Operating and mounting manual
(translation)
EVF
_______________________________________________________________________________________________________
220.100.112-07
Page 6 /13
Version: 12/2015
TM 3926
4.3 Marking
The type sign on the solenoid drive has the following information:
Fabricator
Valve type, nominal width, pressure and temperature indication, fitting position
Year of construction/ production no.
Product ID No.
Valve class and valve group acc.
to DIN EN 16678, DIN 3394-1
No. of relevant location
to 97/23/EC
Fluid group and test pressure PT
to 97/23/EC
Solenoid drive type
Electr.
performance
Voltage
Frequency
Protection
type
When using solenoid drives for x-protection zone 1 refer to information in the valid operating
instructions.
Refer also to section 10.0.
5.0 Installation
5.1
Warning of dangers during installation, operation and maintenance
DANGER!
Safe operation of the valve can only be guaranteed if it is installed, commissioned
and maintained by qualified personnel (see point 2.3 “Qualified staff“) correctly and
in observance of the warnings in this operating manual. Apart from that, the
operation safety order and the qualified use of tools and protection equipment must
be guaranteed. The operating instructions for the valve must be observed during all
work on or with the valve. Failure to observe these instructions may result in injury
or in damage to the valve or other installations.
When the valve is used as a final sealing element, a safety precaution e.g. blanking disc, blind flange,
etc., in accordance with the code of practice of the German Technical and Scientific Association for
Gas and Water (DVGW) is recommended during all repair work.
5.2 Installation
Apart from the general installation guidelines, the following points should be observed:
NOTICE!
Remove the flange covers.
The inside of the valve and the pipeline must be free from foreign particles.
Observe the installation position in relation to the flow direction, see markings
on the valve.
Centre gaskets between the flanges.
The connecting flanges must be aligned.
Ensure that none of the components is strained during installation.
The valve must not be used as a fixed point; it is supported by the pipework
system.
Protect valves from soiling, particularly during construction work.
Thermal expansion of the pipework must be equalized using compensators.
NOTICE!
Please observe the solenoid drive operating instructions (BTA).