• PTXGI-1224 UVPhotoMax photo catalyst module.
• Four self tapping mounting screws P/N HD-PP-0104
• Two lamp mounting screws P/N HD-PP-0005
• One 10” non ozone UVGI lamp P/N AS-1013-1
• One 6 ft 2 conductor power cord P/N AS-IH-0005
• One Y cable for splitting power P/N EL-OH-0080
• One 24 VAC multi tap step down transformer P/N 94-041
• Two Wire nuts (Orange)P/N EL-PP-0012
• One duct board mounting plate P/N SM-IH-0018
• UVC warning label
• Replacement lamp log
sheet
• Warranty card
• Duct board sealing tape
• Product gasket
• Cotton glove
• Warning labels
Package Contents:
Safety Precautions:
It is recommended that this unit be installed and maintained by a trained technician.
WARNING:
UV Hazard. Always protect eyes from ultraviolet light. NEVER look at UV lamps in opera-
tion. Unplug or disconnect power before lamp replacement or servicing.
WARNING:
Severe eye damage or temporary blindness may occur.
WARNING:
DO NOT operate outside of air handler.
WARNING:
No openings should be allowed which would give direct line-of-sight to the UV light.
Note:
In the event of accidental breakage or replacement of the ultraviolet lamp, please ensure that
the lamp is disposed of in accordance with local and state environmental laws regarding fluorescent
lamps containing mercury.
Notice:
All wiring inside of the air handler in direct line of site of the UV lamp must be shielded with
aluminum foil tape or equivalent non-combustible material. When installing this unit, select a mount-
ing location that prevents ultraviolet light exposure to synthetic or other plastic components with
unknown resistance to ultraviolet light. Ultraviolet light may cause color shift or structural degrada-
tion of plastic internal components.
Also Included:
Installation:
Locate a section of duct that
will allow for the installation of
the purifier.
Typically this would be the
supply “exit” side plenum.
Metal tabs fold in,
use the flat as a tem-
plate. Cut a rectangle
4-3/4” W x 4-1/4” H.
Duct board plate
Important!
Adjust the purifier for the air
flow of the environment.
Disconnect power while performing installation
Air F
low
120
208
240
277
VAC
24 VA C
Common
Install transformer per local code. Typically
in the electronics area of the HVAC system.
Choose the proper incoming voltage. cap
any unused wires.
Route wires connect with
supplied wire nuts
Horizontal Install
Vertical Install
Steps:
1. Mechanically mount the product using
2
of
the 4 hex screws.
Note the white cover has two
mount tabs do not use those yet.
2. Install the lamp using supplied 2 screws. Hand
tighten only. Use cotton glove to remove and
finger prints or debris.
3. Make sure the adjustment lever is set to the
appropriate coverage area.
4. Install the white electronics enclose using the
remaining 2 hex screws.
5. Connect the 6 foot cord to the Y connector.
6. Plug each Y into the ports on the purifier.
7. One is on the white power head one is on the
metal base attached to the plenum.
2 X hex screws
diagonal, secures
base.
This product is designed to be powered on constantly. The service life for
the UVC lamp is 18,000 hours or approximately 2 years. The ionization
component does require maintenance and has an effective life of up
to 10 years. It is recommended that all installation and service be per-
formed by a licensed HVAC professional.
Metal Plenum:
Cut a 4” diameter circle.
Duct board:
Use supplied metal plate
Air Flow
Install base first
Then the lamp.
Step 4