UNI-Geräte E. Mangelmann Elektrotechnische Fabrik GmbH 

Holtumsweg 13, D-47652 Weeze, Tel. +49 2837/9134-0, Fax. +49 2837/1444 

www.uni-geraete.de  [email protected] 

Seite  2

 

/ 14 

TM 4021 

220.100.038-18 

 

 

Solenoid drive 

 

Series MG.., MG..A, MG..A..C (no explosion protection)

 

 

 

Series MG..Xn, MG..A..Xn, MG..A..C..Xn (with  - protection  
for the intended use in zone 2) in accordance with 
2014/34/EU (ATEX 95)) 

 

 

 

Special condition for safe use 

1.  Since  temperatures  higher  than  70°C  occur  at  the  cable  entry  and  higher  than  80°C  at  the  core 

junction,  this  equipment  must  be  additionally  marked  with  the  higher  temperature  (label  at  the  cable 
entry). Only a heat-resistant cable may be connected. 

2.  The  solenoid  actuators  need  to  be  protected  against  the  dangerous  consequences  of  short  circuits, 

earth  faults  and  overloads.  A  line-side  fuse  appropriate  to  the  rated  current  (max.  3xIB  acc.  to  IEC 
60127-2-1) is to chosen. A line-side motor circuit breaker - with short-circuit and thermal instantaneous 
tripping - is to be adjusted for the rated current. If the magnet has very low rated currents, fusing with 
the lowest current value in keeping with the stated IEC standard is sufficient.  
Protective devices must be of the kind that prevents automatic reconnection under fault conditions. The 
fusing rated voltage must match or exceed the specified nominal voltage of the solenoid actuator. The 
breaking capacity of the fuse link must match or exceed the maximum short-circuit current expected at 
the place of installation (usually 1500 A). 

3.  When  a  silicon  (or  silicon  containing)  connection  lead  is  used  or  if  the  connecting  lead  is  not 

scratch  proof  respectively,  this  has  to  be  protected  from  mechanical  damage  (e.g.  inetrrupted 
tube system with edge protection). 

4.   A maximum permissible ripple of 20% is valid for all magnets of dc-design. 

 

Electrical connection 

The  diameter  range  /  clamping  range  of  the  cable  gland  must  be  noted  and  adhered  to.  The  connection 
thread  of  the  cable  gland  amounts  up  to  30  Watt  M16x1,5  ,  from  40  Watt  M20  x  1,5.Where  a  flexible 
connecting line is used, insulated wire-end sleeves with plastic collars conforming to DIN 46228 part 4 are 
to  be  used.  The  voltage  supply  at  the  solenoid  actuator  must  lie  within  the  range  -15%  to  +10%.  The 
appropriate  circuit  diagram  can  be  obtained  from  the  connection  diagrams  at  the  end  of  these  operating 
instructions. To guarantee an IP65 degree of protection, the magnetic housing lid must be refitted carefully. 
Versions  supplied  with  a  connecting  cable  ex  works  are  ready  for  use,  i.e.  the  connection  compartment 
does not need to be opened again.  
The capacitors in the solenoid valve control TS800C must be discharged by an expert. 

 

CE-Identification 

The Council of the European Community passed common directives for the free movement of goods within 
the  European  Community,  which  determine  the  minimum  requirements  for  safety  and  health  protection. 
The CE-identification confirms, that the products correspond to the EC directives, i.e. are in agreement with 
the relevant, especially harmonized standards. 
Note concerning directive 2014/34/EU (explosion protection directive ATEX 95): 
The  solenoid  drives  (MG..Xn,  MG..A..Xn,  MG..A..C..Xn)  fulfil  the  relevant  requirements  of  directive 
2014/34/EU; therefore they have the CE-identification as per annex X of the  directive. The declaration of 
conformity is included. 
Note concerning directive 2014/30/EU (EMV-Directive): 
The  solenoid  drives  fulfil  the  requirements  of  the  specification  to  be  applied  of  the  product  families  con- 
cerning the industrial sector as well as the sectors of private housing, business and trading, as well as of 
small businesses. 
On using of AC- and DC-variants the user must provide a suitable mains filter (e.g. X-capacitor 47 nF) at 
the mains entrance to attenuate the physically caused line-related turn-off current of the solenoid. 
In  the  sense  of  the  EMV-directives  solenoid  drives  with  driving  elements  for  valves  are  not  regarded  as 
independently  operable  appliances  and  are  only  processed  further  by  expert  companies,  or  respectively 
installed into a machine. They must not be started up until it was determined that the machine, or respec- 
tively, the complete line, corresponds to the regulations of the EMV-directives. 
 

Summary of Contents for MG A C Series

Page 1: ...vocal identification and the year of build can be obtained from the type plate Solenoid actuators are electrotechnical components that are inoperative without the associated valve and also may not be operated for themselves alone For outdoor installations always use solenoid actuators with a IP65 rating and a rain cover Any solenoid actuators showing signs of damage are not to be installed and mus...

Page 2: ... a flexible connecting line is used insulated wire end sleeves with plastic collars conforming to DIN 46228 part 4 are to be used The voltage supply at the solenoid actuator must lie within the range 15 to 10 The appropriate circuit diagram can be obtained from the connection diagrams at the end of these operating instructions To guarantee an IP65 degree of protection the magnetic housing lid must...

Page 3: ...on 100 ED are permitted even in case of the most unfavourable ambient conditions permissible Danger During operation the solenoid drive may get hot Don t touch danger of injuries During operation it must be guaranteed that neither the maximum permitted ambient temperature or of the fluid nor the load limit excess voltage will be exceeded If necessary the solenoid drive is to be protected against o...

Page 4: ...20 Unscrew hexagonal head screw 900 and remove it including insulating bush 401 Remove cover of solenoid housing 105 from solenoid housing 103 Loosen and remove connecting bolt 501 Solenoid drive volume control butterfly valve Loosen protective cap 505 and remove including o ring 403 Remove cover of solenoid housing 105 from solenoid housing 103 Unscrew and remove hexagonal nut 901 Pos Item Descri...

Page 5: ...ith solenoid actuator volume control butterfly valve sole noid housing cover 105 O ring 403 and flat gasket 402 replace if necessary Assembly will be done in reverse order Screw torques of the connecting bolt 501 and the hexagonal head screw 900 Screw torque Item 501 900 Thread size 4 6 Nm M6 11 Nm M8 22 Nm M10 62 Nm M14 Solenoid drive MG MG Xn Typ MG P W Nominal current A 24 VDC 110 VDC 125 VDC 2...

Page 6: ...0 0 3 6 5 0 6 3 1 0 3 018 A1 900 70 38 2 9 8 2 0 6 4 1 0 3 3 9 0 3 3 8 0 3 8 2 0 6 3 9 0 3 018 A2 1200 70 11 0 6 5 5 0 3 5 2 0 3 5 0 0 3 11 0 6 5 2 0 3 019 A1 1200 120 11 1 1 5 5 0 6 5 2 0 5 5 0 0 5 11 1 1 5 2 0 5 019 A2 1500 90 14 0 8 6 8 0 4 6 5 0 4 6 3 0 4 14 0 8 6 5 0 4 019 A5 3 400 20 17 0 9 3 6 0 2 1 8 0 09 1 7 0 09 1 7 0 08 3 6 0 2 1 7 0 09 019 A5 4 400 50 17 2 1 3 6 0 5 1 8 0 23 1 7 0 2 1 ...

Page 7: ...ted control RKS 5 1500 Solenoid drive MG A Xn With category II3G only permitted outside the ex zone installation of RKS separate from valve in switch cabinet As per request of customer valve control RKS 5 1500 5 4000 for installation into switching cabinet Amb temp 20 C at 100 duty cycle stationary warmed up Amb temp 20 C at 0 duty cycle switch on moment values x factor 1 25 Solenoid drive MG A C ...

Page 8: ... 8 14 TM 4021 220 100 038 18 Solenoid drive Series MG MG A MG A C no explosion protection Series MG Xn MG A Xn MG A C Xn with protection for the intended use in zone 2 in accordance with 2014 34 EU ATEX 95 Standard solenoid drive IP 54 Standard solenoid drive IP 65 compound filled with casting resin Solenoid drive with Harting plug HAN 7D 8D optionally available ...

Page 9: ...ross sectional area of earthing conductors Cross sectional area of the phase conductor of the installation S mm Minimum cross sectional area of the associated protective conductor S mm S 16 S 16 S 35 16 S 35 0 5 S Protective conductor connection The solenoid actuator must always be integrated in the equipo tential bonding A connecting facility is available for this purpose in the vicinity of the m...

Page 10: ...4 005 3 260 64 014 A 016 A 2 220 56 008 010 A 012 A 4 370 50 018 A 019 A 020 A Solenoid drive MG Design VDC Design VAC 24 110 125 220 240 24 110 240 004 01 01 01 01 02 02 005 3 008 2 010 012 014 016 018 019 020 010 A5 04 04 05 04 04 04 012 A5 014 A5 016 A 016 A5 018 A1 018 A2 05 018 A5 04 019 A1 05 019 A2 019 A3 05 05 05 05 019 A5 04 04 04 04 04 019 A5 3 019 A5 4 020 A1 05 05 05 05 05 020 A2 020 A...

Page 11: ...lenoid drive MG Design VDC Design VAC 24 110 125 220 240 24 110 240 3803 06 06 0801 08 08 08 004 08 06 06 005 3 008 2 010 012 014 016 018 019 020 010 A5 03 03 09 03 03 03 012 A5 014 A5 016 A 016 A5 016A5C6 07 016A5 2C6 018 A1 03 03 09 03 03 03 018 A2 09 018 A5 03 019 A1 09 019 A2 019 A3 09 09 09 019 A5 03 03 03 03 03 019A5C6 07 019A5 2C9 019 A5 3 03 03 09 03 03 03 019 A5 4 020 A1 09 09 09 020 A2 0...

Page 12: ... drive MG Design VDC Design VAC 24 110 125 220 240 24 110 240 004 08 08 08 08 010 010 005 3 008 2 010 012 014 016 018 019 020 010 A5 03 03 09 03 03 03 012 A5 014 A5 016 A 016 A5 016A5C6 07 016A5 2C6 018 A1 03 03 09 03 03 03 018 A2 09 018 A5 03 019 A1 09 019 A2 019 A3 09 019 A5 03 03 03 03 019A5C6 07 019A5 2C9 019 A5 3 03 03 09 03 03 03 019 A5 4 020 A1 09 09 020 A2 020 A3 Connection plan with pin a...

Page 13: ...el 49 2837 9134 0 Fax 49 2837 1444 www uni geraete de info uni geraete de Seite 13 14 TM 4021 220 100 038 18 Solenoid drive Series MG MG A MG A C no explosion protection Series MG Xn MG A Xn MG A C Xn with protection for the intended use in zone 2 in accordance with 2014 34 EU ATEX 95 ...

Page 14: ...el 49 2837 9134 0 Fax 49 2837 1444 www uni geraete de info uni geraete de Seite 14 14 TM 4021 220 100 038 18 Solenoid drive Series MG MG A MG A C no explosion protection Series MG Xn MG A Xn MG A C Xn with protection for the intended use in zone 2 in accordance with 2014 34 EU ATEX 95 ...

Reviews: