Wired controller DIP Switch Introductions:
-
on the backside of the wired controller
Code
ON OFF
(Default)
1
External control signal valid
External control signal NOT valid
2
0~10V control signal valid
On/Off control signal valid
1). ON/OFF control signal
When the signal is on (closed), the Heat Pump can work. The running mode will be decided by the
setting of the wired controller. The heat pump will not monitor the setting temperature of the wired
controller.
If the signal is off (open), the Heat Pump can’t work.
But if there is domestic hot water requirement the domestic hot water will not be affected by the
external signal. It will always work as per the setting of wired controller of the heat pump.
2). 0~10V voltage control signal
The external controller gives a signal of 0 to +10V, the heat pump will produce water with different
temperature according to a voltage-water temperature table. Once this control method is in force, the
external signal will control the setting outlet temperature of space heating/cooling, the temperature
setting of the wire controller is not in force anymore.
This control signal is for space heating and space cooling modes.
Voltage
‐
Water
temperature
table
for
space
heating
mode
Signal (Input
Voltage)
Setting water outlet
temp.
Signal (Input Voltage)
Setting water outlet
temp.
0V Waiting
0.5V
22
°
C
5.5V
42
°
C
1.0V
24
°
C
6.0V
44
°
C
1.5V
26
°
C
6.5V
46
°
C
2.0V
28
°
C
7.0V
48
°
C
2.5V
30
°
C
7.5V
50
°
C
3.0V
32
°
C
8.0V
52
°
C
3.5V
34
°
C
8.5V
54
°
C
4.0V
36
°
C
9.0V
56
°
C
4.5V
38
°
C
9.5V
58
°
C
5.0V
40
°
C
10.0V
60
°
C