10.1 Ultrasound humidifier models for fan coils and electrical specifications
Electrical data (power supply voltages) of the various models, as well as their functional characteristics. Note that some models can be powered at different
voltages, obviously with different current and humidity production values.
power supply
model
humidity production
(2; 4)
(kg/h)
power
(2)
(W)
code
voltage
(1)
(V - type)
current
(2)
(A)
cable
(3)
(mm
2
)
wiring diagram (Fig.)
UP1.1
1.1pnd/hr
60
1
115 - 1~
0,6
1,5
10.b
UP2.2
2.2pnd/hr
110
1
115 - 1~
1,2
1,5
10.b
Tab. 1.a
(1) tolerance allowed on rated mains voltage: -15%, +10%;
(2) tolerance on rated values: +5%, -10% (EN 60335-1);
(3) recommended values, referring to PVC or rubber cable in a closed conduit, 20 m (65.6 ft) long; compliance with standards in force is always required;
(4) max instant rated water vapor production: average water vapor production may depend on external factors, such as: room temperature, water quality, water vapor distribution
system.
Important:
to avoid interference, keep power cables separate from probe cables.
10.2 Technical specifications
Technical specifications
UU models
UU01*
humidity outlet
connection dia. mm
40 (ensure an outlet area of 1100 mm2, e.g. 22 x 8 mm holes)
supply water
connection
G 1/8” F
temperature limits °C (°F)
1...40 (33.8....104)
pressure limits (MPa)
0,1...
0,4
(1...
4
bar)
specific conductivity at 20°C
0...50 μS/cm
total hardness
0...25 mg/l CaCO3
temporary hardness
0...15 mg/l CaCO3
total quantity of dissolved solids (cR)
depending on specific conductivity
(1)
dry residue at 180°C
depending on specific conductivity
(1)
iron + manganese
G 1/8” F
chlorides
1...40 (33.8....104)
silicon dioxide
0,1...0,6 (1...6 bar)
chlorine ions
0...50 μS/cm
calcium sulphate
0...25 mg/l CaCO3
instant flow-rate (l/min)
0...15 mg/l CaCO3
drain water
connection dia. mm (“)
10 mm
typical temperature °C (°F)
instant flow-rate (l/min)
7
environmental conditions
ambient operating temperature °C (°F)
1...45 (33.8...113)
ambient operating humidity (% rH)
10...80
storage temperature °C (°F)
-10...60 (14...140)
storage humidity (% rH)
5 to 95 (41 to 203)
index of protection
IP00
electronic controller
auxiliary voltage/frequency (V- Hz)
24 V / 50-60 Hz
maximum auxiliary power (VA)
3
control signal inputs (general features)
can be selected for the following signals: 0 to 10 Vdc, 2 to 10 Vdc, 0 to 20 mA, 4 to 20 mA,
input impedance: 20 kΩ with signals: 0 to 10 Vdc, 2 to 10 Vdc
100 Ω with signals: 0 to 20 mA, 4 to 20 mA
alarm relay outputs (general features)
24 V (max 3 W)
remote enabling signal input (general features)
voltage-free contact; max. resistance 100 Ω; Vmax= 5 Vdc; Imax= 5 mA
power
instant water vapour production
(2)
kg/h (lb/h)
see Tab. 11.a
power consumption at rated voltage (W)
see Tab. 11.a
Tab. 1.b
(1)
= in general C
R
≅
0,65 * σ
R,20 °C
; R
180
≅
0,93 * σ
R, 20 °C
(2 )
= average water vapour production is affected by factors such as: room temperature, water quality, water vapour distribution system
11. GENERAL FEATURES AND MODELS