Connection with External Devices:
The table below gives the pin assignment in the connection with external devices.
* Connector for connection “I/O”: D-sub 15pin female (M2.6mm screw)
『
I/O
』
Description
Remarks
2
Output signal
Lo when actuated, 30VDC
MAX
, 50mA
MAX
, 70mW
3
Setpoint 1 actuating signal
Lo when actuated, 30VDC
MAX
, 50mA
MAX
, 70mW
4
Output signal
Emission Valid, HV check, etc
Lo when actuated, 30VDC
MAX
, 50mA
MAX
, 70mW
5
Input signal
Filament ON, Adjust, etc Actuated when shorted to GND
6
Input signal
Select Filament 1/2, etc Actuated when shorted to GND
7
Setpoint 3 actuating signal
Lo when actuated, 30VDC
MAX
, 50mA
MAX
, 70mW
8
Pressure signal
0 to 10 VDC
9
Signal GND
GND of pressure signal, burnout signal, setpoint, etc.
10
RS485 -
Serial communication RS485 – output
11
Setpoint 2 actuating signal
Lo when actuated, 30VDC
MAX
, 50mA
MAX
, 70mW
12
RS485 +
Serial communication RS485 + output
13
Input signal
Degas ON Actuated when shorted to GND
15
Signal GND
GND of pressure signal, burnout signal, setpoint, etc.
Case
FG
Frame ground
8.1.
Output signal
Lo when actuated, 30VDC
MAX
, 50mA
MAX
, 70mW
Fig.8-1 Output signal
PLC or computer
Internal 5V power supply
Internal
power supply
Display
A
1
2
B
3
4
GND
SETPOINT1
Em.Valid
C
5
6
ERROR
2
3
4
9,15