Auto Regeneration Controller Model UK-2 Instruction Manual
9.2 Factory Setting
Table 9-1 shows the default setting of the parameter.
Table 9-1
Parameter factory setting
Set
Command
Description
Setting
Range
Initial
Value
_2rt
2ND ROOM TEMP (Target value of 2nd heater control)
10
〜
350 300K
_2rd
2ND READY TEMP
(The temperature to which 2nd stage will be cooled down.)
10
〜
350
20K
_2AL
2ND ALARM TEMP (Upper limit value during coolldown.)
10
〜
350
20K
_1rt
1ST ROOM TEMP (Target value of 1st heater control)
45
〜
350 300K
_1rd
1ST READY TEMP
(The temperature to which 1st stage will be cooled down.)
45
〜
350 130K
_1AL
1ST ALARM TEMP (Upper limit value during coolldown.)
45
〜
350 150K
oh
OVER HEAT TEMP
(The temperature at which an overheat protection alarm will be activated.)
45
〜
350 340K
_Pgt
PURGE TIME (Time for purging N2 after warm up.)
0
〜
999
5min
_tt
WAIT TIME (Wait timer after cooldown has been completed.)
0
〜
999
10min
_hP
HI PRESS (The highest limit of pressure that a Cryopum can be started.) 1
〜
99
67Pa
_LP
LOW PRESS
(The lowest limit of pressure that a Cryopum can be started.
)
1
〜
99
40Pa
_2ot
※
1
The temperature at which 2ND HEATER turns ON.
10
〜
350 150K
_2Pb
※
1
Proportional band of 2ND HEATER.
※
1
1
〜
100
2K
_2ti
※
1
Integral time of 2ND HEATER.
0
〜
999 150sec.
_2td
※
1
Derivative time of 2ND HEATER.
0
〜
300 24sec.
_2Pt
※
1
Proportion-cycle of 2ND HEATER.
0.1
〜
10.0
10.0sec.
_2Lt
※
1
Maximum energizing time of 2ND HEATER.
※
2
0
〜
300
45min
_1ot
※
1
The temperature at which 1ST HEATER turns ON.
45
〜
350 150K
_1Pb
※
1
Proportional band of 1ST HEATER
1
〜
100
2K
_1ti
※
1
Integral time of 1ST HEATER.
0
〜
999 150sec.
_1td
※
1
Derivative time of 1ST HEATER.
0
〜
300 24sec.
_1Pt
※
1
Proportion-cycle of 1ST HEATER.
0.1
〜
10.0
10.0sec.
_1Lt
※
1
Maximum energizing time of 1ST HEATER.
※
2
0
〜
300
45min
ULVAC CRYOGENICS INCORPORATED
27
Summary of Contents for UK-2
Page 2: ......
Page 8: ...F 6 ULVAC CRYOGENICS INCORPORATED This page intentionally left blank ...
Page 10: ...IW 2 ULVAC CRYOGENICS INCORPORATED This page intentionally left blank ...
Page 46: ...CS 2 ULVAC CRYOGENICS INCORPORATED This page intentionally left blank ...
Page 48: ...Revision This page intentionally left blank R 2 ULVAC CRYOGENICS INCORPORATED ...