from an airtight door.

•  When using flues with parallel outlets, raise 

the upwind chamber by one notch.

•  The  flue  pipe  must  respect  the  foreseen 

distances from combustible materials 

according to standards in force.

Chimney

The chimney must meet the following 

requirements:

• Have a cross-section and inner shape like 

that of the flue.

•  Have a useful outlet cross-section no less 

than double that of the flue.

• The chimney coming out of the roof or in 

contact with the outside (for example for 

open lofts) must be covered with bricks and, 

in any case, well-insulated. 

• Be built in such a way so that rain, snow or 

foreign objects do not enter the flue and that 

winds in any direction and inclination do not 

hinder the exhaust of combustion products 

(windproof chimney).

• 

The chimney must be positioned to 

guarantee  sufficient  dispersion  and  dilution 

of combustion products and, in any case, 

outside  of  the  reflux  area.  The  different 

dimensions and shapes of this area depend 

on the inclination angle of the roof making it 

necessary to use the minimum heights (Fig. 

2).

• The chimney must be windproof and higher 

than the peak.

• Any buildings or other obstacles higher than 

the chimney must not be too close to it.

Fig. 2: chimney features

YES

NO

Flue gas exhaust

Combustion  products  must  be  exhausted 

through the roof.

There must be one exhaust system for the stove 

(there cannot be exhausts in a flue shared with 

other devices).

Flue gas must be exhausted through a pipe 

diameter 80 00 placed at the back. 

There must be a tee with a condensate 

collection cap at the start of the upright section.

The stove flue gas exhaust must be connected to 

the outside using steel or black pipes (resistant 

to 450°C and beyond) without obstructions.

The pipe must be airtight. The pipes must be 

sealed and insulated using materials resistant 

to at least 300°C (high temperature silicon or 

putty).

The horizontal sections 

can be up to 2m long

There can be up to three 90° elbows.

The vertical pipe can be inside or outside. 

The smoke duct must be appropriately 

Summary of Contents for .it 7

Page 1: ...it INSTALLATION AND MAINTENANCE INSTRUCTIONS 7 8 5 10 5...

Page 2: ...ntre Continuing to use the appliance in these conditions can cause fires or electrocutions If the supplementary air vent is not used only for ducted models check that the fan speed is at zero deactiva...

Page 3: ...intenance Failure to comply with the instructions in the manuals Use which does not comply with safety directives Installation which does not comply with standards in force in the country Installation...

Page 4: ...f the roof or in contact with the outside for example for open lofts must be covered with bricks and in any case well insulated Be built in such a way so that rain snow or foreign objects do not enter...

Page 5: ...guarantee regular combustion and proper environmental well being Make sure that the room where the stove is installed is sufficiently aerated The outdoor air inlet must communicate with the stove and...

Page 6: ...exhaust pipe Pellet tank capacity Autonomy Rated electric absorption at ignition Weight Dimensions LxWxH it 7 kW kW kg h mm Litres kg h W kg mm 6 97 2 84 6 42 2 64 1 4 0 6 92 70 92 06 80 20 13 22 9 1...

Page 7: ...connected to an earthed socket if the supplied cable is not long enough to reach the closest socket use a suitable extension cord Safety distances for fire protection The stove must be installed whil...

Page 8: ...d outside is 4 Pa Fig 9 distances from walls Instructions to install the flame protection Fig 12 lifting the flame protection Fig 13 flame protection rotation Fig 14 removing the flame protection Fig...

Page 9: ...riods of time the tank must be emptied from any residual fuel Parameter Diameter D Length L Water content M Ashes A 32 Mechanical durability DU Fine particles 3 15 mm Additives Lower Calorific Value Q...

Page 10: ...with that described in the standard UNI EN 14961 2 Press the ignition switch at the back of the stove the display will read OFF Ignition Press the key for 2 seconds After a few seconds the flue gas ex...

Page 11: ...ified by the technician the flue gas is modulated as follows flue gas exhaust motor set at maximum speed pellet loading gearmotor at minimum speed tangential heat exchange fan at maximum speed This pr...

Page 12: ...s It reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova Italy tel 39 0376 57001 telefax 39 0376 660556 info...

Reviews: