Operating and mounting manual
(translation)
EV / EVF
_______________________________________________________________________________________________________
220.100.091-05
Page 3 /21
Version: 06/2017
TM 4474
Flange connection measures acc. to
DIN EN 1092-2 / ANSI
Flange DN
Flange ANSI
PN TÜV-
Report-no.
15
(5N)
1/2
20
(7N)
3/4
25
(10N)
1
32
(12N)
1 1/4
40
(15N)
1 1/2
50
(20N)
2
Test
Pressure
(*) PT
5 EV..NÜ..92/93
25
S7/99
X
X
X
O
O
O
PT 16
10 EV..NÜ..92/93
40
S7/99
X
X
X
O
O
-
PT 25
25 EV..NÜ..92/93(#)
40
S7/99
X
X
X
O
O
-
PT 40
40 EV..NÜ..92/93
40
S7/99
X
X
X
O
-
-
PT 40
(*)
Test pressure to perform leakage test "No FUNCTION TEST"
X
Type test acc.,
O
Acceptance test certificate 3.2 possible, - not available,
(#)
For liquefied gas in its liquid form according to DIN 32725
Threaded connection dimension
at DIN ISO 228-1
Connection G
PN
Class
TÜV-
Report-no.
1/2
(5)
3/4
(7)
1
(10)
1 1/4
(12)
1 1/2
(15)
2
(20)
Test
pressure
(*) PT
100-EVF...
100
900/1500
-
O O - - - -
PT 100
(*)
Test pressure to perform leakage test "No FUNCTION TEST"
X
Type test acc.,
O
Acceptance test certificate 3.2 possible, - not available,
Flange connection measures acc. to
DIN EN 1092-2 / ANSI
Flange DN
Flange ANSI
PN TÜV-
Report-no.
15
(5N)
1/2
20
(7N)
3/4
25
(10N)
1
32
(12N)
1 1/4
40
(15N)
1 1/2
50
(20N)
2
Test
Pressure
(*) PT
5 EVF..NÜ..92/93
40
S8/99
X
X
X
O
O
O
PT 16
10 EVF..NÜ..92/93
40
S8/99
X
X
X
O
O
-
PT 25
25 EVF..NÜ..92/93
40
S8/99
X
X
X
O
O
-
PT 40
40 EVF..NÜ..92/93
40
S8/99
X
X
X
O
-
-
PT 40
40 EVF..NH.Ü..
40
S8/99
X
X
X
-
-
-
PT 40
100
EVF..N..
100 -
- -
O(**)
- - - PT
100
(**)
Passage 12mm
(*)
Test pressure to perform leakage test "No FUNCTION TEST"
X
Type test acc.,
O
Acceptance test certificate 3.2 possible, - not available,
Voltage:
VDC 12 – 440 (–15% bis +10%)
VAC 24 – 500 (–15% bis +10%)
Protection type:
IP54 or IP65
Frequency:
40 – 60 Hz
Power:
10 – 4000W
Details to the electrical data can be found on the type signand the adeqaute operating instructions of
the solenoid valves.
1.2 Application
The UNI Geräte solenoid valve EV and EVF are used as automatic safety shut-off valves to secure, to
limit, shut-off and release Liquid gas heating installation and in steam boiler plant.
Qualified for fuel oil EL, M (EV) according to DIN 51603 and for liquid gas to DIN 61522 in liquid state
and other liquids having a viscosity rate up to 75mm²/s and for fuel oil S (EVF).
If used in other cases, the operator must carefully check if construction/design of valve, accessories
and materials are suitable for the new application. The range of application is subject to the
responsibility of the plant planner. The service life of the valve is 20 years.