TECHNICAL DATA
Operating conditions:
(1) Cooling: Outdoor air temperature 35°C; inlet/outlet water temperature 23/18 °C.
(2) Cooling: Outdoor air temperature 35°C; inlet/outlet water temperature 12/ 7°C.
(3) Heating: Outdoor air temperature 7°C DB 6°C WB; inlet/outlet water temperature 30/35°C.
(4) Heating: Outdoor air temperature 7°C DB 6°C WB; inlet/outlet temperature 40/45°C.
(5) Cooling: Water temperature inlet/outlet 7/12°C.
(6) Heating: in average climate condition; T
biv
=-7°C; water temperature inlet/outlet 30/35°C.
(7)
Calculated for a decrease of the water temperature of the plant with 10°C with a defrosting cycle of 6 minutes.
(8)
Sound power:heating mode condition (3); the value is determined respecting the measurements taken in accordance with the regulations UNI EN ISO 9614-2, in
compliant with the Eurovent certification.
(9) Sound pressure: level obtained with internal measurements made in accordance with ISO 3744: 2010.
(10) Packaging height including the pallet: in particular, the pallet height, for the models HP_OWER ONE 70-90 is 117mm, and for the models HP_OWER ONE 120
is 126mm.
And for the models HP_OWER ONE 140-160 is 170 mm.
(*) activating the Max Hz function.
The Power inputs include all circuit components such as fan motors, pumps, valves and controller, the test data is obtained according to EN 14511: 2013.
TECHNICAL CHARACTERISTICS
Unit
HP_OWER ONE Model
70
90
120
140
160
Electrical data
Power supply
230V/1/50Hz
400V/3P+N+T/50Hz
Max. power input
kW
3,3
4,8
6,1
7,7
8,1
Max cue current input
A
9,3
13,7
17,4
21,4
7,7
Max current input
A
14,4
21,2
26,9
32,8
11,5
Cooling
Cooling capacity min/nom/max (1)
kW
3,65 / 6,87 / 7,56*
4,65 / 8,52 / 9,12*
5,4 / 11,9 / 13,1*
6,7 / 13,8 / 15,2*
8,70 / 15,69 / 16,30*
Power input (1)
kW
1,69
2,18
2,65
2,93
3,20
EER (1)
W/W
4,06
3,91
4,49
4,70
4,90
Cooling capacity min/nom/max (2)
kW
2,32 / 5,07 / 5,58*
2,95 / 6,12 / 6,73*
3,27 / 8,49 / 9,6*
5,3 / 11,46 / 12,05*
6,30/ 14,64 / 16,00*
Power input (2)
kW
1,74
2,11
2,74
3,70
4,52
EER (2)
W/W
2,91
2,90
3,10
3,10
3,24
SEER (5)
W/W
3,59
3,61
4,73
4,51
4,77
Heating
Thermal capacity min/nom/max (3)
kW
2,78 / 6,57 / 7,23*
3,54 / 8,01 / 8,81*
4,69 / 12,1 / 12,7*
5,5 / 13,76 / 15,1*
7,10 / 15,21 / 15,90*
Power input (3)
kW
1,47
1,85
2,89
3,2
3,45
COP (3)
W/W
4,47
4,33
4,19
4,3
4,41
Thermal capacity min/nom/max (4)
kW
2,24 / 6,15 / 6,76*
2,85 / 7,92 / 8,71*
3,9 / 11,3 / 12,21*
5,5 / 13,55 / 14,9*
6,50 / 15,17 / 15,80*
Power input ( min/nom/max 4)
kW
1,83
2,40
3,32
4,04
4,38
COP (4)
W/W
3,36
3,31
3,41
3,35
3,46
SCOP (6)
W/W
3,84
3,83
4,31
4,01
4,07
Energy efficiency water at 35°C / 55°C
Classe
A++ / A+
A++ / A+
A++ / A++
A++ / A+
A++ / A+
Compressor
Type
Twin Rotary
DC Inverter
Twin Rotary
DC Inverter
Twin Rotary
DC Inverter
Twin Rotary
DC Inverter
Twin Rotary
DC Inverter
Refrigerant oil (type, quantity)
mL
ESTER OIL VG74,
ESTER OIL
ESTER OIL
ESTER OIL
ESTER OIL VG74,1400
Fan Motor
Type
DC Brushless
DC Brushless
DC Brushless
DC Brushless
DC Brushless
Number
1
1
1
2
2
Refrigerant
Type
R410A
R410A
R410A
R410A
R410A
Refrigerant charge
kg
2,05
1,9
3,35
4,3
4,5
Quantity of CO2 equivalent
ton
4,28
3,97
6,99
8,98
9,40
Design pressure (high/low)
MPa
4,2 / 2,7
4,2 / 2,7
4,2 / 2,7
4,2 / 2,7
4,2 / 2,7
Internal heat
exchanger
Internal heat exchanger typer
Plates
Plates
Plates
Plates
Plates
Number
1
1
1
1
1
Water content
L
0,9
0,9
1,4
1,7
1,7
Hydraulic
circuit
Water content in hydraulic circuit
L
1,9
1,9
2,5
3,7
3,7
Max pressure of the hydronic kit
(safety valve calibration)
Bar
6
6
6
6
6
Expansion vessel
L
1
1
1
2
2
Hydraulic connections
inch
1” M
1” M
1” M
1” M
1” M
Minimum water content in the plant
L
31
37
51
69
88
Circulator
Water flow (3)
m3/h
1,13
1,38
2,08
2,37
2,62
Load losses on user’s heat exchanger
kPa
44,6
34,5
34,2
63,4
52,9
Nominal capacity (3)
kW
0,045
0,045
0,075
0,14
0,14
Max capacity
kW
0,045
0,045
0,075
0,14
0,14
Max current input of the circulator
A
0,44
0,44
0,6
1,10
1,10
Energy Efficiency Index (EEI)
≤ 0,20
≤ 0,20
≤ 0,21
≤ 0,23
≤ 0,23
Noise level
Sound power (8)
dB(A)
63,5
64
65
67,5
68
Sound pressure level at a distance of
dB(A)
49,4
49,9
50,4
52,5
52,7
Sound pressure level at a distance of
dB(A)
32,3
32,8
33,7
36,1
36,6
Dimension and
weight
Length
mm
925
925
1047
1060
1060
Width
mm
380
380
465
455
455
Height
mm
785
785
913
1405
1405
Packaging dimensions (LxHxW) (10)
mm
995 x 944 x 415
995 x 944 x 415
1120 x 1080 x 520
1125x1675x690
1125x1675x690
Shipping weight
kg
71,4
71,4
102
126
137
Weight in operation
kg
67
67,5
97
119
130
Summary of Contents for HP OWER ONE 70
Page 1: ...User s and Installer s Manual 70 90 120 140 160 ONE...
Page 32: ...32...
Page 33: ...33...
Page 40: ...40 17 REGISTER OF OPERATIONS OF MAINTENANCE...
Page 41: ...41 4 5...
Page 42: ...a...
Page 43: ...a...