UNI ACP Series Technical And Operational Manual Download Page 3

SECTION 1 

                          GENERAL 

AND SPECIFICATIONS 

                                     

1-1 INTRODUCTION 

 

   

The AC Power Source ACP series use state of the art PAM (Power Amplitude Modulation) 

technology to provide a pure and stable alternating current (A.C.) power to the loader at very 

low cost never achieved before. The model offers maximum rated power with Variable Voltage 

Variable Frequency for any output voltage 0 to 300VAC with single phase, at any frequency 

from 40 to 999Hz. It is not only suitable for commercial applications (47-63Hz), but also for 

avionics, marine and military applications at 400Hz.   

      The output voltage is a complete semiconductor variable type (booster amplification control 

type). The output frequency of 50Hz, 60Hz and 400Hz, which is used very frequently, is set with 

Frequency Selector Switch. Any frequency from 40 to 999Hz is to be selected using Push 

Wheel Digital Switch.   

    The cooling system for this model is a compulsory air-cooling type using cooling fin. The 

output voltage is down or the over load LED is lit when the cooling fin is over heated or the 

output is overloaded.   

   

 

OPTION

 : The variable frequency range from 1,000Hz to 3,000Hz is provided as a option. 

                            The desired frequency is to be set using the Volume Switch on front panel after   

Selector Switch is on SET, Digital Switch is on 999 and X1 & X10 is on X10.       

 

1-2 APPLIED STANDARDS 

 

 

ANSI (American National Standards Institute)

 

 

IEEE (Institute of Electrical and Electronic Engineers)   

 

K.S. (Korean Standards) 

 

1-3 ENVIRONMENTAL CONDITIONS 

 

 

Operating Temperature : 0 ~ 40

 

 

 

Installation Place : Indoor   

 

Relative Humidity : Less than 90 % (Non-Condensing) 

 

Altitude : Less than 1,000 Meters above the sea level 

Summary of Contents for ACP Series

Page 1: ...ATION MANUAL AC POWER SOURCE PAM Power Amplitude Modulation Type ACP SERIES ACP 200 200VA ACP 500 500VA ACP 1K 1 000VA ACP 2K 2 000VA ACP 3K 3 000VA ACP 5K 5 000VA ACP 10K 10 000VA UNISOURCE CORPORATI...

Page 2: ...ND FUNCTION 2 1 PHYSICAL STRUCTURE 2 2 EACH DEVICE S FUNCTION 2 3 OPERATION CONCEPT SECTION 3 OPERATION 3 1 PREPARATIONS BEFORE USE 3 2 ELECTRICAL CHECK 3 3 CAUTION FOR USERS 3 4 FRONT PANEL LAYOUT 3...

Page 3: ...sed very frequently is set with Frequency Selector Switch Any frequency from 40 to 999Hz is to be selected using Push Wheel Digital Switch The cooling system for this model is a compulsory air cooling...

Page 4: ...e 0 300V Option 0 500V 1Phase or 3Phase Load Regulator Less than 0 5 Current Limit L 1 3A H 0 66A L 3 33A H 1 66A L 6 67A H 3 33A L 13 3A H 6 67A L 20A H 10A L 33 3A H 16 6A L 66 6A H 33 3A Output Wav...

Page 5: ...vice converts alternating electric current AC into direct current DC and provides it to the Inverter section The direct current DC converted by rectifier circuit may include some ripple voltage The ri...

Page 6: ...rror and makes control circuit be controlled in safety free from overload voltage and noise input outside the device Digital Display Panel This device consists of display and operation switch and digi...

Page 7: ...les in the base and side of the machine so that the air flow goes on smoothly without closing air ventilation holes Do not place the machine to be exposed direct to the sun or eroded gas Do not place...

Page 8: ...this Technical and Operation Manual thoroughly and operate the machine according to the procedures in the manual The input power should be single phase AC 220V 60Hz The GROUND of the power line should...

Page 9: ...Switch should be at LOW up to 150V then the position should be at HI up to 300 over 150V The dual transformer is being used with this system since the frequency bandwidth is wide It should be at DOWN...

Page 10: ...LED displays the desired frequency then turn the Output Switch ON And then check if Output LED is lit If Output LED is lit please turn the Voltage Adjust MINE VR in clockwise by looking at Output Volt...

Page 11: ...on Resistance and Insulation Internal Pressure PCB and control circuit Semi conductor elements Filter and surge elements Condenser elements Temperature Rise Transformer and reactor elements less than...

Page 12: ...r Power TR PAM control type Input Rated voltage single phase 220V Voltage variation tolerance field 10 Frequency 60Hz Frequency variation tolerance field 5 Output Rated voltage single phase 0 300V Vol...

Page 13: ...SECTION 5 SERVICE 5 1 SCHEMATIC DIAGRAM...

Page 14: ...2 The Overload LED is lit when Power Switch is ON Power transistor is out 5W 0 1 resistor connected with power transistor emitter is out Replace power transistor Replace 5W 0 1 resistor 3 The system i...

Reviews: