20
“I”
integer variables (Modbus®: REGISTERS)
R/W
ULTRA
PURE
Modbus®
72
199
bF: Drain activation delay in standby
R/W
73
200
AC: Maximum time to measure level when refilling
R/W
74
201
Ad: Maximum time to measure high level
R/W
82
209
AE: Restart fan time in standby for integrated probe reading
R
Tab. 12.b
“D”
digital variables (Modbus®: COILS)
R/W
ULTRA PURE -
Modbus®
2
Just started flag
R
3
Humidifier ready to produce
R
4
Humidity set point reached
R
5
Green LED
R
6
Red LED
R
7
Yellow LED
R
8
Remote On/Off
R
9
Low level
R
10
High level
R
11
Aux level
R
12
Autotest completed
R
14
BMS serial in tLAN mode
R
15
TAM enabled
R
16
TAM reading
R
17
Terminal connected
R
18
Production in progress
R
19
Fill
R
20
Drain
R
21
Transducer 1
R
22
Transducer 2
R
23
Fan
R
24
Alarm relay
R
25
Auxiliary relay
R
26
Manual drain
R/W
27
Disable from serial
R/W
28
Reset hour counter
R/W
29
Reset alarms
R/W
30
Washing due to inactivity activated
R
31
Functional test performed
R
33
Unit of measure
R/W
34
Slave 1 online
R
35
Slave 2 online
R
36
Slave 3 online
R
37
Enable control from serial
R/W
38
Wash activation from serial
R/W
40
Slave 1 disabled
R
41
Slave 2 disabled
R
42
Slave 3 disabled
R
Tab. 12.c
12.2 Production control via network
To control production via a connection, configure the humidifier using
following parameters:
Digital 27, Digital 37 and Integer 60 (Modbus 188)
When the D37 is at 1, the humidifier excludes the external command
signals (external regulator or probes) and uses the value of Integer 60
(modbus 188) as like comand signal. The humidity production can be
managed in two modes:
To manage the production level in percentual mode:
•
Set D 37 = 1;
•
Set parameter A0 = 1 (Ultra Pure 20, Modbus 148, Proportional
Mode);
•
Set integer variable 60 Ultra Pure (188 Modbus) to the desired level
(0-1000 = 0-100.0%).
To manage the production with a humidity probe managed by the master:
•
Set D 37 = 1;
•
Set parameter A0 = 2 20, Modbus 148, Humidity probe Mode);
•
Set integer variable 60 (188 Modbus) to the desired level
(0-1000 = 0-100.0 rH%);
•
Set integer variable 52 (180 Modbus) to the desired humidity setpoint.
When the D37 is at 1, if the communication is lost for the seconds settled
by parameter C4, is generated the “Master Offline” alarm (see alarms
table) and the production stops.
Production is activated/deactivated via digital parameter D27 (see
parameter table).
If D27 = 1 the humidifier is disabled and production stops
if D27 = 0 the humidifier is enabled and production is activated.
D27 is independent from the state of D37.
12.3 Washing cycle activation via network
A washing cycle can be performed at any time by managing digital
variable 38.
Setting the variable to 1 will immediately activate a washing cycle, even
if the unit is in standby, and even if both automatic washing and washing
due to inactivity are disabled by their corresponding parameters.
The variable will keep the value 1 throughout the duration of the washing
cycle, and will automatically be reset at the end of the cycle.