background image

20

“I”

integer variables (Modbus®: REGISTERS)

R/W

ULTRA 

PURE

Modbus®

72

199

bF: Drain activation delay in standby

R/W

73

200

AC: Maximum time to measure level when refilling

R/W

74

201

Ad: Maximum time to measure high level

R/W

82

209

AE: Restart fan time in standby for integrated probe reading

R

Tab. 12.b 

“D”

digital variables (Modbus®: COILS)

R/W

ULTRA PURE - 

Modbus®

2

Just started flag

R

3

Humidifier ready to produce

R

4

Humidity set point reached

R

5

Green LED

R

6

Red LED

R

7

Yellow LED

R

8

Remote On/Off

R

9

Low level

R

10

High level

R

11

Aux level

R

12

Autotest completed

R

14

BMS serial in tLAN mode

R

15

TAM enabled

R

16

TAM reading

R

17

Terminal connected

R

18

Production in progress

R

19

Fill

R

20

Drain

R

21

Transducer 1

R

22

Transducer 2

R

23

Fan

R

24

Alarm relay

R

25

Auxiliary relay

R

26

Manual drain

R/W

27

Disable from serial

R/W

28

Reset hour counter

R/W

29

Reset alarms

R/W

30

Washing due to inactivity activated

R

31

Functional test performed

R

33

Unit of measure

R/W

34

Slave 1 online

R

35

Slave 2 online

R

36

Slave 3 online

R

37

Enable control from serial

R/W

38

Wash activation from serial

R/W

40

Slave 1 disabled

R

41

Slave 2 disabled

R

42

Slave 3 disabled

R

Tab. 12.c 

12.2  Production control via network 

To control production via a connection, configure the humidifier using 

following parameters:

Digital 27, Digital 37 and Integer 60 (Modbus 188)

When the D37 is at 1, the humidifier excludes the external command 

signals (external regulator or probes) and uses the value of Integer 60 

(modbus 188) as like comand signal. The humidity production can be 

managed in two modes:

To manage the production level in percentual mode:

• 

Set D 37 = 1; 

• 

Set parameter A0 = 1 (Ultra Pure 20,  Modbus 148, Proportional 

Mode);

• 

Set integer variable 60 Ultra Pure (188 Modbus) to the desired level 

     (0-1000 = 0-100.0%).

To manage the production with a humidity probe managed by the master:

• 

Set D 37 = 1; 

• 

Set parameter A0 = 2  20,  Modbus 148, Humidity probe Mode);

• 

Set integer variable 60 (188 Modbus) to the desired level    

     (0-1000 = 0-100.0 rH%);

• 

Set integer variable 52  (180 Modbus) to the desired humidity setpoint.

When the D37 is at 1, if the communication is lost for the seconds settled 

by parameter C4, is generated  the “Master Offline” alarm (see alarms 

table) and the production stops.

Production is activated/deactivated via digital parameter D27 (see 

parameter table).

If D27 = 1 the humidifier is disabled and production stops

if D27 = 0 the humidifier is enabled and production is activated.

D27 is independent from the state of D37.

12.3  Washing cycle activation via network

A washing cycle can be performed at any time by managing digital 

variable 38.

Setting the variable to 1 will immediately activate a washing cycle, even 

if the unit is in standby, and even if both automatic washing and washing 

due to inactivity are disabled by their corresponding parameters.

The variable will keep the value 1 throughout the duration of the washing 

cycle, and will automatically be reset at the end of the cycle.

Summary of Contents for pureMist

Page 1: ...NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT Engineering Manual Compact Ultrasonic Humidifier...

Page 2: ...r with the characteristics indicated in this manual must be used for water vapor production Alloperationsontheproductmustbecarriedoutaccordingtotheinstructions provided in this manual and on the label...

Page 3: ...2 Meaning of the symbols 12 6 3 Keypad 12 6 4 Main display 12 6 5 Display software release 12 7 CONFIGURATION PARAMETERS 13 7 1 Basic parameters 13 7 2 Advanced parameters 13 8 ALARMS 14 9 MAINTENANC...

Page 4: ...essories Wand Distributor Production Supply Temperature Electrical Rating Amp Max Weight Dimensions 1 1 2 2 Lbs Hr 33 8 104 F 115 V 60Hz 8 MFS 15 28lbs 12 x 9 x 11 Temp Hum Stat Diffuser Remote Displa...

Page 5: ...fier The following are contained inside fig 1 A IOM manual B Optional accessories if purchased ie distributor 50M filter plastic tube seperate box S S distributer seperate box 10 1 4 RED inlet water 3...

Page 6: ...3 8 push connect fitting Black Connect included RJ11 cord to display and plug into cabinet Terminate 3 wire color coded wired if optional temperature and humidity sensor is used to side of cabinet col...

Page 7: ...tially chemically or bacteriologically contaminated water is prohibited 2 2 Drain water Drain water from the humidifer is not toxic and can be drained into the approved drain system Attach 1 2 FPT fem...

Page 8: ...e elbow It s necessary to clean the filter with compressed air or running water periodically frequency depends on the environment in which the system is installed Features filter 50 micron H 5 D 2 3 6...

Page 9: ...ansducer management only for 2 transducer version OFF parallel management modulation of all 2 ON if demand is less than 50 it works only one transducer at a time alternately Tab 4 c 4 2 Power cable co...

Page 10: ...umper inputs M14 1 and M14 2 enable on the main board connect terminals M10 1 and M10 2 to a humidistat or a remote switch voltage free contact set parameter A0 0 to enable On Off operation see Chap 7...

Page 11: ...emptied automatically When in standby the fan stays on for 5 min 5 3 Autotest When humidifier is first started from off if enabled and humidity production is required a test cycle is run A complete f...

Page 12: ...set the values ENTER PRG for 2 seconds access the list of parameters inside the list of parameters select and confirm like Enter on a computer keyboard 6 4 Display software release 1 on power up the d...

Page 13: ...Maximum time to measure high level s 1 60 10 AE Restart fan time in standby for integrated probe reading min 0 120 10 AF Piezoelectric transducer working life h 0 9999 9999 with demineralised water b...

Page 14: ...ity probe signal cable yes humidification interrupted AUTO 3 slow flashes H_ Low humidity The signal from the probe indi cates humidity less than 20 rH Check humidity probe signal cable yes humidifica...

Page 15: ...iew the inside of the tank Scale build up on the surface of the piezoelectric transducers Clean the inside of the tank and replace the transducers Tab 8 b These malfunctions can be avoided by carrying...

Page 16: ...cally to remove it 4 clean or replace the transducers by removing the screws see Fig 9 b after replacement test water tightness by filling the tank manually 5 reconnect the transducer power cables 6 r...

Page 17: ...17 10 GENERAL FEATURES AND MODELS 10 4 Version 115V Fig 10 c...

Page 18: ...ity at 20 C 0 50 S cm total hardness 0 25 mg l CaCO3 temporary hardness 0 15 mg l CaCO3 total quantity of dissolved solids cR depending on specific conductivity 1 dry residue at 180 C depending on spe...

Page 19: ...Inactivity time for washing on next start R W 32 159 Parameter b3 Washing time fill drain R W 33 160 Parameter b4 Start delay time R W 34 161 Parameter b5 Operating hours for CL alarm R W 35 162 Param...

Page 20: ...at 1 the humidifier excludes the external command signals external regulator or probes and uses the value of Integer 60 modbus 188 as like comand signal The humidity production can be managed in two...

Page 21: ...of a signal Y from an external device The type of signal can be selected between the following standards 0 to 10 Vdc 2 to 10 Vdc 0 to 20 mA 4 to 20 mA Maximum humidifier production corresponding to th...

Page 22: ...ituation is repeated alarm EP is activated which shuts down the unit If after a percentage of A8 set by parameter Ab default 70 the water is above the high level threshold atomised water production st...

Page 23: ...llowing fields Percentage request sent to the Master Fig 3 Operating hour counter Fig 4 resettable pressing UP DOWN for 5 seconds see parameter d3 Unit alarms Fig 5 means no alarms are present resetta...

Page 24: ...ctrical wiring from alarm relay output on the master to auxiliary input J17 on the slave and vice versa from alarm relay output on the slave to auxiliary input J17 on the master Main board Slave unit...

Page 25: ...Main Board Connections MASTER UNIT Connections M 11 TX RX GND GND 1 RS485 Supervisore ON OFF 4 Main Board Connections SLAVE UNIT Connections 2 3 6 4 7 5 1 8 ON M9 M 11 M 11 M 11 6 6 6 TLan 2 Supervis...

Page 26: ...Ultra Pure Systems 1855 E Southern Ave Mesa AZ 85204 800 729 5192 www ultrapureus com...

Reviews: