background image

35

4.4 - OPERATION OF THE

BOILER

To ascertain that the form and the dimension of
the burner flame, which we estimate very
important, are the correct ones for the good
operation of the boiler, it is suggested to make
a visual inspection of the furnace at least one
month after the first lighting.
The furnace cylinder shall show a homogeneous
coloration for all of its length to demonstrate
that the flame reverses in proximity of the blind
bottom.
Contrarily, a furnace that underlines a clean
distinction of colour among two zones (the
anterior part clearer than the rear part), it would
be the typical example of a flame of inadequate
length, for which the adjustment of the burner,
to avoid located overheatings, with consequent
probable serious damages, needs to be
immediately revised.
Similarly, the state of the exchange surfaces on
the water side, where possible, i.e. on the boi-
lers beginning from the model ELL 1100,

standard equipped with inspection hand  holes,
and in the case the presence of limestone,
sludges or deposits is found, the opportune
provisions to seek of it and to eliminate its causes
must be taken.
Such control must be effected within the first
months of exercise of the boiler, in any case
compulsorily to the first stop of the heating
system, at the end of the heating season or on
the occasion of standstills for other extraordinary
interventions, particularly in the case of heating
systems with large water content.
The HIGH EFFICIENCY ELLPREX boilers are
forseen to operate with a return water
temperature never below 54 °C when opera-
ted on light oil, and never below 59 °C when
operated on gas, to avoid (or, at least, to
reduce) the smoke acid condensation
phenomenon, which can be the reason of a
premature deterioration of the steel boiler body.
The working thermostat, pos. 32 of the panel
board, must be set at a temperature of
approximately 80 to 85 °C.

The room temperature will be compulsorily
adjusted through a mixing valve and,
eventually, an outer compensator.
To homogenise the water temperature, or avoid
as maximum as possible, returns into the boiler
at a temperature below 54 °C when operated on
oil, or 59°C when operated on  gas, a properly
dimensioned shunt pump must be fitted between
flow and return pipes of the boiler.
N.B.The metal sheet corrosion due to the acid
condensate is not covered by the guarantee
because it depends only from the operation of
the C.H. system.
The ELLPREX panel board is equipped with a
low temperature thermostat not allowing the
operation of the pump when the boiler
temperature is below 50 °C (protection against
cold starts).

4.5 - SWITCH OFF OF THE

BOILER

- Switch OFF the burner (switch No.12 to 0

position).

5.1 - GENERAL RULES

Before effecting any operation of cleaning or
maintenance, disconnect the boiler from the
electrical supply acting on the main switch onto
the panel board.
In case of failure or bad operation of the boiler,
switch it off, abstaining your self from any
attempt of reparation or direct intervention.
Exclusively address to professionally qualified
personnel.
The possible reparation of the boiler must be
effected by an authorized service center using
only original spare parts.
The non respect of the above can jeopardize

- Leave the pumps working up to when they are

not stopped by the minimum thermostat.

- Switch Off the power to the boiler panel board.
- If it is decided not to use the boiler for a

MAINTENANCE

the safety of the boiler.
To guarantee the efficiency of the boiler and
for its correct operation it is essential to submit
the boiler to an annual maintenance, through a
professionally qualified technician, according to
the indications of the manufacturer.
When it is decided not to use the boiler
anymore, the parts which can be potential
sources of danger shall be made harmless.
After a month of boiler operation, open the front
door and ascertain the smoke pipes are clean.
In case of a heavy dirtiness:
- Remove the turbulators from smoke pipes.

- Clean all the smoke pipes using the brush

delivered with the boiler.

- Open the two cleaning doors on the sides

of the smoke chamber and remove, with a
vacuum cleaner all the soot.

- Relocate the two cleaning doors and the

turbulators; then close the boiler front door
and check for soundness all around the
sealing rope.

- Then adjust the burner.
Note: With a burner properly adjusted only a
cleanup at the season end is necessary.

5

long period close also the gate valves of
the fuel.

5.2 - ORDINARY

MAINTENANCE

The boiler operating condition are very different
from one case to the other and depend on the
fuel used, on the adjustment of the burner, on
the number of starting, on the C.H. system
characteristics, etc. and for that reason it is
not possible to esthablish, in advance, the
frequence of the maintenances.
It is, then, necessary that the technician, who

performs the first cleaning, esthablish the
cleaning frequency on the base of the boiler
status.
Generally, we suggest the following frequency,
according to the fuel used:
- Gas fired boilers: once a year.
- Oil fired boilers: twice a year or more often

if there is reason to doubte of  their
adjustment.

In any case the local rules in force have to

complied with.
We suggest to shake the turbulators, without
removing them from the smoke tubes, at least
once an month of operation, not to allow the soot
blocking them and making them extremely diffi-
cult to be removed.
During the operations of ordinary maintenance
it will be necessary to brush the tube bundle  -
after the removal of the turbulators - and the
furnace and collect the soots through the

Summary of Contents for ELLPREX Series

Page 1: ...26739 01 13 rev 4 ELLPREX INSTALLATION USE AND SERVICING INSTRUCTION to be kept by the user...

Page 2: ...boiler house the safety devices the chimney the fuel supply lines the electrical installations and all the other local requirements and safety instructions Approvals The UNICAL boilers ELLPREX range h...

Page 3: ...ter systems BS 5546 Installation of gas hot water supplies for domestic purposes 2nd Family Gases BS 6644 Ventilation for gas appliances of rated input exceeding 60 kW HEALTH SAFETY DOCUMENT No 635 Th...

Page 4: ...2 7 3 Burner installation page 15 2 8 Connection of the sight glass to the burner via a cooling line page 16 2 9 Casing assembly page 16 STANDARD PANEL BOARD page 24 3 1 Panel board type 21057 functio...

Page 5: ...by a textile in mineral fiber For models from ELL 4500 to ELL 7000 the outer shell is insulated with a felt lamellar matress thick 50 mm protected by an alumi fig 1 1 2 WORKING PRINCIPLE The ELLPREX b...

Page 6: ...190 251 264 298 398 462 565 Water side pressure loss m w c 0 09 0 15 0 19 0 33 0 12 0 21 0 16 0 28 0 09 0 17 0 14 0 25 0 21 0 38 9 15 15 28 13 25 17 34 16 29 24 43 32 55 Smoke side pressure loss mm w...

Page 7: ...1122 1122 B mm 1605 1800 1995 1432 1432 1432 C mm 190 190 190 D mm 195 195 195 E mm F mm 190 190 190 G mm 765 765 765 H mm 480 480 480 1989 2184 2379 L mm 125 125 125 1540 1540 1540 M mm 298 298 298 N...

Page 8: ...H mm 595 595 640 640 690 690 2346 2686 2781 3151 3225 3545 L mm 180 180 75 75 75 75 1540 1540 1650 1650 1810 1810 M mm 461 461 561 561 661 662 N mm 330 670 510 880 670 990 O mm 500 500 550 550 700 700...

Page 9: ...G mm 1315 1535 1535 H mm 772 915 915 3835 3879 4279 L mm 115 144 144 1990 2271 2271 M mm 325 377 777 N mm 1100 1060 1060 O mm 1330 1280 1420 P mm 1620 1870 1870 Q mm 3200 3164 3564 R mm Nominal Outpu...

Page 10: ...00 3800 5000 4180 5500 4560 6000 4940 6500 5320 7000 3638 3 4838 7 4064 2 5421 8 4446 8 5914 4877 6506 2 5255 3 6989 2 5689 8 7590 5 6012 6012 7058 7058 7909 7909 0 70 0 85 0 80 1 05 0 95 1 15 1 00 1...

Page 11: ...ion is highly recommended To allow the cleaning of the smoke pipes in front of the boiler a clearance equal to the length of the boiler has to be available With the boiler door opened at 90 the distan...

Page 12: ...the entity of the reinstatement water to avoid inconvenients due to untreated water For that reason it is suggested to fit in the feeding line to the boiler a water meter for small capacities 2 5 2 C...

Page 13: ...le A Adjustment in vertical way it is possible only by introducing some washers of convenient thickness under the hinge on which the door rotates fig 17 B Adjustment in transversal way it is possible...

Page 14: ...L H side are normally used as rotating hinges from Right to Left whilst the two ones on the R H side are used as closing hinges Exactly the contrary will happen when the door is hinged on the R H side...

Page 15: ...0 970 270 270 ELLPREX 290 630 220 250 ELLPREX 170 240 180 250 2 7 1 CONFORMITY OFTHE BURNER All the burners equipping the ELLPREX boilers must be CE certificated and must conform to the following dire...

Page 16: ...REX 1850 30001 casing upper part ELLPREX 1850 30002 casing front part ELLPREX 2200 30003 casing rear part ELLPREX 2200 30004 casing upper part ELLPREX 2200 30002 casing front part ELLPREX 2650 30081 c...

Page 17: ...ion B Locate the side panels 3 and 4 with the lower bend inside the bottom L profiles and the upper bend in the seats of front and rear tube plates To determine which is the left and right panel ensur...

Page 18: ...ht panel ensure that the cable clamp plates are positioned facing toward the front edge Fit the four flathead screws 8 on the inner bend of the rear side panels 3b 4b C Open the combustion chamber doo...

Page 19: ...nd to the upper L profile To determine which is the left and right panel ensure that the cable clamp plates 5 are positioned facing toward the front edge C Open the combustion chamber door and fit the...

Page 20: ...e side panels 3a 3b 3c and 4a 4b 4c with the lower bend inside the bottom L profiles and hooking the upper bend to the upper L profile To determine which one of the front side panels is the left or th...

Page 21: ...les and hook them to the screws fitted to the upper square tube To determine which one of the front side panels is the left or the right ensure that the cable clamp plates 5 are positioned facing towa...

Page 22: ...thermostat 3 minimum thermostat 4 We recommend that the introduction of the sensors is made up to bottom of the bulb holder s To get a better contact introduce also the arcuated spring 6 and secure th...

Page 23: ...of the two side screws from the panel board rotate its cover towards the front and insert the cables and the capillaries of thermometer and thermostats through the slots on its base Insert the capill...

Page 24: ...een the switching points of the two double pole is 6 C not adjustable Theminimumthermostat accessiblethrough the opening of the panel board cover switches OFF the C H pump during the reacing of the st...

Page 25: ...er and flow are included in the supply the room sensors for the C H systems No 1 and No 2 are optionals The mixing valve and the relevant motor are not supplied by Unical When the room sensor is not f...

Page 26: ...G V 6 6 7 7 8 8 9 9 10 10 2nd stage Tm Minimum thermostat Ts High limit thermostat Vm2 Mixing valve for 2nd zone A Burner lockout warning lamp eventual B Hourmeter eventual 3 5 ELECTRICAL WIRING DIAGR...

Page 27: ...08 RELAY FUNC 1 00 30 C 90 C RELAY TEMP 1 30 C 2K 10K HYST RELAY 1 5K 00 03 RELAY FUNC 2 00 00 01 OFF ON SCREED 00 OFF See explanation SCREED PROGR RETURN Default IV Value range Designation HOTWATER...

Page 28: ...00 24 00 OUT TEMP DEL 1 0K 50K SLOPE OFFSET 5K 00 01 OFF ON B HEAT SINK 01 ON Exit level using RETURN Default IV Value range Designation HEATING CIRCUIT 1 00 04 HC FUNCTION 00 00 03 PUMP MODE 00 5 25...

Page 29: ...ensor code no required after input there is a restart of the controller RETURN end of INSTALLATION Start INSTALLATION Set value Save value and next value Start INSTALLATION Set value Save value and ne...

Page 30: ...02 OPTIMIZAT 00 0 00 3 00 h M OPT TIME 2 00 h 0 00 3 00 h ECONO OPTI 0 00 h 0000 9999 PC ENABLE 0000 Default IV Value range Designation HEATING CIRCUIT 2 MODE 5 C 40 C T ROOM DES 1 20 C 5 C 40 C T RO...

Page 31: ...Mo Tu We TH Fr 06 00 to 22 00 Sa Su 07 00 to 23 00 Value range Designation HEAT CIRCUIT 2 HEAT PROGRAM 1 FACTORY SETTING Mo Tu We TH Fr 06 00 to 08 00 16 00 to 22 00 Sa Su 07 00 to 23 00 HEAT PROGRAM...

Page 32: ...hydraulic schemas shown in the figs 35 36 are principle schemas in case of different system circuits contact please our after sale service dept which will supply you with all the necessary informatio...

Page 33: ...ponsibility of a specialized and well trained burner technician authorised by the burner manufacturer In that occasion a commissioning report has to be filled out POSITION OF THE CORE INSIDE THE TURBU...

Page 34: ...RSTCOMMISSIONING At the commissioning stage of the boiler a qualified technician has to perform the following checks Internal and external sound test of burner and fuel feeding pipe Adjustment of the...

Page 35: ...0 position 5 1 GENERAL RULES Before effecting any operation of cleaning or maintenance disconnect the boiler from the electrical supply acting on the main switch onto the panel board In case of failur...

Page 36: ...ty and control devices imposed by local requirements that cannot be attributed to the constructive geometry and or to the materials used and to the constructive technique and therefore they are not co...

Page 37: ...37 Notes...

Page 38: ...38 Notes...

Page 39: ...39 Notes...

Page 40: ...Unical AG declines any liability for the inaccuriaces that may appear due to errors in trascription or printing It also reserves the right to introduce those modifications to its products that it con...

Reviews: